1. Specification
Note:
1. All data are based on the following conditions:
-
Cooling Temperature : Indoor 26.7°C(80°F) DB / 19.4°C(67°F) WB
Outdoor 35°C(95°F) DB / 23.9°C(75°F) WB
- Heating Temperature : Indoor 21.1°C(70°F) DB / 15.6°C(60°F) WB
Outdoor 8.3°C(47°F) DB / 6.1°C(43°F) WB
- Piping Length : Interconnected Pipe Length = 7.5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national
code.
3. Due to our policy of innovation some specifications may be changed
without notification.
4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased(maximum 3dB(A)) owing to
ambient conditions during opration.
*: This temperature(-20 ~ -10℃) can be operated only when Low
Ambient Kit is installed.
Outdoor unit A2UW18GFA0
[LMU18CHV]
Testing Combination AMNW09GDBL1 * 2EA
Capacity
Cooling Min.~Rated~Max. kW
5
Min.~Rated~Max. Btu/h
17,000
Heating Min.~Rated~Max. kW
6.5
Min.~Rated~Max. Btu/h
22,000
Power Input Cooling Min.~Rated~Max. kW
1.31
Heating Min.~Rated~Max. kW
2.04
EER Btu/Wh
13
SEER / HSPF -
22.0/9.7
Power Supply V , Ø , Hz 208/230, 1, 60
Running Current Cooling Min.~Rated~Max. A5.9
Heating Min.~Rated~Max. A9.2
Starting Current Cooling Max. A -
Heating Max. A -
Wiring Connections
Power Supply Cable (included Earth) No. x mm2(AWG) 3C x 2.5 (12)
Power and Communication
Cable (included Earth) Outdoor ~ BD unit No. x mm2(AWG) -
Combination
Sum of Indoor Units Capacity kBtu/h 24
Number of Indoor Units EA 2
Number of BD Units EA -
Casing Color -Warm Gray
Dimensions W x H x D mm 870 × 655 × 320
W x H x D inch 34-1/4 x 25-25/32 x 12-19/32
Net Weight kg (lbs) 45 (99.2)
Compressor
Type -Twin Rotary
Model Model x No. GKT176MA x 1
Motor type -BLDC
Motor Output W x No. 1,500 (at 60Hz) x 1
Refrigerant
Type -R410A
Precharged Amount g (oz) 1,800 (63.5)
Chargeless-Pipe Length m (ft) 15(49.2)
Additional Charging Volume g/m (oz/ft) 20 (0.22)
Control -Electronic Expansion Valve
Refrigerant Oil Type -FVC68D
Charged volume cc x No. 670 x 1
Heat Exchanger (Row x Column x Fins per inch) x No. -(2 x 28 x 14) x 1
Fan Type -Propeller
Air Flow Rate m3/min x No. 50 x 1
Fan Motor Type BLDC
Output W x No. 85.4 x 1
Sound Pressure Level Cooling Rated dB(A) 50
Heating Rated dB(A) 52
Sound Power Level Cooling Rated dB(A) 62
Piping Connections Liquid Outer Dia. mm(inch) x No. Ø 6.35 (1/4) x 2
Gas Outer Dia. mm(inch) x No. Ø 9.52 (3/8) x 2
Piping Length
Total Piping Max. m (ft) 50 (164.0)
Main Piping Max. m (ft) -
Total Branch Piping Max. m (ft) -
Each Branch Piping Max. m (ft) 25 (82.0)
Maximum Height Difference Outdoor Unit ~ Indoor Unit Max. m (ft) 15 (49.2)
Indoor Unit ~ Indoor Unit Max. m (ft) 7.5 (24.6)
Operation Range
(Outdoor Temperature)
Cooling Min. ~ Max. ℃ DB (℉ DB) -18(-0.4) *~ 48 (118.4)
Heating Min. ~ Max. ℃ WB (℉ WB) -20 (-4.0) ~ 18 (64.4)