Programmable Logic Controller Installation Guide
XGF-AD4S
This installation guide provides simple function information ofPLC control. Please readcarefully
this data sheet and manuals before using products. Especially read safety precautions and
handle the products properly.
■ Meaning of warning and caution inscription
WARNING indicates a potentially hazardous situation which,
if not avoided, could result in death or serious injury.
CAUTION indicates a potentially hazardous situation which,
if not avoided, may result in minor or moderate injury.
It may also be used to alert against unsafe practices.
①Do not contact the terminals while the power is applied.
②Protect the product from being gone into by foreign metallic matter.
Do not manipulate the battery(charge, disassemble, hitting, short, soldering).
①Be sure to check the rated voltage and terminal arrangement before wiring.
②When wiring, tighten the screw of terminal block with the specified torque range.
③Do not install the flammable things on surroundings.
④Do not use the PLC in the environment of direct vibration.
⑤Except expert service staff, do not disassemble or fix or modify the product.
⑥Use the PLC in an environment that meets the general specifications contained
in this datasheet.
⑦Be sure that external load does not exceed the rating of output module.
When disposing of PLC and battery, treat it as industrial waste.
■To install, observe the below conditions.
℃
℃
5 ~ 95%RH, non-condensing
5 ~ 95%RH, non-condensing
5 Vibration
Resistance
IEC 61131-2
each
direction
for
X, Y, Z
■ For system configuration, the following version is necessary.
1) XGI CPU : V2.2 or above
2) XGK CPU : V2.1 or above
3) XGR CPU : V1.3 or above
4) XG5000 Software : V2.41 or above
■This is front part of the CPU. Refer to each name when driving the system. For more
information, refer to user manual.
■ Here describes the method to attach each product to the base or remove it.
1) Installing module
①Slide the upper part of module to fix
to the base, and then fit it to the base
by using the module fixed screw.
②Pull the upper part of module to check
if it is installed to the base completely.
2) Removing module
①Loosen the fixed screws of the upper
part of module from the base.
②Hold the module by both hands and press
the fixed hook of module thoroughly.
③By pressing the hook, pull the upper
part of module from the axis of the lower
part of module.
④By lifting the module upward, remove
the fixed projection of module from the fixing hole.
■Performance specifications are as follows.
Analog input
Range
DC 1~5V
DC 0~5V
DC 0~10V
DC 4~20mA
DC 0~20mA
Accuracy ±0.05% or less (when ambient temperature is 25 ℃)
Temperature coefficient: ±40ppm/℃(0.0040%/℃)
■ Precaution for wiring
1) Don’t let AC power line near to analog module’s external input signal line. With an
enough distance kept away between, it will be free from surge or inductive noise.
2) Cable shall be selected in due consideration of ambient temperature and allowable
current. More than AWG22 (0.3㎟) is recommended.
3) Don’t let the cable too close to hot device and material or in direct contact with oil for
long, which will cause damage or abnormal operation due to short-circuit.
4) Check the polarity when wiring the terminal.
5) Wiring with high-voltage line or power line may produce inductive hindrance causing
abnormal operation or defect.
■ Wiring examples
1) Voltage input
CH0
CH3
R
R
+
-
+
-
COM0
I0+
V0+ R
COM0
I3+
V3+
R
R
R
2) Current input
CH0
CH3
R
R
+
-
+
-
COM0
I0+
V0+ R
COM0
I3+
V3+
R
R
R
①Use a 2-core twisted shielded wire. AWG 22 is recommended for the cable
standard.
②Voltage input’s input resistance is 250 Ω (typ.).
③Current input’s input resistance is 1 MΩ (min.).
■ Warranty period
18 months after the production date.
■ Scope of Warranty
18-month warranty is available except:
1) The troubles caused by improper condition, environment or treatment except the
instructions of LS ELECTRIC.
2) The troubles caused by external devices
3) The troubles caused by remodeling or repairing based on the user’s own discretion.
4) The troubles caused by improper usage of the product
5) The troubles caused by thereason which exceeded theexpectation from science and
technology level when LS ELECTRIC manufactured the product
6) The troubles caused by natural disaster
■ Change in specifications
Product specifications are subject to change without notice due to continuous product
development and improvement.
LS ELECTRIC Co., Ltd. www.ls-electric.com 10310000680 V4.4 (2021.11)
•E-mail: automation@ls-electric.com
•Headquarter/Seoul Office
Tel: 82-2-2034-4033,4888,4703
•LS ELECTRIC Shanghai Office (China)
•LS ELECTRIC (Wuxi) Co., Ltd. (Wuxi, China)
•LS-ELECTRIC Vietnam Co., Ltd. (Hanoi, Vietnam)
•LS ELECTRIC Middle East FZE (Dubai, U.A.E.)
•LS ELECTRIC Europe B.V. (Hoofddorf, Netherlands)
•LS ELECTRIC Japan Co., Ltd. (Tokyo, Japan)
•LS ELECTRIC America Inc. (Chicago, USA)
•Factory: 56, Samseong 4-gil, Mokcheon-eup, Dongnam-gu, Cheonan-si, Chungcheongnam-
do, 31226, Korea
Applicable Support Software
Parts Name and Dimension (mm)
Installing / Removing Modules
Performance Specifications
0680