Lynxspring BW437-FCU-LX User manual

BW437-FCU-LX (Fan Coil Unit)
Wall Controller Quick Guide
www.lynxspring.com

BW437-FCU-LX Quick Guide
Disclaimer
Please read this manual before proceeding to install this controller or any other Onyxx LX device.
This manual applies to Onyxx LX UI software version 4.0 and higher and using firmware version 1.050 and higher.
All firmware updates must be done utilizing a Supplied USB-COM adapter or USB to MSTP converter cable.
Installations shall be made by a properly certified technician and respect all local mandatory codes and regulations.
Electronic controls are static sensitive devices: discharge yourself properly before manipulating and installing a controller.
Any short circuit or incorrect wiring may permanently damage the controller or the controlled equipment.
Double check all wiring before applying power.
If a control failure could lead to personal injury and/or loss of property, it becomes the responsibility of the installer to add safety
devices and/or alarm system to protect against failures.
www.lynxspring.com

BW437-FCU-LX Quick
Guide Symbol Definitions
The following table lists the symbols used in this document to denote certain conditions:
Symbol Definition
ATTENTION: Identifies information that requires special consideration
TIP: Identifies advice or hints for the user, often in terms of performing a task
REFERENCE _ INTERNAL: Identifies an additional source of information within the bookset.
Indicates a situation which, if not avoided, may result in equipment or work (data) on the system being
damaged or lost, or may result in the inability to properly operate the process.
Indicates a situation where users must observe precautions for handling electrostatic sensitive devices.
CAUTION: Indicates a potentially hazardous situation which, if not avoided, may result in minor or
moderate injury. It may also be used to alert against unsafe practices.
WARNING: Indicates a potentially hazardous situation which, if not avoided, could result in serious
injury or death.
www.lynxspring.com

BW437-FCU-LX Quick
Guide Contents Disclaimers……………………………………………………………………………………
Symbol's definition………………………………………………………………………………….
Description and model numbers……………………………………………………………………
Installation………………………………………………………………………………………
Mounting…………………………………….……………………………………….
Internal Jumper Settings………………………………………………………………………
Power Supply Connections…………………………………………………………………
I/O’s Wiring Instructions……………………………………………………………………
Interface………………………………………………………………………………………
Buttons…………………………………………….…………………………………….
Local LCD display…………………………………………………………………………
Using the menus……………………………………………………………………………….
Network configuration settings………………………………………………………………..
Quick setup menu…………………………………………………………………………
Applications, sequences and curves………………………………………………………….
Temperature control (Main PID loops)…………………………………………………………..
4 Pipes modulating 0-10 Vdc valves………………………………………………..……
4 Pipes modulating floating valves……………………………………………….………
4 Pipes on/off N.C. valves…………………………………………….……..…………
4 Pipes on/off N.O. valves………………………………………………………….…..
2 Pipes modulating 0-10 Vdc valves…………………………………………………..…
2 Pipes modulating floating valves…………………………………………………………
2 Pipes on/off N.C. valves…………………………………………………………….…
2 Pipes on/off N.O. valves………………………………………………………………
Single speed analog fan control………………………………………………………………..
3 speeds fan control……………………………………………………………………..
2 speeds fan control………………………………………………………………………
Single speed on/off fan control…………………………………………………………….
Reheat control………………………………………………………………………………
Service menu…………………………………………………………………………………
Test IO menu………………………………………………………………………………….
Object list……………………………………………………………………………………
Physical Inputs and Outputs…………………………………………………………………….
Analog Values……………………………………………………………………………….
Binary Values……………………………………………………………………………….
MultiStates Values……………………………………………………………………………….
RS-485 Network Guidelines……………………………………………………………………. ……
Specifications. ……………………………………………………………………. …………
p. 2
p. 3
p. 5
p. 8
p. 8
p. 10
p. 11
p. 12
p. 14
p. 14
p. 15
p. 16
p. 16
p. 17
p. 21
p. 21
p. 22
p. 23
p. 24
p. 25
p. 26
p. 27
p. 28
p. 29
p. 30
p. 31
p. 32
p. 33
p. 34
p. 36
p. 37
p. 38
p. 38
p. 39
p. 40
p. 41
p. 45
p. 49
www.lynxspring.com

BW437-FCU-LX Quick
Guide Models Available
BW437-FCU-LX
Base Model
BW437MH-FCU-LX
Base Model
w/PIR Motion Sensor
w/Humidity Sensor
BW437HC-FCU-LX
Base Model
w/Humidity Sensor
w/CO2 Sensor
BW437MHC-FCU-LX
Base Model
w/PIR Motion Sensor
w/Humidity Sensor
w/CO2 Sensor
BW437H-FCU-LX
Base Model Base
Model w/Humidity
Sensor
www.lynxspring.com

1. After unpacking your BW437-FCU-LX,
unscrew the retaining screw at the
bottom of the unit.
Installation
BW437-FCU-LX Mounting Instructions
2. Gently pull the cover away
from the base.
3. Pull the wires through the hole in
the base.
www.lynxspring.com

4. Connect the wires to the terminal,
referring to the chart inside the
base for the proper connections.
5. Before replacing the cover, make sure that you
have made any necessary modification to DIP
switch or jumper settings (see “Jumper Settings”).
Electronic controls are static sensitive devices; discharge yourself properly before manipulating and installing the device.
Short circuits or incorrect wiring may permanently damage the controller. Double check your wiring before applying power.
If acontrol failure could lead to personal injury and/or loss of property, the installer must add safety devices and/or alarm
systems to protect against failures.
Installation
BW437-FCU-LX Mounting Instructions
www.lynxspring.com

Installation
Internal Jumper Settings
Jumpers setting:
JP2 to select between BO7 or AO1:
Jumper up = Using BO7 (Low Speed Fan)
Jumper down = Using AO1 (ECM)
JP3 enables EOL (
120 Ohm )
:
Set jumpers to EOL position if this device is the
last node of the BACnet MS/TP network.
Jumper up = EOL not activated
Jumper down = EOL activated
MS/TP Network
Power Supply
www.lynxspring.com

Installation
Power Supply Connections
COM
24VAC
2 A
240-120/24VAC
Transformer
Add 24VAC transformer
when the power is not
supplied by the equipment
Always protect
your circuit with a
2 A fuse
Wire size based on VA rating and distance from Power source
The BW437 must be powered using a
Class 2, 24Vac transformer. When
powering from a 24Vac transformer, do not
ground either side of the transformer’s
secondary
For details on
grounding within control
panels, NFPA 79 and
UL508A provide the
required details.
WARNING: Internally, this device utilizes a half-wave rectifier and
therefore can only share the same AC power source with other half-
wave rectified devices. Sharing AC power with full wave rectified
devices is NOT recommended. If not properly wired, connecting
controllers on an MSTP BACnet network that have internal full wave
rectifier controllers with Onyxx LX half-wave controllers can have
adverse effect on network communications and in some cases would
result in damaging the Onyxx LX Controllers. Not properly wiring
the devices will void the warranty.
www.lynxspring.com

Installation
I/O Wiring Instructions
(R)
BO1
BO2
BO3
BO4
BO5
BO6
AO1/BO7
AO2
AO3
COM
AI1
AI2
A+
B-
AO4
COM
AI3
AI4
MS/TP
Supported Wire Size 28-16 AWG
RS-485 Wire Required for communications wiring
**recommend using pilot relays in any application utilizing Binary outputs
asswitching loads. **
www.lynxspring.com

Fan
3 speeds 2 speeds 1 speedVariable speed
Installation
I/O Wiring Instructions
BO1
BO2
BO3
BO4
BO5
BO6
AO1
AO2
AO3
AI1
AI2
AO4
AI3
AI4
2 pipes 4 pipes
On/Off On/OffFloating Floating
Heat NC valve
Heat NO valve
0-10v Aux/Reheat 0-10v Aux/Reheat
Open Cool/Heat
Close Cool/Heat
Cool NC valve
Cool NO valve
Open Cool
Close Cool
Heat NC valve
Heat NO valve
Open Heat
Close Heat
BO7
Cool/Heat Cool
Heat
2 pipes
0-10v Aux/Reheat
Alarm1 Alarm1 Alarm1 Alarm1
Alarm2 Alarm2 Alarm2 Alarm2
ChangeOver
Remote Sensor
4 pipes
SupplyT
Remote Sensor
0-10v Aux/Reheat
High High High
Medium
Low Low
Enable
Factory Program Terminal Functions
www.lynxspring.com

Parameters
Buttons
This section describes all the user adjustable interface functions of the BW437-FCU-LX
System Mode
Fan Mode
Up
Down
Hold for 3 seconds to
display the device Name
Hold for 7 seconds to
Enable or Disable PIR
state screen display. The
backlight display will
follow the PIR
movement detection for
a few minutes
Hold for 3 seconds to
display the device Model
Please note that attempting to adjust the Setpoint using the arrows, in unoccupied mode,
will automatically set the controller to Override / Day / Occupied mode
www.lynxspring.com

Display Icons
Local LCD
The signal icon indicates network connection status
Visible and fixed static = Online to both the BACnet MSTP network and the Strato Automation server
Blinking = Online to the BACnet MSTP network only
The lock icon indicates that setpoints have been locked from the network and cannot be modified by the thermostat keys
The wrench icon indicates that the device is in configuration mode
The warning icon indicates that there may be MSTP communication errors / problem (invalid frames)
Check wiring and use an MSTP sniffer tool if necessary
Displays whether the time is AM or PM
This line displays the room temperature or room setpoint
Use up and down arrows to temporarily modify the display setpoint
Displays the time (hh:mm) on the first line and the day of the week.
Icon to display night mode / unoccupied.
The water droplet icon indicates whether the dehumidification or humidification process is on and working
The segmented bar indicates whether the humidifier is at 33, 66 or 100% output capacity
The A indicates that the humidity function is in Automatic mode
The fan icon indicates that fan is on and working
The segmented bars indicates whether the fan in 1st, 2nd or 3rd speed
The A indicates that the Fan mode is in Automatic mode
The snowflake indicates that cooling process is on and working
The segmented bar indicates whether the cooling is at 33, 66 or 100% output capacity
The A indicates that the cooling function is in Automatic mode
The flame indicates that heating process is on and working
The segmented bar indicates whether the heating is at 33, 66 or 100% output capacity
The A indicates that the heating function is in Automatic mode
www.lynxspring.com

Using the menus
Network Configuration Settings
Set the BW437-FCU’s configuration in the “CONFIG MODE” directly on the BW437-FCU’s
screen using the keypad. To be able to do so, press simultaneously and
buttons for 3 seconds.
Press these PIN keys in sequence on the BW437-FCU’s keypad
CONFIG MODE will blink on the screen
Press the button to start cycling thought the configuration menus .
Press button to cycle through each parameter
Access any configuration menu by pressing on the menu’s display screen,
Using the and the button, adjust each digit to the desired value.
When done, press once more to confirm the new value.
Accept to SAVE by selecting YES and pressing
www.lynxspring.com

Access the “SETUP MENU” directly on the BW437FCU’s screen using the keypad. To be
able to do so, press simultaneously and buttons for 3 seconds.
Press these PIN keys in sequence on the BW437FCU’s keypad
SETUP will appear on the screen for 1 second
The first configurable object to be displayed in the SETUP menu is the PIPENUM
This is the one used for this next example
The object name and the actual configuration will blink alternatively on screen.
Note that the same steps apply to any other configurable object
Use the to change the object SETUP configuration
When the value is as wanted, press or to save the settings and switch to
the next object
To exit SETUP menu, scroll to the QUIT menu using
Press when YES is displayed
Using the menus
Setup menus (quick setup)
MSV52 BV75 MSV15 MSV58 MSV55 MSV54 MSV46 MSV47 MSV48 BV51
www.lynxspring.com

Using the menus
Setup menus (quick setup)
Object
Instance
Setup menu
Description
Options Function
MSV52 PipeNum Pipe number installed 2 Pipes
4 Pipes
Sets for a 2 pipes system where the same coil is used for heating and cooling
Sets for a 4 pipes system with separate heating and cooling coils
BV75 VALVCTL Valve motors control type On/Off
Floating
Sets the system for using either NO or NC on/off control valves
Sets the system for using floating type (Open/Neutral/Close) control valves
MSV15
SeqOper Control sequence of operation
Sets the main sequence of
operation of the controller. System
modes (MSV16) not supported will
be rejected
Cooling
Heating
Cool-Rt
Heat-Rt
Cl-Ht
Cl-Ht-R
See cooling only sequence below
See heating only sequence below
See cooling with reheat sequence below
See heating with reheat sequence below
See cooling / heating sequence below
See cooling / heating with reheat sequence below
www.lynxspring.com

Using the menus
Setup menus (quick setup)
Object
Instance
Setup menu
Description
Options Function
MSV58
Fan_Seq Control fan sequence L-M-H
L-H
L-M-H-A
L-H-A
On-Auto
Sets the system for regular 3 speeds fan control (Low
-Med-High)
Sets the system for 2 speeds fan control (Low
-High)
Sets the system for 3 speeds fan control with automatic mode (Low
-Med-High-Auto)
Sets the system for 2 speeds fan control with automatic mode (Low
-High-Auto)
Sets the system for single speed fan control (On
-Auto) On/Off or Modulating fan control
MSV55
Reheat Reheat type Basebrd
Coil
Sets the reheat device as a perimeter heating equipment like a baseboard (water or electric)
Sets the reheat device like an electric duct heater as a second stage of heat if needed
MSV54
Aux_CFG Auxiliary output configuration Reheat
Occ-NO
Occ-NC
Fan-NO
Fan-NC
Network
Sets the reheat output BO4 to be used as a control reheat output as per MSV15 & 55
Sets the device output BO4 to follow the local occupancy mode where Occ=Closed
Sets the device output BO4 to follow the local occupancy mode where Occ=Opened
Sets output BO4 to follow the local occupancy mode when fan is On Occ=Closed
Sets output BO4 to follow the local occupancy mode when fan is On Occ=Opened
Sets the device output BO4 to follow object BV14
Aux_cmd
www.lynxspring.com

Using the menus
Setup menus (quick setup)
Object
Instance
Setup menu
Description
Options Function
MSV46
AI1_CFG Analog input 1 configuration None
Rem NSB
Mot-NO
Mot-NC
Window
Sets the configuration of AI1 to none. Analog status of input can still be read via AI1 object
Sets the configuration of AI1 to use a remote time clock contact for occupancy
Sets the configuration of AI1 to use a remote PIR sensor for occupancy where Closed=Occ
Sets the configuration of AI1 to use a remote PIR sensor for occupancy
where Opened=Unocc
Sets the configuration of AI1 to use a remote window switch for automatic
Unocc mode monitor with BV35
MSV47
AI2_CFG Analog input 2 configuration None
DoorDry
Overrid
Filter
Service
Sets the configuration of AI2 to none. Analog status of input can still be read via AI2 object
Sets the configuration of AI2 to use a remote door switch for automatic
Unocc mode with AI1=Windows
Sets the configuration of AI2 to use a remote local override switch to by
-pass Unocc mode
Sets the configuration of AI2 to use a remote local pressure switch for filter status monitoring BV36
Sets the configuration of AI2 to use a remote local service contact for a local alarm display BV37
MSV48
AI3_CFG Analog input 3 configuration None
COC/NH
COC/NC
COS
SS
Sets the configuration of AI3 to none. Analog status of input can still be read via AI3 object
Sets the configuration of AI3 to use a remote Normally Heat
ChangeOverContact for a 2 pipes system
Sets the configuration of AI3 to use a remote Normally Cool
ChangeOverContact for a 2 pipes system
Sets the configuration of AI3 to use a remote 10K changeover sensor for a 2 pipes system via AV13 object
Sets the configuration of AI3 to use a remote monitoring 10K sensor via AV12 object
www.lynxspring.com

Application FCU –Typical Control Curves
Temperature control (PID loops)
PIDZoneHeat(Loop2) relates to Heating demand(AV21)
PIDZoneCool(Loop1) relates to Cooling demand(AV22)
HeatCoolPB - MSV65
PB°F (PB°C)
3°F (1.2°C)
4°F (1.7°C)
5°F (2.2°C)
6°F (2.8°C)
7°F (3.3°C)
8°F (3.9°C)
9°F (5.0°C)
10°F (5.6°C)
Default : 5°F (2.2°C)
SetpointDB - AV63
Min: 2°F (1°C)
Max: 5°F (2.5°C)
Default : Min: 2°F (1°C)
Direct
Action
Reverse
Action
Direct
Action
Reverse
Action
Deadband
2°F..5°F
Deadband
1°C..2.5°C
°C °C
°F
°F
% %
%%
63°F 65°F
64°F
www.lynxspring.com

Installation
I/O Wiring & Sequence
4 pipes –Modulating 0-10 VDC valves
4 pipes –modulating 0-10 VDC valves
Add 24VAC transformer when the power is not supplied
by the equipment
18
19
20
21
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1COM
24VAC
(R)
BO1
BO2
BO3
BO4
BO5
BO6
AO1/BO7
AO2
AO3
COM
AI1
AI2
A+
B-
AO4
COM
AI3
AI4
MS/TP
AO1
BO7
JP2
EOL
NONE
JP3
COOL
C24S
HEAT
C24S
Cooling demand > 25% for at least 180 seconds
Mode is Auto or Cool (MSV16)
Fan is running
Window contact is Closed (BV35 if used)
Analog (AO2) Analog (AO3)
Heating demand > 25% for at least 180 seconds
Mode is Auto or Heat (MSV16)
Fan is running
Window contact is Closed (BV35 if used)
Sequence of operation
Occupied Mode: Setpoints will revert to those defined by occupied cooling and heating setpoints.
Stand-by Mode (only available when PIR models are used): Setpoints will revert to those defined by stand-by
cooling and heating setpoints.
Unoccupied Mode: Setpoints will revert to those defined by unoccupied heating and cooling setpoints.
Occupied Override Mode: The system will revert to occupied mode for the duration determined by the “OvrTime” parameter
On a call for cooling: Cooling valve will modulate to maintain room temperature. Heating valve is closed.
On a call for heat: Heating valve will modulate to maintain room temperature. Cooling valve is closed.
www.lynxspring.com
Table of contents
Other Lynxspring Controllers manuals

Lynxspring
Lynxspring JENEsys Edge 534 User manual

Lynxspring
Lynxspring onyxx LX BZ122-LX User manual

Lynxspring
Lynxspring JENEsysONE JO-PC1 Installation instructions manual

Lynxspring
Lynxspring JENEsys Edge 100 User manual

Lynxspring
Lynxspring JENEsys Edge 534 User manual

Lynxspring
Lynxspring JENEsys Edge 414 User manual

Lynxspring
Lynxspring ONYXX LX BZ424-LX User manual

Lynxspring
Lynxspring JENEsys Edge 534 User manual

Lynxspring
Lynxspring onyxx LX BW437-RTU-LX User manual