[01] Lockout setting
Set Lock / Unlock of lockout setting.
SETTING VALUE DESCRIPTION INITIAL VALUE
Lock Lockout setting enable Lock
Unlock Lockout setting disable
Even when setting is ‘Lock’, it is available to move on to
each setting mode and confirm the setting value of each
setting parameter. In each setting parameter display, when
‘Lock’, ‘DATA (Locked)’ is indicated, when ‘Unlock’, ‘DATA’
is indicated.
[06] Angle offset
Set the position for 0% input entered to the unit. Setting
is performed by teach. Press set button to display the pre-
sent input value. With input value desired as 0% is entered,
pressing set button again enables to fix the setting. The
value entered the setting is displayed as ‘INPUT’ in meas-
uring mode.
[07] Angle span
Set the Angle span.
SETTING RANGE INITIAL VALUE
60 – 359.99 270.00
[10] Rotating direction
Set the rotating direction of input value.
SETTING VALUE DESCRIPTION
CW Clockwise
CCW Counter-clockwise
[14] 0 % input scaling
Set the display value of 0 % input.
SETTING RANGE INITIAL VALUE
-99999 – 999999 0
[15] 100 % input scaling
Set the display value of 100 % input.
SETTING RANGE INITIAL VALUE
-99999 – 999999 100.00
[16] Input decimal point
Set the decimal point position of [14] 0 % and [15] 100 %
input scaling.
SETTING VALUE
DESCRIPTION INITIAL VALUE
oooooo Decimal point: None
2 places of deci-
mals
ooooo.o Number of decimal places: 1
oooo.oo Number of decimal places: 2
ooo.ooo Number of decimal places: 3
oo.oooo Number of decimal places: 4
o.ooooo Number of decimal places: 5
[17] Output range
Set the range of output signal of the unit.
SETTING VALUE DESCRIPTION INITIAL VALUE
0 – 20 mA Output: 0 – 20 mA DC
0 – 20 mA-5 – +5 V Output: -5 – +5 V DC
-10 – +10 V Output: -10 – +10 V DC
When output range is changed, turn the power off, and
then set the output setting DIP SW on the side of the unit.
Setting is as follows. Output setting value is changed to ini-
tial value.
OUTPUT
RANGE
SW1
12345678
0 – 20 mA OFF ON OFF OFF OFF OFF ON OFF
-5 – +5 V OFF OFF ON OFF ON OFF OFF ON
-10 – +10 V OFF OFF ON OFF OFF ON OFF ON
[18] 0 % output setting
Set the 0 % output setting.
OUTPUT RANGE
SETTING RANGE
MIN. SPAN
INITIAL VALUE
0 – 20 mA 0.000 – 19.000 1.000 4.000
-5 – +5 V -5.000 – 4.750 0.250 -5.000
-10 – +10 V -10.000 – 9.000 1.000 -10.000
Set as follows.
[18] 0 % output setting < [19] 100 % output setting
The value is indicated by ‘OUTPUT’ at measuring mode.
[19] 100 % output setting
Set the 100 % output setting.
OUTPUT RANGE
SETTING RANGE
MIN. SPAN
INITIAL VALUE
0 – 20 mA 1.000 – 20.000 1.000 20.000
-5 – +5 V -4.750 – 5.000 0.250 5.000
-10 – +10 V -9.000 – 10.000 1.000 10.000
Set as follows.
[18] 0 % output setting < [19] 100 % output setting
The value is indicated by ‘OUTPUT’ at measuring mode.
[20] 0 % output scaling
Set the display value of [18] 0 % output setting.
SETTING RANGE INITIAL VALUE
-99999 – 999999 0.00
[21] 100 % output scaling
Set the display value of [19] 100 % output setting.
SETTING RANGE INITIAL VALUE
-99999 – 999999 100.00
[22] Output decimal point
Set decimal point position for [20] 0 % and [21] 100 % out-
put scaling.
SETTING VALUE
DESCRIPTION INITIAL VALUE
oooooo Decimal point: None
2 places of deci-
mals
ooooo.o Number of decimal places: 1
oooo.oo Number of decimal places: 2
ooo.ooo Number of decimal places: 3
oo.oooo Number of decimal places: 4
o.ooooo Number of decimal places: 5
[23] Overrange output <0 %
Set the output range for not greater than 0 %.
Available range between -5.00 to 0.00 %.
[24] Overrange output >100 %
Set the output range for not less than 100 %.
Available range between 100.00 to 105.00 %.