M-system M2XPA2 User manual

M2XPA2
P. 1 / 5EM-5060 Rev.6
FREQUENCY TRANSMITTER
(PC programmable) MODEL M2XPA2
INSTRUCTION MANUAL
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.
■ PACKAGE INCLUDES:
Signal conditioner (body + base socket) ...................... (1)
■ MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
To change I/O ranges, the JX Configurator Connection Kit
(model: JXCON) is required. For detailed information, refer
to the data sheet and instruction manual for the JXCON.
POINTS OF CAUTION
■ NONINCENDIVE APPROVAL OPTION
• This equipment is suitable for use in Class I, Div. 2, Groups
A, B, C and D or Non-Hazardous Locations only.
• WARNING! Before You Remove the Unit from Its Base
Socket or Mount It, Turn Off the Power Supply and Input
Signal for Safety.
• WARNING! – Explosion Hazard –
Substitution of Components May Impair Suitability for
Class I, Div. 2.
• WARNING! – Explosion Hazard –
Do Not Disconnect Equipment Unless Power Has Been
Switched Off or The Area is Known To Be Non-Hazard-
ous.
• The equipment was evaluated for use in the ambient tem-
perature and relative humidity as mentioned in ‘ENVI-
RONMENT’ section.
• The input and output wiring must be in accordance with
Class I, Div. 2 wiring methods and in accordance with the
authority having jurisdiction for use in these hazardous
locations.
■ CONFORMITY WITH EC DIRECTIVES OR UL
• This equipment is suitable for use in a Pollution Degree
2 environment and in Installation Category II, with the
maximum operating voltage of 300V.
Basic insulation is maintained between signal input and
output. The voltage across the input terminals is limited
to 70V or less. Prior to installation, check that the insula-
tion class of this unit satisfies the system requirements.
• Altitude up to 2000 meters
• The equipment must be mounted inside a panel.
• Risk of Electrical Shock: The front cover of the panel is to
be opened only by qualified service personnel.
• The equipment must be installed such that appropriate
clearance and creepage distances are maintained to con-
form to CE/UL requirements. Failure to observe these re-
quirements may invalidate the CE/UL conformance.
■ POWER INPUT RATING & OPERATIONAL RANGE
• Locate the power input rating marked on the product and
confirm its operational range as indicated below:
100 – 240V AC rating: 85 – 264V (90 – 264V for UL),
47 – 66 Hz, approx. 4 – 6VA
24V DC rating: 24V ±10%, approx. 3W
110V DC rating: 85 – 150V (110V ±10% for UL), approx. 3W
■ WARNING!
• To protect very delicate components contained inside
the unit against damage from static electricity, wear a
grounded wrist strap when handling them. If you do not
have one, touch both of your hands to a safely grounded
object or to a metal object.
• Ensure that the power supply and input signal are
switched off before you plug in or remove the unit.
■ ENVIRONMENT
• Indoor use
• When heavy dust or metal particles are present in the air,
install the unit inside proper housing with sufficient ven-
tilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -5 to +55°C
(23 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
• Be sure that the ventilation slits are not covered with ca-
bles, etc.
■ WIRING
• Do not install cables (power supply, input and output)
close to noise sources (relay drive cable, high frequency
line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■ AND ....
• The unit is designed to function as soon as power is sup-
plied, however, a warm up for 20 minutes is required for
satisfying complete performance described in the data
sheet.

M2XPA2
P. 2 / 5EM-5060 Rev.6
COMPONENT IDENTIFICATION
■ HOW TO OPEN THE LEFT SIDE COVER
Insert the tip of a minus driver into the openings indicated
with arrows in the figure, and pull up the cover.
■ HOW TO CLOSE THE LEFT SIDE COVER
Place the side A first and push in the parts B, gently not to
break the enclosure.
INSTALLATION
Loosen the fixing screw at the front of the unit in order to
separate the body from the base socket.
■ DIN RAIL MOUNTING
Set the base socket so that
its DIN rail adaptor is at
the bottom. Position the
upper hook at the rear side
of base socket on the DIN
rail and push in the lower.
When removing the socket,
push down the DIN rail
adaptor utilizing a minus
screwdriver and pull.
■ WALL MOUNTING
Refer to ‘EXTERNAL DI-
MENSIONS.’
Model
Body Base Socket
Connection
Diagram
Specifications
Fixing Screw
A
B
DIN Rail
35mm wide
Spring Loaded
DIN Rail Adaptor
EXTERNAL DIMENSIONS unit: mm (inch)
5
9
21.5 (.85)
70.5 (2.78)
86.7 (3.41)7.3 (.29) 15 (.59)
6 (.23)
59 (2.32)
DIN RAIL
35mm wide
[4 (.16)]
8–M3
SCREW
72 (2.83)
23 (.91)
2–4.2x5
(.17x.20)
MTG HOLE
6 (.24) deep
116.7 (4.59)
• When mounting, no extra space is needed between units.
14
8
12
14 13
4 (.16)

M2XPA2
P. 3 / 5EM-5060 Rev.6
TERMINAL CONNECTIONS
Connect the unit as in the diagram below or refer to the con-
nection diagram on the side of the unit.
CHECKING
1) Terminal wiring: Check that all cables are correctly con-
nected according to the connection diagram.
2) Check DIP switch setting.
3) Power input voltage: Check voltage across the terminal
13 – 14 with a multimeter.
4) Input: Check that the input voltage is within 0 – 100% of
full-scale.
5) Output: Check that the load resistance meets the de-
scribed specifications.
6) Status indicator LED: Check that it flashes in the nor-
mal patterns.
ZERO/SPAN ADJUSTMENTS
This unit is calibrated at the factory to meet the ordered
specifications, therefore you usually do not need any cali-
bration.
For matching the signal to a receiving instrument or in case
of regular calibration, fine zero and span adjustments can
be done to ±5% by pressing UP/DOWN switches enabled
with the zero/span selector switch. Calibrated values are
stored in the non-volatile memory, which will not be lost
even when you turn off power supply to the unit.
Zero and span are respectively set to 0% and 100% at the
factory.
■ FRONT VIEW (with cover open)
Zero/Span Selector
ZERO: UP/DOWN switches usable for zero adjust-
ment.
OFF: UP/DOWN switches unavailable.
SPAN: UP/DOWN switches usable for span adjust-
ment.
UP/DOWN Switches
UP: Pressing UP increases adjusted values.
DOWN: Pressing DOWN decreases adjusted values.
■ HOW TO CALIBRATE THE ZERO
Slide the Zero/Span Selector to the bottom position and
press UP or DOWN switch. Incrementing speed will be
doubled when you keep pressing a switch.
■ HOW TO CALIBRATE THE SPAN
Slide the Zero/Span Selector to the top position and press
UP or DOWN switch. Incrementing speed will be doubled
when you keep pressing a switch.
■ HOW TO RESET
After you calibrated manually with these switches, you
can reset them to its ex-factory state by pressing both UP/
DOWN switches at once.
■ ADJUSTMENT PROCEDURE
Use a signal source and measuring instruments of sufficient
accuracy level. Turn the power supply on and warm up for
more than 20 minutes.
1) ZERO: Apply 0% input. Slide the Zero/Span Selector
to the bottom position. Press UP or DOWN switch and
adjust output to 0%.
2) SPAN: Apply 100% input Slide the Zero/Span Selector
to the top position. Press UP or DOWN switch and ad-
just output to 100%.
3) Check ZERO adjustment again with 0% input.
4) The ZERO and SPAN adjustments are processed in
a digital processor, and therefore they do not interact.
However, if ZERO value is changed, repeat the above
procedure 1) – 3).
UP/DOWN Switches
The front cover cannot be opened to 180 deg.
when flush with neighboring units.
Configurator Jack
n FRONT VIEW (with cover open) n LEFT SIDE VIEW (with cover removed)
Status Indictor LED
Zero/Span Selector
Top: SPAN
Middle: OFF
Bottom: ZERO
Selector SW
SW3
HL
SW2
1234
HL
ON
OFF
SW1
SW4
HL
+
–
OUTPUT
8
9
12
1
5
4
CONFIGURATOR JACK
U(+)
V(–)
POWER
13
14
INPUT *1
*1. Input Connection Examples
1
5
4
+
1
5
4
1
5
4
nDry Contact
+
–
–
PWR
n2-Wire Current Pulse
nMechanical Contact
+
+
–
PWR
nVoltage Pulse
+
+
–
–
PWR
1
5
4
8
nRS-422 Line Driver Pulse
+
–
–
INPUT
+
–
PWR
8
5100Ω
+
–
INPUT
4

M2XPA2
P. 4 / 5EM-5060 Rev.6
ADJUSTING DETECTING LEVEL (voltage pulse, two-wire current pulse only)
Appropriate detecting level is determined according to the flow chart below.
START
Confirm the Sensitivity Scale in Table 1
below.
Assign the value in the following equation.
Detecting Level (V)*1=
DC Offset (V)*2×Sensitivity Scale
Set DIP SW to the DC coupling and adjust
the detecting level to the value calculated
above.
Set to 4V when the calculation result is
higher than 4V, set to -2V when it is lower
than -2V.
Set DIP SW to the capacitor
coupling and adjust the
detecting level to 0V.
DC coupled input sensing? No
Yes
*1.
*2.
Rounded off to two decimal places.
Divide a current input (mA) by 10 and convert it into voltage (V).
e.g. Offset = 10mA --> 10mA x 1/10 = 1V
Table 1
A specific sensitivity scale is applied according to the pulse
amplitude by setting up the DIP switch and PC Configura-
tion Software. The scaled input voltage is then compared to
the detecting level at -2.00 through +4.00V.
With DC coupling, the scaled maximum input voltage level
voltage must be higher than and the scaled minimum input
voltage level must be lower than the detecting level so that
the pulse state is accurately detected.
PULSE AMPLITUDE SENSITIVITY SCALE
50 – 100V p-p 1/20
25 – 50V p-p 1/10
10 – 25V p-p 1/5
5 – 10V p-p 1/2
1 – 5V p-p 1
0.5 – 1V p-p 1
0.1 – 0.5V p-p 1
• Setting Examples
Voltage Input (DC Offset = Pulse Amplitude / 2)
PULSE AMPLITUDE DETECTING
AMPLITUDE (Vp-p) RANGE (Vp-p) LEVEL (V)
100 50 – 100 2.5
50 25 – 50 2.5
30 25 – 50 1.5
25 10 – 25 2.5
15 10 – 25 1.5
10 5 – 10 2.5
7.5 5 – 10 1.9
5 1 – 5 2.5
3.5 1 – 5 1.75
2 1 – 5 1
1 0.5 – 1 0.5
0.5 0.1 – 0.5 0.25
Current Input (DC Offset = Pulse Amplitude / 2)
PULSE AMPLITUDE DETECTING
AMPLITUDE (mAp-p) RANGE (Vp-p) LEVEL (V)
16 (1.6Vp-p) 1 – 5 0.8
25 (2.5Vp-p) 1 – 5 1.25

M2XPA2
P. 5 / 5EM-5060 Rev.6
M-SYSTEM WARRANTY
M-System warrants such new M-System product which it manufactures to be free from defects in materials and workmanship during the 36-month period following the date that such
product was originally purchased if such product has been used under normal operating conditions and properly maintained, M-System’s sole liability, and purchaser’s exclusive
remedies, under this warranty are, at M-System’s option, the repair, replacement or refund of the purchase price of any M-System product which is defective under the terms of this
warranty. To submit a claim under this warranty, the purchaser must return, at its expense, the defective M-System product to the below address together with a copy of its original
sales invoice.
THIS IS THE ONLY WARRANTY APPLICABLE TO M-SYSTEM PRODUCT AND IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING ANY IMPLIED
WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. M-SYSTEM SHALL HAVE NO LIABILITY FOR CONSEQUENTIAL, INCIDENTAL OR
SPECIAL DAMAGES OF ANY KIND WHATSOEVER.
M-System Co., Ltd., 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN, Phone: (06) 6659-8201, Fax: (06) 6659-8510, E-mail: [email protected]
n DIP SWITCH SETTINGS
• Input Type Table 2
INPUT SW1 SW2 SW3
Open Collector H H H
Mechanical Contact H H H
Voltage Pulse H H H
Two-wire Current Pulse H H H
RS-422 Line Driver Pulse L L L
• Pulse Sensing Table 3
SENSING SW4-3
Capacitor Coupled OFF
DC Coupled ON
• Noise Filter Table 4
FILTER SW4-2 SW4-1
Large (time constant 50 ms)
ON OFF
Small (time constant 10 ms)
OFF ON
Without OFF OFF
UP/DOWN Switches
The front cover cannot be opened to 180 deg.
when flush with neighboring units.
Configurator Jack
n FRONT VIEW (with cover open) n LEFT SIDE VIEW (with cover removed)
Status Indictor LED
Zero/Span Selector
Top: SPAN
Middle: OFF
Bottom: ZERO
Selector SW
SW3
HL
SW2
1234
HL
ON
OFF
SW1
SW4
HL
STATUS INDICATOR LED
The M2XPA2 is provided with a status indicator LED which
flashes in different patterns indicating various status of its
CPU.
When it is functioning within normal parameters, the LED
flashes in a regular pattern of ON and OFF. The high levels
mean that the light is ON for 500 millisec., while the low
levels means OFF for 500 millisec. as shown in the figure
below.
When the unit is in an abnormality, it flashes in particular
patterns repeating approximately in 4 seconds.
MAINTENANCE
Regular calibration procedure is explained below:
■ CALIBRATION
Warm up the unit for at least 20 minutes. Apply 0%, 25%,
50%, 75% and 100% input signal. Check that the output
signal for the respective input signal remains within accu-
racy described in the data sheet. When the output is out of
tolerance, recalibrate the unit according to the “ADJUST-
MENT PROCEDURE” explained earlier.
CHANGING I/O TYPE & RANGE
Input type and range, and output type and range can be
programmed on the Configuration Software. Additionally,
when changing the input type, hardware settings are need-
ed as explained below.
Normal Mode
PC configuration complete; Operating normally
LED Patterns
Abnormal Mode
CPU Communication Error
LED Patterns
Table of contents
Other M-system Transmitter manuals

M-system
M-system 6BPA User manual

M-system
M-system 15TS User manual

M-system
M-system M3SXT User manual

M-system
M-system F2VF User manual

M-system
M-system M3LLC User manual

M-system
M-system F2TS User manual

M-system
M-system B5MS User manual

M-system
M-system M6DXU User manual

M-system
M-system B3HU2 User manual

M-system
M-system 10JT User manual

M-system
M-system M2LR User manual

M-system
M-system BVS User manual

M-system
M-system M3LU2 User manual

M-system
M-system W2VF User manual

M-system
M-system M5MS-5-R User manual

M-system
M-system Mini-M M2AC User manual

M-system
M-system W2RS1 User manual

M-system
M-system CTH User manual

M-system
M-system M5XU-1-R User manual

M-system
M-system M5CT User manual