EM-3118 Rev.4 P. 1 / 3
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
INSTRUCTION MANUAL
BEFORE USE ....
Thank you for choosing us. Before use, please check con-
tents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact our sales office or representatives.
■PACKAGE INCLUDES:
Signal conditioner
(body + base socket + input resistor)..................................(1)
Input resistor is provided only with current input type.
■MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
POINTS OF CAUTION
■CONFORMITY WITH EU DIRECTIVES
• The equipment must be mounted inside a panel.
• Insert noise filters for the signal input and output con-
nected to the unit. COSEL Model NAC-06-472 or equiva-
lent is recommended.
• The actual installation environments such as panel con-
figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated
in a panel system. The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures to ensure the CE conform-
ity.
• Install lightning surge protectors for those wires connect-
ed to remote locations.
■GENERAL PRECAUTIONS
• Before you remove the unit from its base socket or mount
it, turn off the power supply and input signal for safety.
■ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -5 to +55°C
(23 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
■WIRING
• Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■AND ....
• The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
COMPONENT IDENTIFICATION
Input Resistor
Body
Base Socket
Specifications
Zero Adj.
Span Adj.
Connection
Diagram
(side)
INSTALLATION
Pull out the body in pressing the clamps located at the top
and bottom of the unit for separate the body from the base
socket.
■DIN RAIL MOUNTING
DIN Rail
35mm wide
Spring Loaded
DIN Rail Adaptor
Set the base socket so that
its DIN rail adaptor is at
the bottom. Hang the upper
hook at the rear side of base
socket on the DIN rail and
push in the lower. When
removing the socket, push
down the DIN rail adaptor
utilizing a minus screwdriv-
er and pull.
■WALL MOUNTING
Refer to “EXTERNAL DIMENSIONS.”
SIGNAL TRANSMITTER
(isolated) MODEL BVS
BVS
EM-3118 Rev.4 P. 2 / 3
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
TERMINAL CONNECTIONS
Connect the unit as in the diagram below or refer to the connection diagram on the side of the unit.
When an input resistor is provided with the module, attach it together with input wiring to the input screw terminals.
Do not interconnect negative sides of input and output terminals (via grounding terminals e.g.) as they are not of the same
potential level.
Ground the terminal 4 for RFI protection if necessary. When grounded, dielectric strength between output signal line and
ground is of 500V DC, though it is of 500V AC when not grounded.
■EXTERNAL DIMENSIONS unit: mm (inch)
12
34
7
6
8
5
3 (.12)2 (.08)
26 (1.02) 107 (4.21) 26 (1.02)
93 (3.66)
15
(.59)
2–4.5 (.18)
HOLE
15 (.59) deep
DIN RAIL
35mm wide
[3.3 (.13)]
8–M3.5
SCREW
93 (3.66)
CLAMP
(top & bottom)
137 (5.39)
80 (3.15)
•When mounting, no extra space is needed between units.
7.8 (.31)
■CONNECTION DIAGRAM
1
2
4
+
–
INPUT R*
*Input shunt resistor attached for current input.
7
8
+
–
mA
MONITOR
+
–
+
–
6
5
LOAD
OUTPUT
24V DC
4 – 20mA DC
■TERMINAL ASSIGNMENTS unit: mm (inch)
34
7
6
8
5
12
INPUT RESISTOR
(model: REM)
19 (.75)
Input shunt resistor attached
for current input.
BVS
EM-3118 Rev.4 P. 3 / 3
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
WIRING INSTRUCTIONS
■SCREW TERMINAL
Torque: 0.8 N·m
CHECKING
1) Terminal wiring: Check that all cables are correctly con-
nected according to the connection diagram.
2) Input: Check that the input signal is within 0 – 100% of
full-scale.
3) Output: Check that the load is within the permissible
limit including wiring resistance.
Load Resistance (Ω) = Supply Voltage (V) – 12 (V)
0.02 (A)
(including leadwire resistance)
4) When you check the output signal, connect an ammeter
of which the internal resistance is of 10Ω max. to the
monitor terminals.
ADJUSTMENT PROCEDURE
This unit is calibrated at the factory to meet the ordered
specifications, therefore you usually do not need any cali-
bration.
For matching the signal to a receiving instrument or in case
of regular calibration, adjust the output as explained in the
following.
■HOW TO CALIBRATE THE OUTPUT SIGNAL
Use a signal source and measuring instruments of sufficient
accuracy level. Turn the power supply on and warm up for
more than 10 minutes.
1) ZERO: Apply 0% input and adjust output to 0%.
2) SPAN: Apply 100% input and adjust output to 100%.
3) Check ZERO adjustment again with 0% input.
4) When ZERO value is changed, repeat the above proce-
dure 1) – 3).
MAINTENANCE
Regular calibration procedure is explained below:
■CALIBRATION
Warm up the unit for at least 10 minutes. Apply 0%, 25%,
50%, 75% and 100% input signal. Check that the output
signal for the respective input signal remains within accu-
racy described in the data sheet. When the output is out of
tolerance, recalibrate the unit according to the “ADJUST-
MENT PROCEDURE” explained earlier.
LIGHTNING SURGE PROTECTION
We offer a series of lightning surge protector for protec-
tion against induced lightning surges. Please contact us to
choose appropriate models.

Other M-system Transmitter manuals

M-system MXLC User manual

M-system

M-system MXLC User manual

M-system 10SP User manual

M-system

M-system 10SP User manual

M-system M3LPA2 User manual

M-system

M-system M3LPA2 User manual

M-system Mini-M M2XU User manual

M-system

M-system Mini-M M2XU User manual

M-system 6BVS User manual

M-system

M-system 6BVS User manual

M-system KCNA User manual

M-system

M-system KCNA User manual

M-system M6SCTC User manual

M-system

M-system M6SCTC User manual

M-system 15TS User manual

M-system

M-system 15TS User manual

M-system M5VSH User manual

M-system

M-system M5VSH User manual

M-system M2VF User manual

M-system

M-system M2VF User manual

M-system Mini-M M2RS User manual

M-system

M-system Mini-M M2RS User manual

M-system JPA2 User manual

M-system

M-system JPA2 User manual

M-system F2VS User manual

M-system

M-system F2VS User manual

M-system VOS2T-R User manual

M-system

M-system VOS2T-R User manual

M-system Mini-MW Series User manual

M-system

M-system Mini-MW Series User manual

M-system 10JFT User manual

M-system

M-system 10JFT User manual

M-system W5PA User manual

M-system

M-system W5PA User manual

M-system M1EXS-2 User manual

M-system

M-system M1EXS-2 User manual

M-system M5XTR User manual

M-system

M-system M5XTR User manual

M-system F2VS User manual

M-system

M-system F2VS User manual

M-system WRS2 User manual

M-system

M-system WRS2 User manual

M-system 10VK User manual

M-system

M-system 10VK User manual

M-system W2CA User manual

M-system

M-system W2CA User manual

M-system 6TS1 User manual

M-system

M-system 6TS1 User manual

Popular Transmitter manuals by other brands

Johnson Controls GS3000 installation guide

Johnson Controls

Johnson Controls GS3000 installation guide

PR electrinics 2271V101-IN manual

PR electrinics

PR electrinics 2271V101-IN manual

Rosemount 8732E Quick installation guide

Rosemount

Rosemount 8732E Quick installation guide

AIV FMT 893 RDS instruction manual

AIV

AIV FMT 893 RDS instruction manual

Alutech AT-15 user manual

Alutech

Alutech AT-15 user manual

iT+ 30.3180.IT instruction manual

iT+

iT+ 30.3180.IT instruction manual

Radio Systems i.AM.Radio Transmitter Installation and operation

Radio Systems

Radio Systems i.AM.Radio Transmitter Installation and operation

Solt SQ100 user guide

Solt

Solt SQ100 user guide

Nice DTX600 Instructions and warnings for installation and use

Nice

Nice DTX600 Instructions and warnings for installation and use

Spektrum DX20 instruction manual

Spektrum

Spektrum DX20 instruction manual

Endress+Hauser Liquisys M CUM223 operating instructions

Endress+Hauser

Endress+Hauser Liquisys M CUM223 operating instructions

Magnetrol STI KOTRON 805 Installation and operating manual

Magnetrol

Magnetrol STI KOTRON 805 Installation and operating manual

Johnson Controls P-5219 manual

Johnson Controls

Johnson Controls P-5219 manual

EUTECH INSTRUMENTS ALPHA PH 800 PHORP CONTROLLERTRANSMITTER operating instructions

EUTECH INSTRUMENTS

EUTECH INSTRUMENTS ALPHA PH 800 PHORP CONTROLLERTRANSMITTER operating instructions

Loewe Klang Link 56222W00 quick start guide

Loewe

Loewe Klang Link 56222W00 quick start guide

Viewpro DDL24E-ESPB user manual

Viewpro

Viewpro DDL24E-ESPB user manual

ABB 266CRH instructions

ABB

ABB 266CRH instructions

technetix AIMA3000.FT5P Product user manual

technetix

technetix AIMA3000.FT5P Product user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.