GENERATORS IS 2.5
- 16 -
GB
4.0. ELECTRICALCONNECTIONS
4.1. Batteryconnection
To start off the unit an independent battery of 12V is
needed, capacity 18 - 30 Ah min.
It should be connected to the clamp of the generator as
shown in fig. 11 with cables of section 25 mm2up to
distancesof5metresandwithcablesofsection35mm2
for longer distances, and following the sequence of
operationsdescribedbelow:
- Firstconnect thepositivepole (+)ofthe batterytothe
terminalmarkedwiththesymbol(+)onthegenerator,
(thestarter).
- Thenconnectthenegativepole(-)ofthebatterytothe
terminalmarked withthesymbol(-)on thegenerator.
- Wipe the connections with special mineral grease to
protectagainstoxidationandcorrosion.
The generator includes an electronic device to
automaticallyrecharge the start-upbattery, giving10
A, at a voltage of 12 V, when fully charged.
IMPORTANT
Install the battery in a well-ventilated area, away
from the generator and from any device which
might produce heat or sparks.
Periodically check the state of the connections of
the terminals and the water level of the battery. If
the cables need to be disconnected, follow the
instructions for connection in reverse order.
Do not invert the poles of the connecting cables
since serious damage might be caused to the
generator and the battery.
Do not connect other loads to the battery.
Inordertoreducegalvaniccurrentstoaminimum,the(-
) of the battery of the electric generator should not be
connected to the (-) ofthe other batterieson board.
4.2. Control panel connection
Thisconnectioncanbemadethroughtheterminalboards
(fig.12,ref.1)usingthecablesprovidedalreadyconnected
to the control panel. The terminals to be used are those
marked no. 1 to no. 9 for the control cables. The earths
braidshouldbeconnectedtothefastonterminal(fig.12,
ref.2)insulatingthemcarefullyandusingapre-insulated
female faston. In making the connections it is important
to follow the diagram and the colours codes as indicate
(fig. 13). Fasten the cable with the provided plastic
support on the bail (fig. 12, ref. 3).
Thecontrolpanelcontains5LEDsforoperationandalarm
(fig.14,ref.1),anhourcounter(fig.14,ref.2)andthestart
and stop buttons (fig. 14, ref. 3/4/5).
For fixing the control panel is necessary to perforate as
showninfig.14.
IMPORTANT
The control panel is indispensable for operating
the unit and must be installed; do not use devices
othet than the control panel supplied with the unit
since they might not be compatible with the
generator.
Make the connections with the battery
disconnected.
CAUTION
The control panel is provided with a connecting
cable 10 metres long. This cable should not be
modified since it might cause the panel circuit to
functionincorrectly.
4.3. A.C.Connection
Thisconnectioncanbedonethroughthepowerterminal
board(fig.15,ref. 1)placedinsidethederivationbox.
This range includes the possibility of use both at 115V
50Hz - 120V 60Hz and 230V 50Hz - 240V 60Hz.
For this reason it is possible to make two types of
connection (and use), according to the following
configurations.
1- Parallelconfiguration:inthisconfigurationthereisa
singleoutputat115(120)VbetweenpointsP1andF2,
connectingtheoutputsofthealternator(P1,F1,P2,F2)
as shown in the diagram in fig. 16.
2- Serial connection; in this configuration it is possible
touseavoltageof230(240)VbetweenpointsP1and
F2, as shown in the diagram in fig. 17.
Inserialconnection,powercanbepickedupbothat110
(120)VbetweenpointsF1-F2andP1-P2andat220(240)
V between points P1and F2at the same time, as shown
in the diagram in fig. 18.
Itisalsopossibletofeedtwoseparatelines asshownin
fig. 19 on the outputs P1- F1and P2- F2.