
16
3.3 Electrical Connection
WARNING
When performing the following listed work steps, the applicable safety regulations as
specified by VDE 0104 and the “five safety rules” must be followed when setting up
and operating high voltage testing systems (see section 1.2).
The test site and the forbidden area must be made safe, fenced off and equipped with
indicator lamps and warning signs according to the regulations.
WARNING
Before performing the actual electrical connection of the tan Delta test attachment,
the VLF sine wave test system must be brought into position, secured and earthed
according to the work steps described in the manual.
Connection of the VLF sine wave test system to the mains may only be done after the
installation of the tan Delta test attachment.
CAUTION
The measuring sensors were functionally tested for alternating currents of up to
40 kVRMS. To avoid damage, tests with higher alternating current or any other
operating mode (e.g. interval operation, DC tests) may not be performed with the test
attachment installed!
As a rule, the connection on the test object should be made free of partial discharge.
Partial discharges at the connection point could falsify the measurment results.
Versions of
measurement set-up
For a measurement of the loss factor, only the measurement unit MDU needs to be
installed - as described in the following section - in the HV path between test voltage
source and test object.
If, during the measurement, the leakage current over the terminations is additionally to
be recorded and considered in the measurement result, the TCU box must also be
installed in the immediate vicinity of the test object. Electrical connections must also be
made on the remote end (see section 3.3.2).
A measurement with leakage current compensation is always recommended, if small
tanδ values are to be expected. For example, this can be expected when measuring on
homopolymeric and copolymeric XLPE cables. In these cases, the leakage current
caused by dirty or moist cable terminations should not be neglected. If this is not
recorded and compensated for, the measurement results can be falsified which would
make the analysis more complicated.
If the terminations are obviously clean or if the measurement is performed on aged
paper-insulated lead covered (PILC) cables, leakage current compensation is not a
mandatory requirement.
To obtain comparable measurement results, repeat measurements must always be
undertaken with the identical measurement set-up.