Micatrone MG-4000-R2 Specification sheet

MG-4000-R2
Mi-262gb / 2017-04-03
USE
MG-4000-R2 is designed to measure the O2-con-
tent in flue gases from oil burners, gas burners
and biomass-fired boilers. MG-4000-R2 can, to-
gether with a controller, optimize the air/fuel ratio.
The result is the highest possible firing efficiency
can be obtained and sustained over time indepen-
dent of changes in the fuel and combustion air.
The probe (MG-4000-R2/S) is installed in the flue
gas duct directly after the boiler. The tip of the pro-
be is easy to adjust so that it is positioned in the
centre of the flue gas zone. No special gas is re-
quired for calibration, this is done directly in the
surrounding air. Installation and use are as easy
as using a standard temperature sensor.
The O2-transmitter consists of two parts: the probe
and the central unit. The probe houses a sensor of
zirconium dioxide (ZrO2), heating element, signal
amplifier and generator for the ion pump. The cen-
tral unit houses the electronics for measuring the
sensor signal, analogue outputs, relay contacts for
the alarm outputs, control panel and the power
supply. All functions in the central unit are mana-
ged and monitored by a microprocessor.
Current measurement values, error indications
and set parameters are all presented on the inte-
grated display.
8 LEDs provide a quick indication of the operating
status.
© AB MICATRONE 2017-04-03 [O:\ Apps \ Typeset \ Mima \ mi-262gb_170403.vp]
Oxygen (O2) transmitter with monitoring
catrone®
Operating and Installation manual
Version 1.3x
PGM ESC
O -transmitter
2MG-4000-R2
®
Measuring
Relay 1
Relay 2
High O -content
2
Low O -content
2
Out of range
Calibration
Error
AB MICATRONE
O2-cont 3.1 %

2
© AB MICATRONE 2017-04-03 [O:\ Apps \ Typeset \ Mima \ mi-262gb_170403.vp]
TABLE OF CONTENTS
USE........................1
MEASUREMENTPRINCIPLE..........3
Relationship between O2-content in dry and
wetfluegases ................4
Fuel-Oil...................4
Fuel-Biomass...............4
INSTALLATION..................4
Centralunit..................4
Probe.....................5
Galvanicisolation..............5
Wiring....................5
NOTE!....................5
OXYGENE SENSOR CROSS SENSITIVITY . . 6
CombustibleGases..............6
HeavyMetals.................6
Halogen and Sulphur Compounds ......6
Reducing Atmospheres ............6
Others.....................6
ELECTRICALCONNECTION..........7
Description ..................7
Signals to the probe .............7
Ground currents ................7
Connection diagram for Central unit and
Probe.....................8
Translation chart MG-4000 // MG-4000-R2. . 9
FUNCTIONS ..................10
Measurementvalues.............10
O2-content.................10
Nernst ...................10
Current&Voltage .............10
Temperature................10
Output signals ................10
Relays....................10
Communication ...............11
INITIALIZEOPERATION............11
PROGRAMMING................12
LCDdisplay.................12
Keypad....................12
Startmenu..................12
Theindicationofparameters ........12
Programmingaparameter..........12
Programmemenu.............12
Parameterselection............12
Programmingavalue ...........13
Cancelling programming mode ......13
Thefunctionmenu..............13
Defaultsettings ...............14
Communication...............14
Defaultsettings ...............14
Factory...................14
INDICATIONS..................15
Displays...................15
LEDs.....................15
Measuring.................15
Out of range ................15
Calibration.................15
Relay1...................15
Relay2...................15
High O2-content ..............15
Low O2-content...............15
Error....................15
Measurementvalues.............15
Status ....................15
PROBECALIBRATION.............16
Limitsforcalibration............17
MAINTENANCE.................17
Fuses.....................17
TROUBLESHOOTING.............18
Notextdisplayed..............18
The Out of range LED is lit.........18
TheHighO
2-contentLEDislit.......18
The Low O2-contentLEDislit.......18
MG-4000-R2 shows incorrect O2-content . 18
MG-4000-R2 cannot be calibrated.....18
Ground currents ..............18
Glitches...................18
Errorindications..............18
TECHNICAL DATA ...............19
Central unit MG-4000-R2 ..........19
Measuring probe MG-4000-R2/S ......19
LISTOFPARAMETERS ............20
This instruction applies for MG-4000-R2 software
version 1.2x

MEASUREMENT PRINCIPLE
At higher temperatures (>500 °C) stabilised zirco-
nium dioxide (ZrO2) is a solid electrolyte for oxy-
gen. This can be used in two ways:
1. To transport oxygen through a ZrO2-disc (ion
pump) according to Faraday’s first law.
2. To measure the ratio of partial pressure from
oxygen on each side of a ZrO2-disc according
to Nernst’s equation.
Most modern oxygen meters available on the mar-
ket use one of the aforementioned principles. To
avoid disadvantages such as relatively large pro-
bes, linearization of measurement signals, refe-
rence air, etc. both principles can be combined
into a dynamic oxygen sensor.
The sensor consists of two identical ZrO2-discs
with platinum electrodes and a platinum ring which
creates a small chamber between the discs. One
disc is used as a reversible ion pump according to
Faraday. The other disc generates a measurement
voltage proportional to the ratio of the oxygen par-
tial pressure in the chamber (P2) and surroundings
(P1)accordingtoNernst.
When measuring, the reversible ion pump will al-
ternately pressurise and evacuate the chamber.
Reversing takes place at two preset voltage levels
V1and V2on the Nernst voltage VN.
The time of a pump cycle (tp) becomes directly
proportional to the surrounding partial pressure
from the oxygen (P1). An increase in the surroun-
ding oxygen content increases the partial pressure
(P1) and tp increases. With a decreasing oxygen
content tp falls. At 0 % O2tp is approximately 0.5
seconds and in fresh air (20.7 % O2) tp is approxi-
mately 7 seconds.
The sensor is enclosed by a heating element to
maintain the temperature of the ZrO2-discs at 700
°C. This makes the sensor insensitive to changes
in the flue gas temperature and the flow rate.
qBased on this principle the sensor is very small
and with that the probe can be made small.
qNo reference air is required and the Nernst
voltage does not need to be linearized.
3
© AB MICATRONE 2017-04-03 [O:\ Apps \ Typeset \ Mima \ mi-262gb_170403.vp]
P1
P2
Figure 1
Principle construction for a dynamic O2-sensor.
Platinum-
electrodes
Platinum-
electrodes
Platinum-
ring
ZrO2-
disc
Ion pump
ZrO2-
disc
Voltage
VNacc. to
Nernst
Figure 2
Measuring signal from the O2-sensor.
Figure 3
Cross-section view of the sensor element.
Sensor of
ZrO2
Heating-
element

Relationship between O2-content in
dry and wet flue gases
MG-4000-R2, which has its probe mounted in the
flue gas duct, measure the O2-content in wet flue
gases. Portable O2-measurement instruments ex-
tract a gas sample from the duct and measure the
content in dry gases.
Fuel - Oil
Following approximate relation between wet and
dry flue gas is valid when excess air does not ex-
ceed 50%.
O2-content (wet gas) = 0.9 x O2-content (dry gas)
Fuel - Bio mass
See graph to the right
Note! If the measuring probe is exposed for redu-
ced atmospherers, e.g. high content of CO (car-
bon oxide), the life-span of the probe is reduced.
Therefore, it is of great importance the the O2-
control is operating properly.
INSTALLATION
Central unit
MG-4000-R2 should be located fully visible and
easily accessible. It is important to remember the
ambient temperature, max. 45 °C when positioning
the unit. The case is fitted with hinges on the
left-hand side of the cover for easy opening. Make
sure the cover can be opened fully.
Outside dimensions:
H x W x D = 360 x 300 x 140 mm.
Hole pattern for wall mounting:
When choosing the position for installation, re-
member the following:
1. The central unit must not be subjected to an
ambient temperature higher than 45 °C. Prefe-
rably the ambient temperature should be
below 30 °C.
2. The signal cable between the probe and the
central unit must be a shielded 10 conductor
cable e.g. FKAR-G 10 x 0.5 mm2. The area of
each conductor should be at least 0.5 mm2.
The correct cable, which is a prerequisite for
reliable operations, is enclosed. The cable shi-
eld must only be connected in the central unit.
3. The length of the signal cable between the
probe and the central unit should be as short
as is practically possible, maximum 10 m.
4. The signal cable between the probe and the
central unit must not be routed together with
cables used for low or high voltages.
The minimum permitted distance to low
andhighvoltagecablesis30cm. Cables
must cross at right angles.
5. Avoid placement where the central unit is sub-
jected to vibration.
6. The central unit should be positioned so that
the control panel is approximately at eye level.
4
© AB MICATRONE 2017-04-03 [O:\ Apps \ Typeset \ Mima \ mi-262gb_170403.vp]
1
2
3
4
5
6
7
8
O -content flue gases
2
10 20 30 40 50 60
% Excess air
Dry flue gas
Wet flue ga
s
Water content
in fuel (%)
40
45
50
55
60
Figure 4
Relationship between O2-content
in dry and wet flue gases.
250 mm
335 mm
Diameter 10 mm

Probe
When installing the probe it is important to select cor-
rect placement. It should be easy to remove the pro-
be from the flue gas duct and easy to connect the
signal cable between the probe and the central unit.
1. Fit a 3/4" union on the flue duct after the boiler.
Make sure the union extends outside of the in-
sulation to facilitate installation of the probe. It
should be installed at a 15° angle to the hori-
zontal plane, so that the tip of the probe points
slightly downward (see figure 5), alt. top moun-
ted (see figure 6). This is to protect the probe
from condensation water.
2. Always install the supplied radiation protection
(see figure 7) on the probe’s insertion tube to
prevent the sensor’s electronics from overhea-
ting. Sole use of the radiation protection is not
recommended, the flue gas duct should also
be insulated.
3. The probe should be inserted so far that at le-
ast 10 cm of the tube hangs free inside the
duct. This is so the tip of the probe is not coo-
led via the union.
4. The supplied warning sign concerning precau-
tions that should be taken when the boiler is
swept must be set up where it is fully visible.
Galvanic isolation
The O2-probe should always be mounted using
the attached compression fitting which is fitted with
a isolation socket made of PTFE (TEFLON â)to
seperate the probe galvanically from protective
earth (ground) in the boiler/flue-gas duct which
could interfere with the measuring. Check that no
electrical connection is between the probe and
boiler/duct by measuring the resistance between
them both.
Wiring
The cable between the probe and the central unit
must NOT be extended. Leave an "eye" on the
cable by the probe so that the probe can be easily
removed from the flue gas duct for calibration and
duct sweeping.
The cable between the probe and the central unit
and cables to analogue output signals and data
communications must be shielded for the best me-
asurement result. The shield must only be connec-
ted to the ground rail in the central unit.
NOTE!
The probe must be operational (voltage fed) and
always maintain the operating temperature if it is
installed in the flue gas duct, irrespective of whet-
her the boiler is operational or not. When the pro-
be is not in use it should be kept in the surroun-
ding air. Wipe the probe dry if it is moist before in-
sertion.
5
© AB MICATRONE 2017-04-03 [O:\ Apps \ Typeset \ Mima \ mi-262gb_170403.vp]
NOTE! The measuring probe connection box should not be exposed to tempertures above 60 °C and must therefore be protec-
ted against the radiation heat caused by the flue gas duct or the boiler. Good insulation of the flue gas duct and enough space
between the insulation and the probes connection box is important. Always use the attached radiation protection shield.
max 20 m/s
max 400°C
~ 15°
min10cm
max 60°C
Union 3/4" inner thread
Max 260°C
Radiation shield
Probe pipe
INSULATION
Figur 5
Side mounting of the probe
Warning against dry-firing!
When "dry-firing" a biomass-fired boiler, the probe must not
be placed in the flue gas duct.
~ 15°
max 20 m/s
max 400°C
min10cm
Figure 6
Top mounting of the probe
Figure 7
Radiation shield for connection box

OXYGENE SENSOR CROSS SENSITIVITY
Cross sensitivity with other gases:
The oxygen sensor measures partial oxygen pressure. Gases or chemicals that will have an influence on
the life of the sensor or on the measuring results are:
Combustible Gases
Small amounts of combustible gases will be bur-
ned at the hot Pt-electrode surfaces or Al2O3filters
of the sensor.
In general combustion will be stoichiometric as
long as enough oxygen is available, the sensor will
measure the residual oxygen pressure. Investiga-
ted were:
qH2(Hydrogen) up to 2%; stoichiometric
combustion
qCO (Carbon Monoxide) up to 2%; stoichio-
metric combustion
qCH4(Methane) up to 2.5%; stoichiometric
combustion
qNH3(Ammonia) up to 1500 ppm; stoichio-
metric combustion
Heavy Metals
Vapours of metals like Zn (Zinc), Cd (Cadmium),
Pb (Lead), Bi (Bismuth) will have an effect on the
catalytic properties of the Pt– electrodes. Exposu-
res to these metal vapours has to be avoided.
Halogen and Sulphur Compounds
Small amounts (< 100ppm) of Halogens and/or
Sulphur compounds have no effect on the perfor-
mance of the oxygen sensor. Higher amounts of
these gases will in time cause readout problems
or, especially in condensing environments, corro-
sion of sensor parts. Investigated gases are:
qHalogens, F2(Flourine), Cl2(Chlorine)
qHCL (Hydrogen Chloride), HF (Hydrogen
Fluoride)
qSO2(Sulphur Dioxide)
qH2S (Hydrogen Sulphide)
qFreons
qCS2(Carbon Disulfide)
Reducing Atmospheres
Long time exposure to reducing atmospheres may
in time impair the catalytic effect of the Pt-electro-
des and has to be avoided.
Others
qVapours (organic silicone compounds) of
RTV (Room Temperature Vulcanised) rub-
bers are well known pollutants of zirconia
based oxygen sensors. The organic part of
the compound will be burned at hot sensor
parts, leaving behind a very fine divided
SiO2(Silicone Dioxide/Silica). This SiO2
completely blocks the pores and active
parts of the electrodes. If RTV rubbers are
used we advise to use high quality, well
cured.
qDust. Fine dust (Carbon parts/soot) might
cause clogging of the porous stainless ste-
el filter and might have an effect on the re-
sponse speed of the sensor.
qHeavy Shocks or Vibrations might alter
sensor properties.
qWater vapour. Condensing water vapour
might cause clogging of filters or internal
corrosion of sensor parts. We advise to
keep the sensor at operating temperature
or standby temperature when exposed to
exhaust gases. Direct exposure to water
droplets has to be avoided.
6
© AB MICATRONE 2017-04-03 [O:\ Apps \ Typeset \ Mima \ mi-262gb_170403.vp]

ELECTRICAL CONNECTION
Description
Voltage supply
MG-4000-R2 is fed with 230 VAC, 50 Hz on termi-
nals 1 (neutral) and 3 (phase). The supply should
incorporate a circuit-breaker to facilitate servicing.
Alarm function
On terminals 5-7 and 8-10, are two potential free
switching relay contacts. The relay contact func-
tion can be programmed on MG-4000-R2, e.g.
alarm with low O2-content and probe error. The re-
lay contacts are low voltage, 230 VAC.
Probe
Terminals 11-19 are connected to the probe’s ter-
minals 1-9.
Output signals
MG-4000-R2 has two analogue output signals for
the current O2-content, a mA-signal (0/4..20 mA)
on terminals 21 (+) and 22 (-) and a Volt-signal
(0/2...10 V) on terminals 23 (+) and 24 (-).
NOTE! Common neutral (-). The output signals
are not galvanically isolated from each other.
Communication
MG-4000-R2 has 2 interfaces, RS-232 and
RS-485. Only one interface at a time can be used.
RS-232 is connected to a modular jack (RJ45) and
is designed for Micatrone’s Programming adapter,
part no. 60-0972-2.
RS-485 is connected to terminals 25 (A) and 26
(B) and requires MG-4000-R2 to be equipped with
Micatrone’s Communication module, part no.
60-0973.
If both RS-232 and RS-485 are connected simulta-
neously RS-232 is given priority for communica-
tions. Also see the operating description for com-
munications on page 11.
Signals to the probe
Term Description Signal
11 Positive supply to the
probe’s electronics.
+7 Volt DC, 2.5 mA.
12 Feedback signal from
heating element in
probe.
± 50 mVolt, square
wave 1 kHz at 700 °C.
13 Control signal to the ion
pump for evacuation.
+6 / -4 Volt, square
wave 1 kHz.
14 Supply to the heating
element.
1.7 A, approx. 4.2 Volt
DC on probe.
15 Measurement zero from the electronics.
16 Neutral wire to the heating element.
17 Control signal to the ion
pump for pressurising.
+6 / -4 Volt, square
wave 1 kHz.
18 Measurement signal
from the zirconium
dioxide sensor.
Periodic signal
0...4 Volt DC.
19 Negative supply to the
probe’s electronic.
-5 Volt DC, 2.5 mA.
Ground currents
The probe has low voltage signals, 50 mV. Any
ground currents may influence the measurement
and it's important that the probe is galvanically iso-
lated from ground. This can easy be checked by
measuring the resistance between terminal 15 and
the ground rail in the central unit.
The result of the measuring should be a resistance
over 1 MW(Megaohm), break is prefered.
If the resistance is under 1 MW, the installation of
the probe need to be checked. Also check that the
output signal don't shorting between terminal 15
and ground. You might need a transmitter with gal-
vanic separation to the output signal.
7
© AB MICATRONE 2017-04-03 [O:\ Apps \ Typeset \ Mima \ mi-262gb_170403.vp]

Connection diagram for Central unit and Probe
8
© AB MICATRONE 2017-04-03 [O:\ Apps \ Typeset \ Mima \ mi-262gb_170403.vp]
AB MICATRONE
Ritad
Det. nr Antal Benämning Material Anmärkning
Mod. nr Ämne
Dimension
Datum Sökväg
Filnamn
Ritningsnummer
LJ 2012-04-02
O:\Produkter\MG-4000-R2\CDR\
MG-4000-R2 Inkoppling.cdr
S-3767
Connection diagram for
MG-4000-R2 Ver 1.10
Page 1 (2)
PAD 1
SNAP1 SNAP2
SNAP5 SNAP6 SNAP7 SNAP8
SNAP4
SNAP3
J7
1
K3
E17
AC6
J2
R55
C41
R26
AC24
R77
C43
K1
IC1
LED1
C6
C12
R2
C27
C10
C16
C15
C17
C20
C28
D10
C63
R16
R67
D11
E18
E11
E3 E4
E15 E16
E10 E6
C13
C4
C5
IC3
IC8
IC24
IC25
KD1
C11
P2
C9
R76
R78
C53 D12
R70
T1
C26
TR1
TR2
FH3
FH2
FH1
R1
C1
C3
C2
1
PL1
400 mAT
5x20 mm
(3x)
D3
D2
D1
C8
C7
IC2
IC4
KD2 K2
E5
R4
TD2 TD1 IC9
P1
R5
C29
IC11
C30
IC12
FH4
2AT
5x20 mm
C18
D4 C19
C23 D5
R3
FM1
FM2 FM3
TD3
1
PL2
1
PL3
E12 E13
E14
L1
IC17
J1
R75
C54
R51
R42
C55
R46
R44
E2
E1
IC6
IC7
AC7
J8
R6
R7
R8 R9 R10 R11 R12
IC13
R61
AC21
AC22
R30
R31
C56
C59
C44
C52
R54
C35
D13
R20
C64
C65
R73
R28
D14
E8
C48
R27
R50
AC17
R45
R69
R74
R17
R29
AC25
C50 R57
R52
R43
D9
R71
R68
AC8
C51
R49
R48
R47
C60
C61
AC20
R62
R63
R64
IC20
R60
R66
C62
R65
C31
C57
AC27
R40
R72
C34
R32
C47
C49
C58
P3 P4
IC21
IC22
AC29 AC28
R58
R56
AC26
R25
R59
R53
IC27
IC29
IC28
IC26
IC15
IC16
C42
AC15
AC16
IC10
R23
R21
C36
C37
R18
D7 D8
R38
R41
R39
R37
AC19
IC19
C32
R15
C33
R13
D6
R33
AC14
IC14
C38
R24
C39
C40
R19
E9
E7
C22
C46
R36
IC18
AC18
RL1 RL2
AC23
R35
C45
R34
IC5
C25
R14
C14
AC13
R22
1
J3
1
J4
1
J6
C24
C21
IC23
P-3728 V2.00
2007-02
Top Silk
17
12
9
15
11
8
714 21
18
22 24 25 26
13
10 16
A
BRS-485
Current loop
Output signal 1
Output signal 2
19 20 23
NO
C
NC Relay 2, 230 VAC
Signal voltage
1
Fuse FH4 for heating
element in sensor 2 AT
5x20 mm
Fuses for the electronics
3 pcs. 400 mAT 5x20 mm
Location for RS-485
Communication.
plug-in module
10 11 26
+
Ri
0/4...20 mA RL max 500 ohm
-
-5 Volt
Low voltage
230 VAC
56
Ri
+
+7 Volt
132 4
N
N
L
L
Neutral
Line
230 VAC
MG-4000-R2
NO
C
NC Relay 1, 230 VAC
0/2...10 Volt Ri min 50 kohm
RL
+++
Ri
9
8
7
56
132 4
Probe
MG-4000-R2/S
NOTE!!! The shield of the signal
cable may NOT be connected to
the O -probe. The shield must
only be connected to the ground
rail in the central unit.
2

Translation chart MG-4000 // MG-4000-R2
9
© AB MICATRONE 2017-04-03 [O:\ Apps \ Typeset \ Mima \ mi-262gb_170403.vp]
AB MICATRONE
Ritad
Det. nr Antal Benämning Material Anmärkning
Mod. nr Ämne
Dimension
Datum Sökväg
Filnamn
Ritningsnummer
LJ 2007-12-21
I:\MG-4000-R2\CDR\
MG-4000-R2 Inkoppling.cdr
S-3767
Inkoppling av MG-4000-R2
Ver 1.00
Sidan 2 (2)
17
12
9
15
11
8
714 21
18
22 24 25 26
13
10 16 19 20 23
56
132 4
17
12
9
15
11
8
714
18
13
10 16 19 20
56
132 4
MG-4000-R2
MG-4000

FUNCTIONS
Measurement values
O2-content
MG-4000-R2 measures the O2-content in flue gas
using a zirconium dioxide sensor. The measure-
ment range of the output signal can be selected
between 0...5%, 0...10%, 0...20% or 0...100% O2.
If the measured O2-content is outside of the selec-
ted measurement range an orange LED is lit on
the control panel.
MG-4000-R2 has visual alarms (red LEDs on the
control panel) for specific high and low O2-content.
The limits are stated in % O2-content.
Theprobemustfirstbecalibratedtoprovideaccu-
rate measurements. Calibration is performed in
fresh air, see page 16. The current barometric
pressure can be programmed during calibration on
MG-4000-R2 to give the best possible accuracy.
The value is stated in mBar.
Nernst
Indicates the measurement signal from the probe.
Nernst will vary between 0 and 4 Volts during nor-
mal measurements.
Current & Voltage
Indicates the present current and voltage to the
probe’s heating element.
Temperature
Indicates the present temperature of the probe’s
zirconium dioxide sensor.
Output signals
MG-4000-R2 produces two output signals (one for mA
and one for Volt). The output signals state the current
O2-content for the selected measurement range.
Output signal 1 can be selected between 0...20
mA or 4...20 mA and output signal 2 can be selec-
ted between 0...10 Volt or 2...10 Volt.
Relays
MG-4000-R2 has two potential free switching con-
tactsthatcanbeusedtomonitortheO
2-content or
the function of the probe.
The function is activated in parameter 14/21 by se-
lecting whether the high or low signal is to be mo-
nitored. Select a source (input signal) in parameter
15/22. If error indication is chosen the function
(parameter 14/21) needs to be programmed to
HIGH.
When monitoring the O2-content a level is pro-
grammed (parameter 16/23) and a hysteresis (pa-
rameter 17/24). The level and the hysteresis are
stated in % O2-content. These two parameters are
not used when monitoring error indication.
Switching on and off can be delayed by the cho-
sen number of seconds in parameters 18/25 and
19/26. In parameter 20/27 the position of the swit-
ching contact is selected when the monitoring sta-
te is in normal mode. A yellow LED on the control
panel comes on when the relay contact is active.
10
© AB MICATRONE 2017-04-03 [O:\ Apps \ Typeset \ Mima \ mi-262gb_170403.vp]
Par.no: Description Range Value
O2-measurement
1Range 0..5%
0..10%
0..20%
0..100%
2High O2 0,0...99,9
3Low O2 0,0...99,9
4Barometer 800...1200
Par.no: Description Range Value
Outputs
28 Source 1 O2-cont
29 Signal 1 0..20mA
4..20mA
30 Source 2 O2-cont
31 Signal 2 0..10V
2..10V
Par.no: Description Range Value
Relay 1
14 Function OFF
HIGH
LOW
15 Source O2-cont
ERROR
16 Level 0,0...99,9
17 Hysteresis 0,1...99,9
18 Delay on [s] 0...999
19 Dly fall [s] 0...999
20 Norm.pos. FALLEN
ACTIVE
Relay 2
21 Funktion OFF
HIGH
LOW
22 Source O2-cont
ERROR
23 Level 0,0...99,9
24 Hysteresis 0,1...99,9
25 Delay on [s] 0...999
26 Dly fall [s] 0...999
27 Norm.pos. FALLEN
ACTIVE

Communication
A communications module (accessory) can be fit-
ted in MG-4000-R2 to provide data communica-
tions using RS-485 (2-wire current loop) as the
interface.
There is also an adapter for RS-232 (serial port)
available as an accessory. The adapter is intended
for temporary use, for example, during installation
and trimming and does NOT require a communi-
cations module to be installed. Only one interface
(RS-485 or RS-232) can be used at any time.
The protocol used is Comli. Parameters and mea-
surement values are read with message type 2
and new values for parameters are transferred
with message type 0. The Comli number is the
same as the parameter number. Data communica-
tions can be limited so that only reading is
possible. (parameter 36).
INITIALIZE OPERATION
NOTE! The probe must be operational (voltage
fed) and always maintain operating temperature if
fitted in the flue gas duct, irrespective of whether
the boiler is operational or shutdown. If the probe
is not operational it should be stored in the sur-
rounding air.
NOTE! If the probe is subjected to reducing at-
mospheres, e.g. high content of CO (carbon mo-
noxide), this will reduce the service life of the pro-
be. It is important that the O2-control works cor-
rectly.
Check that all connections between the probe and
the central unit are correct before MG-4000-R2 is
connected to the mains supply, 230 VAC.
When the power is switched on MG-4000-R2 will
start to heat the probe. This takes 180 seconds
and during this period, the display shows "Start
up", the O2 content shows 0.0% and the outputs
are 0/4 mA respectively 0/2 Volt.
Should an error be discovered, e.g. a faulty con-
nection on the signal cable between the probe and
the central unit, the "Error" LED lights and the fault
is presented in plain text on the display. For a
description of how to rectify the error, refer to page
18.
If it is the first time that MG-4000-R2 has been
started the settings for the selected measurement
range and output signals should be checked.
MG-4000-R2 also needs to be calibrated in fresh
air to match the central unit with the probe, see
page 16.
11
© AB MICATRONE 2017-04-03 [O:\ Apps \ Typeset \ Mima \ mi-262gb_170403.vp]
Par.no: Description Range Value
Communication
32 Address 1...247 21
33 Location 0...32767 0
34 Protocol COMLI COMLI
35 Baud 600 b
1200 b
2400 b
4800 b
9600 b
4800 b
36 Protect NO
YES
NO
Par.no: Description Range Value
O2-measurement
1Range 0..5%
0..10%
0..20%
0..100%
2High O2 0,0...99,9
3Low O2 0,0...99,9
4Barometer 800...1200
Par.no: Description Range Value
Outputs
28 Source 1 O2-cont
29 Signal 1 0..20mA
4..20mA
30 Source 2 O2-cont
31 Signal 2 0..10V
2..10V

PROGRAMMING
LCD display
MG-4000-R2 has a two-row alphanumeric LCD
display with back light and can show 16 characters
on each row. Normally the display indicates pre-
sent operating values but it is also used to indicate
measurement values and programmed parameter
values.
Keypad
MG-4000-R2 has a keypad with four keys, mar-
ked, 65, PGM and ESC.
qThe arrow keys, 65, are used to scroll
between different parameter groups, para-
meters and functions and increase or de-
crease the value of programmed parame-
ters.
qThe PGM key is used for programming and
indicating of set parameters.
qBy pressing the ESC key ongoing program-
ming can be aborted. The ESC key is also
used when returning to the start menu.
Start menu
The start menu is the entry point for indication and
programming of parameters along with special
functions such as default programming and calib-
ration.
If the start menu is not showed on the display,
press repeatedly on the ESC button. The start
menu is by default replaced to indicate operating
values. One press of the ESC button shows the
start menu for a short while and returns automati-
cally to indicate operating values. Use the arrow
keys, 6 5, to scroll between different display alter-
natives as follows.
Top row Bottom row
AB MICATRONE O2-content
Voltage Current
Status Relay 1, Function Status Relay 2, Function
Error message
Run time
Serial number
The indication of parameters
One press of the PGM key when default start
menu is showing will activate an automatic scroll
and list all parameters for about two seconds. The
top row indicating the parameter group and bottom
row the parameter and its value. The listing will
end when all parameters has been showed, or if
the ESC key is pressed.
Programming a parameter
Programme menu
The program menu includes all parameters and
measuring values that are accessible. All parame-
ters are divided into different parameter groups
where each function has its own group.
To activate the program menu, continuously press
the PGM key until following display is shown. Re-
lease the key.
The second parameter group is shown on the top
row.
Parameter selection
By using the arrow keys, 65, different groups of
parameters can be selected. If the last group is
shown and the arrow key, 6, is pressed, the first
menu is shown and vice versa.
Parameter groups
1Internals 5Outputs
2O2-measuring 6Communication
3Relay 1 7Current values
4Relay 2 8Status
When the desired group is shown, it can be selec-
ted by pressing the PGM key once. The first para-
meter inside the selected group is shown on the
bottom row of the display.
12
© AB MICATRONE 2017-04-03 [O:\ Apps \ Typeset \ Mima \ mi-262gb_170403.vp]
AB MICATRONE
O2-cont 3.1 %
MG-4000-R2
START-MENU
Internals
Prog.ver. 1.30
MG-4000-R2
PROGRAM-MENU
O2-measuring
O2-measuring
Range 0..10%

With the arrow keys, 65, all parameters inside
the group can be selected. If the last parameter in
the selected group is shown and the arrow key,6,
is pressed, the first parameter is shown and vice
versa.
To select another group of parameters when a pa-
rameters is shown on the bottom row, press the
ESC key. The programming mode is cancelled
when the ESC key is pressed repeatedly until the
default start menu is shown.
Programming a value
Parameters with a numeric value (integers and de-
cimal values):
When the selected parameter is sh
own in the display it can be selected for program-
ming by pressing the PGM key once. The first digit
will flash to indicate that it can be changed using
the arrow keys, 65.
If the digit flashing is “9” and the arrow key, 5,is
pressed, the counter will start from “0” and count
forwards (-9 for parameters that accept negative
values) without changing any other of the digits in
the value. The counter will continue in the opposite
way if the digit is flashing “0” and the arrow key,
6, is pressed. Continue to the next digit by pres-
sing the PGM key again.
When the last digit is set and the PGM key is pres-
sed the actual change of the parameter value is af-
fected. The entire bottom row in the display will
flash to confirm that the programming was suc-
cessful.
Parameters with preset alternatives
When the selected parameter is shown in the dis-
play it can be selected for programming by pres-
sing the PGM key once. The entire text will flash to
indicate that it can be changed to the preset alter-
natives using the arrow keys, 65.
The same procedure as with digits will occur if an
arrow key, 65, is pressed when the last, re-
spectively the first, parameter alternative is shown.
By pressing the PGM key, when the desired para-
meter alternative is shown, will execute the pro-
gramming and change the parameter. The entire
bottom row in the display will flash to confirm that
the programming was successful.
Cancelling programming mode
Ongoing programming can be cancelled by pres-
sing the ESC key. The parameter value will stop
flashing and the original value remains the same.
The function menu
To activate the function menu, press both PGM
and ESC key simontaneously and keep the keys
pressed until the following display is shown. Rele-
ase the buttons.
The first function is shown in the display.
Selecting a function:
With the arrow keys, 65, different functions can
be selected, for instance, default programming
and calibration. If the last function is shown and
the arrow key, 6, is pressed, the first function will
shown again and vice versa.
Functions
1Calibration of probe
2Default settings, Communication
3Default settings, Factory
4Calibration analogue inputs *)
5Calibration analogue outputs *)
When the desired function is displayed it can be
selected by pressing the PGM key.
The functions menu can be aborted by pressing
the ESC key.
*) Calibration of analogue inputs and outputs
require use of special equipment. All ana-
logue signals are factory calibrated and
should not during normal circumstances
have to be calibrated again.
13
© AB MICATRONE 2017-04-03 [O:\ Apps \ Typeset \ Mima \ mi-262gb_170403.vp]
O2-measuring
Low O2 00.5
Relay 1
Function HIGH
MG-4000-R2
FUNCTIONS-MENU
Calibration of
probe

Default settings
Communication
Default settings
Factory
14
© AB MICATRONE 2017-04-03 [O:\ Apps \ Typeset \ Mima \ mi-262gb_170403.vp]
Par.no: Description Range Value
Communication
32 Address 1...247 21
33 Location 0...32767 0
34 Protocol COMLI COMLI
35 Baud 600 b
1200 b
2400 b
4800 b
9600 b
4800 b
36 Protect NO
YES
NO
Par.no: Description Range Value
Internals
0Prog.ver. 0,00...9,99 1,00
O2-measuring
1Range 0..5%
0..10%
0..20%
0..100%
0..10%
2High O2 0,0...99,9 10,0
3Low O2 0,0...99,9 0,5
4Barometer 800...1200 1013
Relay 1
14 Function OFF
HIGH
LOW
LOW
15 Source O2-cont
ERROR
O2-cont
16 Level 0,0...99,9 0,5
17 Hysteresis 0,1...99,9 0,1
18 Delay on [s] 0...999 10
19 Dly fall [s] 0...999 2
20 Norm.pos. FALLEN
ACTIVE
ACTIVE
Relay 2
21 Function OFF
HIGH
LOW
HIGH
22 Source O2-cont
ERROR
ERROR
23 Level 0,0...99,9 0,0
24 Hysteresis 0,1...99,9 0,1
25 Delay on [s] 0...999 0
26 Dly fall [s] 0...999 0
27 Norm.pos. FALLEN
ACTIVE
ACTIVE
Outputs
28 Source 1 O2-cont O2-cont
29 Signal 1 0..20mA
4..20mA
4..20mA
30 Source 2 O2-cont O2-cont
31 Signal 2 0..10V
2..10V
0..10V
Communication
32 Address 1...247 21
33 Location 0...32767 0
34 Protocol COMLI COMLI
35 Baud 600 b
1200 b
2400 b
4800 b
9600 b
4800 b
36 Protect NO
YES
NO

INDICATIONS
Displays
Different operating values are shown on displays
in the start menu, see page 12. Use the arrow-
keys, 6or 5, to scroll through the different dis-
plays with operating values.
Top row Bottom row
AB MICATRONE O2-content
Voltage Current
Status Relay 1, Function Status Relay 2, Function
Error message
Run time
Serial number
LEDs
The LEDs on the control panel indicate the follo-
wing:
Measuring
Flashes green for each new measurement pe-
riod/pump cycle (tp) from the probe, see page 3.
Outofrange
Lit orange when the measured O2-content is outsi-
de of the measurement range selected in parame-
ter 1.
Calibration
Lit orange while calibration of the probe is in pro-
gress.
Relay 1
Lit yellow when the relay contact for terminals 5-7
is active.
Relay 2
Lit yellow when the relay contact for terminals 8-10
is active.
High O2-content
Lit red when the measured O2-content exceeds
the value set in parameter 2.
Low O2-content
Lit red when the measured O2-content is below the
value set in parameter 3.
Error
Lit red in the event of a probe error. The error is
shown in plain text on the display, see page 18.
Measurement values
The following measurement values can be read on
the display from the program menu, see page 12.
Status
The following status values can be read on the
display from the program menu, see page 12.
Key to status texts
R1 Func. and R2 Func.
OFF The relay function is shutoff = not used.
WON Waiting for operation = the measurement value
has passed the limit, but the time for operation
has not elapsed.
ON The measurement value has passed the limit, but
the time for operation has elapsed.
W FALL Waiting for release = the measurement value is
on the normal side of the limit + connection diffe-
rence, but the time for release has not elapsed.
FALL The measurement value is on the normal side of
the limit + connection difference, but the time for
release has elapsed.
15
© AB MICATRONE 2017-04-03 [O:\ Apps \ Typeset \ Mima \ mi-262gb_170403.vp]
Par.no: Description Range Value
Measuring values
100 O2-cont. 0,0...99,9
101 Nernst -0,50...4,50
102 Current 0,00...3,00
103 Voltage 0,00...9,99
104 Temp. 550...850
105 Reg. active NO
YES
106 Reg. out 0,00...100,00
107 CSP 0...999
108 Counter 0...65535
109 Counter OF -99...99
90 Cal. Temp. 550...850
91 Cal. Level 1520...6840
Par.no: Description Range Value
Status
110 R1 Func. OFF
WON
ON
W FALL
FALL
112 R2 Func. OFF
WON
ON
W FALL
FALL
114 Counting... STOP
UP
DOWN
115 Ionpump... STOP
PRESS
EVACU

PROBE CALIBRATION
Introduction
The central unit and probe must be calibrated to-
gether for MG-4000-R2 to measure the correct
O2-content. If any of the units are replaced a new
calibration must be made. Calibration takes about
10 minutes to complete.
Step 1
Make sure MG-4000-R2 is connected to the mains
supply and the probe. Start calibration at the earli-
est 10 minutes after MG-4000-R2 has been star-
ted, i.e. that both the mains supply and probe have
been connected. If no error is indicated it is assu-
med that the probe has reached its working tem-
perature, approx 700 °C.
Calibration is performed from the function menu,
see page 16. When the following is displayed:
press PGM to start calibration.
The following text is now shown:
You can cancel calibration at any time by pressing
ESC.
The function menu is displayed again. No calibra-
tion has been performed and the previous calibra-
tion value still applies.
Press PGM to continue the calibration. The pro-
grammed barometric pressure in mBar is now dis-
played.
Press PGM if the value is OK, otherwise you must
cancel (press ESC) and program the barometric
pressure in question via the program menu, see
page 12.
Step 2
The following text is now shown:
Theprobeiscalibratedinfreshair.Removethe
probe from the flue gas duct and place/hang the
probe so that at least 10 cm of the tip of the pro-
be is hanging freely in the air.
Remember that the tip is extremely hot. Ariskof
burns exists! Press PGM to continue.
If calibration is started less than 10 minutes after
the mains supply has been connected to
MG-4000-R2 the unit will wait until the time remai-
ning has elapsed before continuing with the
calibration.
When the counter reaches zero calibration conti-
nues with the next step.
Step 3
The Calibration LED now comes on and the cen-
tral unit makes 9 readings from the probe.
The measurement value and temperature from the
probe are shown for each reading.
Five dashes are shown if the measurement value
is not approved. If more than 2 measurements fail
the probe cannot be calibrated.
Cancel calibration and check the probe, see page 18.
16
© AB MICATRONE 2017-04-03 [O:\ Apps \ Typeset \ Mima \ mi-262gb_170403.vp]
Calibration of
probe
[PGM] Continue
[ESC] Abort
Aborting...
Place probe in
air [PGM/ESC]
0of9
Barometer 1013
OK? [PGM/ESC]
1 of 9 3468
689
Calibration ERR
[ESC]
Waiting... 123

Step 4
The Calibration LED goes out when calibration is
complete and the following text is displayed.
The 2 numbers are values from the most recent
calibration and do not need to be the values
shown in the example above. Calibration is
approved!
Press PGM to continue. You will now be asked
whether the new calibration should be saved and
used from now on.
Press PGM to save or ESC to cancel.
Press ESC to close the function menu.
Step 5
Double check the calibration, i.e. measure the
O2-content with the probe in the flue gas duct and
read the measurement value on the central unit.
Estimate whether the measurement value is rea-
sonable or make a reference measurement using
another O2-transmitter. Change the air or fuel sup-
ply and check that the O2-content changes.
Limits for calibration
Barometer Low limit High limit
800 1520 4560
900 1710 5130
1000 1900 5700
1013 1925 5774
1100 2090 6270
1200 2280 6840
MAINTENANCE
NOTE! The probe must be operational (voltage
fed) and always maintain operating temperature if
fitted in the flue gas duct, irrespective of whether
the boiler is operational or shutdown. If the probe
is not operational it should be stored in the
surrounding air.
NOTE! If the probe is subjected to reducing at-
mospheres, e.g. high content of CO (carbon mo-
noxide), this will reduce the service life of the pro-
be. It is important that the O2-control works
correctly.
A design without moving parts means the probe is
fairly insensitive to external influences; resulting in
a long service life.
However, you should remove the probe from the
flue gas duct maybe once after each firing season
to check that the tip of the probe is not clogged by
soot or deposits. These deposits can affect the
probe’s time constant, i.e. the reaction time will in-
crease with the increase in deposits.
If the tip of the probe is dirty it can be carefully cle-
aned using a cloth dampened with, e.g. methyla-
ted spirit or petroleum spirits. Make sure that the
tip has had time to cool to room temperature.
MG-4000-R2 should be recalibrated for the first
time after about 2 months, then roughly once per
firing season.
Fuses
MG-4000-R2 contains 4 fine-wire fuses. These are
positioned to the right of the transformer and are
numbered FH3, FH2, FH1 and FH4 from the top.
Also see the figure on the terminal diagram.
FH3, 400 mA slow-burn.
Fuse for the control panel and processor card.
FH2, 400 mA slow-burn.
Fuse for the galvanically isolated supply for data
communications.
FH1, 400 mA slow-burn.
Fuse for the relay coils and supply to the probe’s
electronics.
FH4, 2 A slow-burn.
Fuse for the probe’s heating element.
17
© AB MICATRONE 2017-04-03 [O:\ Apps \ Typeset \ Mima \ mi-262gb_170403.vp]
Calibrering OK
3432 688 [PGM]
Cnt: 3432 T:688
Save? [PGM/ESC]
Cnt: 3432 T:688
Saving...
Completes...

TROUBLE SHOOTING
No text displayed
Check that MG-4000-R2 is voltage fed, 230 VAC
on terminals 1 and 3.
Check the 3 fuses to the right of the uppermost
transformer on the left-hand side of the PCB. They
should be 400 mAT, 5x20 mm glass-tube fuses.
The Out of range LED is lit
MG-4000-R2 is measuring O2-content that is outsi-
de of the selected measurement range. This is
normal when the boiler has stopped and the flue
gas duct contains fresh air. If this occurs when the
boiler is operational a larger measurement range
should be selected in parameter 1.
The High O2-content LED is lit
MG-4000-R2 is measuring O2-content in excess of
the value in parameter 2.
The Low O2-content LED is lit
MG-4000-R2 is measuring O2-content below the
value in parameter 3.
MG-4000-R2 shows incorrect O2-content
Calibrate, see page 16.
MG-4000-R2 cannot be calibrated
Check the connections between the central unit
and the probe.
Read the Counter measurement value via the pro-
gram menu. The value should be between 1925
and 5774 when the probe is warm and is in fresh
air at normal barometric pressure 1013 mBar.
Ground currents
The probe has low voltage signals, 50 mV. Any
ground currents may influence the measurement
and it's important that the probe is galvanically
isolated from ground. This can easy be checked
by measuring the resistance between terminal 15
and the ground rail in the central unit.
The result of the measuring should be a resistance
over 1 MW(Megaohm), break is prefered.
If the resistance is under 1 MW, the installation of
the probe need to be checked. Also check that the
output signal don't shorting between terminal 15
and ground. You might need a transmitter with gal-
vanic separation to the output signal.
Glitches
If MG-4000-R2 gets disrupted or receives transi-
ents, so that O2-measurement fails, the software
will reboot. The reboot takes 3 minutes and during
this period the outputs are 0/4 mA respectively 0/2
Volt.
Error indications
Should MG-4000-R2 discover an internal fault, for
example on the probe, this is indicated by a red
LED on the control panel and text on the display.
In the event of an error the O2-content will indicate
0.0 % O2and the output signals will drop to a mini-
mum. This is to guarantee an excess of air for
combustion.
Relay 1 and Relay 2 can be programmed to send
out a signal when an error occurs, see page 10.
The error texts that can appear on the display are
presented below.
Nernst, Signal too high/low
The measurement signal from the probe has been
outside of its working range 0...4 Volt for some
time. Restart MG-4000-R2 to try to reset the error.
Check the connections between the central unit
and the probe. Try another probe.
Current, Signal too high.
Too high current, > 1.9 A, is fed from the central
unit to the heating element in the probe. Try anot-
her probe.
Current, Signal too low.
Too low current, < 1.65 A, is fed from the central
unit to the heating element in the probe. Check
fuse FH4 in the central unit. Check the connec-
tions between the central unit and the probe. Try
another probe.
Voltage, Signal too high.
Too high voltage, > 8.0 Volt, is fed from the central
unit to the heating element in the probe. Check the
connections between the central unit and the pro-
be. Try another probe.
Voltage, Signal too low.
Too low voltage, < 4.0 Volt, is being fed from the
central unit to the heating element in the probe.
Check fuse FH in the central unit. Check the con-
nections between the central unit and the probe.
Try another probe.
Temperature, Signal too high/low
The probe does not maintain the right working
temperature. Restart MG-4000-R2 to try to reset
the error. Check the connections between the cen-
tral unit and the probe. Try another probe.
No measurement period, Defective probe
Restart MG-4000-R2 to try to reset the error.
Check the connections between the central unit
and the probe. Try another probe.
18
© AB MICATRONE 2017-04-03 [O:\ Apps \ Typeset \ Mima \ mi-262gb_170403.vp]

TECHNICAL DATA
Central unit MG-4000-R2
General
Supply voltage: 230 VAC, 50/60 Hz
Power consumption: 35 VA
Ambient temperature: 0...45 °C,
recommended < 30 °C
El. connections: Max. 2 pcs. 1,5
mm2/term.
Cable entries: 12 holes ø 20 mm
Degree of protection: IP 65
Dimensions: h x w x d 360 x 300 x 140 mm
Weight: 6,5 kg
O2-measuring
Range: 0...5 % O2
0...10 % O2
0...20 % O2
0...100 % O2
Resolution: 0,1 % O2
Accuracy: max 5 % of range
max 0,2 %-units of the
O2-content
Time constant: < 10 seconds
Heating time: < 200 seconds
Relay outputs
Max. load: 230 VAC, 2A
Outputs
mA
Signal range: 0/4...20 mA
Max. load: 500 W
Volt
Signal range: 0/2...10 Volt DC
Min. load: 50 kW
Data communication (optional)
Interface: RS-485 or. RS-232
Protocol: Comli
Measuring probe MG-4000-R2/S
General
Temperature range for
flue gases: 0...400 °C
Flue gas velocity: max 20 m/s
Ambient temperature for
connection box: 0...60 °C
Max. temperature at the
compression fitting: 260 °C
El. connections: 1.5 mm2/term.
Cable entries: 1 hole ø 20 mm
Cable to central unit: FKAR-G 10x0,5 mm2
Cable length: max 10 m
Degree of protection: IP 65
Material insertion tube: Stainless steel
Material connections
box: Aluminium
Duct fitting: G 3/4"
Weight: 1,5 kg
19
© AB MICATRONE 2017-04-03 [O:\ Apps \ Typeset \ Mima \ mi-262gb_170403.vp]
80
125
58
38
390
Figur 8
Dimensions measuring probe MG-4000-R2/S

20
© AB MICATRONE 2017-04-03 [O:\ Apps \ Typeset \ Mima \ mi-262gb_170403.vp]
AB MICATRONE Telephone: +46 8-470 25 00
Åldermansvägen 3 Fax: +46 8-470 25 99
SE-171 48 SOLNA Internet: www.micatrone.se
LIST OF PARAMETERS
Par.no: Description Range Value
Internals
0Prog.ver. 0,00...9,99
O2-measuring
1Range 0..5%
0..10%
0..20%
0..100%
2High O2 0,0...99,9
3Low O2 0,0...99,9
4Barometer 800...1200
Relay 1
14 Function OFF
HIGH
LOW
15 Source O2-cont
ERROR
16 Level 0,0...99,9
17 Hysteresis 0,1...99,9
18 Delay on [s] 0...999
19 Dly fall [s] 0...999
20 Norm.pos. FALLEN
ACTIVE
Relay 2
21 Function OFF
HIGH
LOW
22 Source O2-cont
ERROR
23 Level 0,0...99,9
24 Hysteresis 0,1...99,9
25 Delay on [s] 0...999
26 Dly fall [s] 0...999
27 Norm.pos. FALLEN
ACTIVE
Outputs
28 Source 1 O2-cont
29 Signal 1 0..20mA
4..20mA
30 Source 2 O2-cont
31 Signal 2 0..10V
2..10V
Communication
32 Address 1...247
33 Location 0...32767
34 Protocol COMLI
35 Baud 600 b
1200 b
2400 b
4800 b
9600 b
36 Protect NO
YES
Par.no: Description Range Value
Current values
100 O2-cont 0,0...99,9
101 Nernst -0,50...4,50
102 Current 0,00...3,00
103 Voltage 0,00...9,99
104 Temp. 550...850
105 Reg. active NO
YES
106 Reg. out 0,00...100,00
107 CSP 0...999
108 Counter 0...65535
109 Counter OF -99...99
90 Cal. Temp. 550...850
91 Cal. Level 1520...6840
Status
110 R1 Func. OFF
WON
ON
W FALL
FALL
112 R2 Func. OFF
WON
ON
W FALL
FALL
114 Counting... STOP
UP
DOWN
115 Ionpump... STOP
PRESS
EVACU
Table of contents
Other Micatrone Transmitter manuals