Micropelt iTRV MVA 005 Application guide

MAR2019 Autor: Micropelt - Eine Marke der EH4 GmbH - DokumentenNr.: MVA005_1DS_0319v2e.docx
Wireless heating valve actuator
MVA005 EnOcean
User manual and device specification
EnOcean Equipment Profile A5-20-06
Annex: List of adapters and theft protection

MVA005
User manual and Datasheet
MAR 2019 Page 1 / 33 MVA005_1DS_0319v2e.docx
INDEX
INDEX 1
1Document history 2
2ERRATA 2
3Use and safety recommendations 3
4System description 4
4.1Picture MVA005 with dial for local control 6
5Energy-supply through thermal Energy Harvesting 7
6User Control - Quick overview table 8
6.1Installation with Manual Pairing (Teach-In) 8
6.2Local offset 8
6.3Deactivation and RESET 10
6.4Installation through SIGNAL telegram and Remote Commissioning 11
6.5Remarks Remote Commissioning 12
6.6Flowchart Remote Commissioning 13
6.7Flowchart Manual RESET 14
6.8Flowchart Teach-In, Mounting position and activation 15
7Notes on radio operation 16
7.1Transmission range 16
7.2Other interference sources 16
7.3Loss of communication with the room controller 16
8EnOcean Equipment Profile EEP A5-20-06 17
8.1Protocol data overview 17
8.2Description of individual functions 20
8.2.1Setpoint Selection (SPS) 20
8.2.2Operating mode (SP) 20
8.2.3Local offset (LO) 20
8.2.4Radio communication interval (RFC) 20
8.2.5Summer bit (SB) 21
8.2.6Valve recognition and ACO 21
8.2.7Window open detection (DWO) 21
8.2.8Radio strength and com. error (RSS & RCE) 21
8.2.9Reference Run (Maintenance) 21
8.3Radio telegram example 22
9EnOcean Remote Management (ReMan), Remote Commissioning (ReCom) 23
9.1EnOcean Link Table 23
9.2Outbound Teach-In 23
9.3ReMan supported functions 23
9.4ReCom Standard Functions 24
9.5ReCom internal MVA Parameter 25
10Extended Features and Functions 27
11Product ID and Label 28
12Performance data 29
13Mechanical Interface to Radiator Valve 31
14Annex 1: Adapter list 32
15Annex 2: Theft protection 33

MVA005
User manual and Datasheet
MAR 2019 Page 2 / 33 MVA005_1DS_0319v2e.docx
1 Document history
Date Description
V
ersion Status
31.08.2018
Transfer from released German version and first
release English version
0818_v1e Released
01.10.2018
Section 10:
Product ID 0x004900000001
Added product label picture
Added SEC CODE default valve
0818_v1e Released
01.03.2019
Dissolved Errata MVA005_V5.15.b.3
Added manual RESET SEC CODE
Freeze protection sensor changed from ambient
to flow
Radio loss set point changed
Added 2nd freeze protection value 0°C (SPS=1
and Setpoint 0°C)
Additional flow charts and descriptions
Added LED-signal with temperature sensor
failures (Short circuit, disconnection)
0319v2e.docx Released
2 ERRATA
VERSION
THEMA WORKAROUND
MVA005_V5.15.b.3 RECOM Standard Command RESET TO
DEFAULT not supported
Execute RECOM Operation and write
Default values
RESET SEC CODE TO DEFAULT not
supported
<>
MVA005_V5.26.a.7 4BS radio communication interval 120min
not supported
<>

MVA005
User manual and Datasheet
MAR 2019 Page 3 / 33 MVA005_1DS_0319v2e.docx
3 Use and safety recommendations
Dear valued customer,
Thank you for choosing our product. To operate the self-powered radiator actuator, please read this manual
carefully. Keep the instructions for future reference.
In case of questions, please contact:
Use and safety instructions:
The metallic part of the unit’s housing serves as a heat sink. Be sure that the air circulation around it
is not obstructed by furniture, curtains, plants, or other objects.
If the device has been stored in a cold environment, make sure that it resumes close to room
temperature before use. This is to prevent damaging due to condensation.
The thermostatic radiator valve is designed for indoor use only. Do not allow the thermostatic radiator
valve to get wet. Its sensitive electronics can be affected.
The unit is best cleaned with a dry or slightly damp cloth. Do not use aggressive cleaning agents or
solvents.
Refrain from exposing the unit to environmental stress such as high mechanical forces (do not step
on it), strong vibrations, direct sunlight or extreme temperatures.
The unit must not be disassembled or modified. In case you are unsure how to use the unit, please
get in touch with Micropelt.
Be aware that correct operation can be affected by strong electromagnetic fields. Typical sources of
such are mobile phones, 2-way radios, RC transmitters, microwave ovens, electric motors.
The housing contains actuated springs that can lead to injuries if released. For servicing, refer to
qualified service personnel.
The thermostatic radiator valve has been designed and must solely be used for the purpose of
controlling a M30 x 1.5 heater valve. Any other use may pose a hazard to the device itself, to the
equipment involved, or to the health of the user.
When operating the device in a workplace environment, be sure to observe the workplace regulations
that may apply.
Intended use: The self-powered thermostatic radiator valve is suitable solely for controlling water-filled heating
radiators. Any other use – including control of floor heating systems - is not permitted and can result in damage.
Do not disassemble or modify any part of the product. It is important to comply with the safety notice included
in these operating instructions.

MVA005
User manual and Datasheet
MAR 2019 Page 4 / 33 MVA005_1DS_0319v2e.docx
4 System description
This document defines the properties of Micropelt’s battery free, intelligent thermostatic radiator valve (iTRV).
MVA005 is an 868MHz EnOcean wireless actuator, which is self-powered through thermal energy harvesting.
It is used to single room control heating radiators with standard valve connection M30x1.5 (Section 13). To
operate the device, the unit must be paired with a compatible room controller or gateway unit supporting EEP
A5-20-06. The pairing is done either via manual 4BS Teach-In or trough EnOcean Remote Commissioning.
Once mounted and activated on the valve body, a calibration cycle starts to automatically adapt itself to the
individual valve and is ready for use. Adapter are available for a majority of non M30x1.5 valve bodies (Section
14).
Room controller time schedules can be conveniently used to set individual room temperatures at different
times and to a desired °C value. By lowering room temperatures in times of absence, heating costs can be
saved without any loss of comfort. Reducing the room temperature by only a few °C does further add to
reduction of heating energy consumption and respective CO2 pollution.
The actuator generates the required electrical energy for operation (motor, sensors and radio communication)
by means of a built-in thermoelectric generator (TEG) and therefore operates maintenance-free. It is powered
from the temperature difference between the radiator heat and ambient temperature (usually room
temperature). An additional energy source such as a battery or external power supply is not required. The
internal energy storage is fully charged upon delivery, so that sufficient energy is available for installation and
up to approximately one year of operation. In winter and heating season, the actuator then supplies itself
independently trough the converted heat of the heating circuit. Due to the surplus of generated energy in
winter, the internal storage provides sufficient energy for 365 days per year operation including transition
periods and summer.
The product is delivered in mounting position (off) with the valve plunger completely retracted. The drive does
recognize when installed on a valve body by means of internal force and travel distance measurement.
Unmounted activation does allow to execute Remote Commissioning operation (Instant SIGNAL telegram is
transmitted immediately after each activation from mounting position) but will always return the device back to
mounting position to switch off. The drive does have a built-in motor error detection "ACO". The ACO bit does
signal incomplete or unsuccessful reference runs from mounting, motor issues during normal operation as well
as motor runs from mounting position and back to mounting position (Section 8.2.6).
The actuator operates with the EnOcean equipment profiles EEP A5-20-06 in either valve position (% value
transmitted) or temperature setpoint using its internal temperature control loop (°C setpoint transmitted). The
device has a built-in flow temperature sensor to automatically switch its Radio communication cycle (2, 5 or
10 minutes) based on available radiator temperatures. Installation and activation will immediately set the radio
communication interval to every 2 minutes and for an installation period of 30 minutes to provide quicker
feedback (Section 8.2.9). The ambient temperature value transmitted during such installation period is the raw
and actual temperature (Without approximation and smoothing). The device transmits a variety of information
to the room control unit including flow and ambient temperature, received radio signal strength, radio
communication failure, window open detection (Refer to Section 8). The control units responds either with a
new position value in the range 0% (valve closed) to 100% (valve open) or temperature setpoint (0 ... 40°C).
Setpoint changes will be instantly processed and new position values are calculated.
The MVA005 has a red and a green LED to support and indicate successful or failed operations for activation
and deactivation (More details in Section 6).
The device is equipped with a dial for local user setpoint changes that are instantly transmitted to the room
controller. The controller however decides whether or not and how these local changes are accepted and
processed by responding with a corresponding telegram answer that includes or ignores the local change
request. In valve position mode, all local changes are transmitted as relative values. Changes in temperature
setpoint mode are added or subtracted to the current set point temperature and transmitted as absolute
temperature value on the controller (Section 8). Successful local inputs are confirmed by a corresponding
number of discreet ton signals. Successive inputs within a maximum time period of 5 seconds time are
transmitted as a result value to the room controller. Example: 2 x right (+ 2°C) followed by 2 tone signals.
Within the 5 seconds period 3 x left (-3°C) followed by 3 tones. The result of -1°C is transferred after 5 seconds

MVA005
User manual and Datasheet
MAR 2019 Page 5 / 33 MVA005_1DS_0319v2e.docx
on the room control unit. There will be no further tone signal to confirm the result of -1°C. Incorrect inputs will
be displayed by an approx. 2 seconds long red LED signal. Failed attempts will require a waiting period of 2
seconds. Local changes will lead to an instant telegram transmission to the room controller. In case of no
response from the correspondent room controller, another telegram will be transmitted 1 second later.
Integrated temperature sensors (valve body and environment) are both used to control the radio interval and
internal temperature controller, window-detection as well as freeze protection. The ambient sensor is used to
measure the room temperature. During heating operation, the ambient sensor is influenced by the near-field
of the radiator as well as self-heating of the metallic device housing. The resulting temperature failure due to
offset is compensated on the basis of the flow sensor and a built-in temperature compensation
(approximation), as well as a subsequent smoothing function. Within the first 30 minutes after activation, the
actuator sends the actual ambient temperature without any corrections. After 30 minutes, the device sets the
ambient temperature to its smoothing start value to 20°C that will be kept as long as the calibration cycle takes.
The approximation process in a non-heating cycle takes 3 x 10 minutes. Device activation in an active heating
cycle will extend the start value and smoothing cycle to as long as the measured ambient and flow sensor
values stabilize with deviations smaller than 1°C. When operated in temperature setpoint, the use of an
external room temperature sensor is recommended which is then transmitted to the MVA005 with every 4BS
telegram through the room controller. Without external room sensor, the built-in ambient sensor is used with
the respective in accuracy given the nearfield radiator environment or any other related effects such as
mounting position, curtains, furniture. (See picture 4.1).
Anti-freeze protection uses the flow sensor integrated in the metallic valve connection. Standard freeze
protection is active at <6°C. With a temperature setpoint transmission of 0°C, than the freeze protection
temperature is also lowered to 0°C. It does not matter if the 0°C setpoint value was requested by radio or by
manual adjustment.
Alternate flashing of red and green LEDs in 0.5 second intervals signals a sensor error (short circuit or
interruption). In this condition, normal operation is not possible.
Window open detects any temperature drop within a time period of 2 minutes on the local ambient temperature
sensor. Once a given negative temperature change is detected, the device sets the DWO bit (Section 8.2.7)
and immediately reports the state transmitting a 4BS telegram to the room controller. Its transmitted ambient
temperature is the actual temperature value (no approximation or smoothing). The window open detection
function is limited to the transmission of data telegrams and setting the DWO bit, no further internal reactions
by the actuator apply. The detection of a temperature drop depends on a recognizable stream of cold air in
the close environment of the actuator. For a reliable detection, the drive must be installed in unspoilt situation
and on radiators below the respective window. Fully opened windows in winter season are usually reliably
detected at low outside ambient temperatures. Window in tilt position and heaters in faraway distance to the
window cannot be detected reliable. The window open function is independent of the selected communication
interval and automatically runs every 2 minutes. Should the temperature fall further and below freeze protection
temperature of 6°C (respectively 0°C), the drive automatically opens to prevent from freeze related damages.
Radio failures after 6 unsuccessful 4BS communication attempts in paired situation are reported with its status
bit RCE. The actuator automatically switches to its internal temperature control using the last received and
valid temperature setpoint from the control unit. With the lack of a valid temperature setpoint °C value (e.g.
SPS=0 operation), the internal default value of 21°C is used. Radio signal strength of the received telegram
(RSS) is also activated due to lack of incoming data telegrams. There is no change on the radio communication
cycle. The local offset function of the dial remains active and any local adjustments are calculated from a
default value 21°C. E.g. 5 x left decreases the setpoint from 21°C to 16°C, independent from the last received
setpoint value. Due to lack of response from the master control unit keeps the drive this setpoint and regulates
accordingly. Consecutive local changes are again calculated from the default value of 21°C, e.g. 3 x right =
24°C followed by 1x right = 22°C. The drive returns to normal operation, once the radio communication is re-
established.
When permanently use in unheated rooms, the internal storage will be ultimately discharged. In such
circumstance, the drive automatically opens to 50% for recharging. For operation in unheated rooms, the valve
and its EEP A5-20-06 provide options to reduce and minimize energy consumption through either stand-by
operation (SBY Bit) or summer bit (SB) 8 hours radio interval. Using the local offset input, the drive can at any
time be activated from standby (SBY) and returns to normal operation.

MVA005
User manual and Datasheet
MAR 2019 Page 6 / 33 MVA005_1DS_0319v2e.docx
The MVA005 is equipped with hard - and software functions to simplify installation, control and real-time
monitoring. Apart from standard, manual 4BS teach-in are EnOcean Remote Commissioning (ReCom)
operations available to teach and configure the device prior deployment or during operation. ReCom is
operated with separate from 4BS and periodically transmitted SIGNAL (0x09) telegrams. Single or multiple
ReCom commands must be executed within an 8 seconds time period after the UNLOCK command. ReCom
can be used to set its link-table and change device-internal parameters such as control loop gain, temperature
offset parameter or readout of its internal storage value (Refer to Section 9.5).
The drive can be restarted by means of manual RESET (Section 6.5). Holding the dial in one of the two end
positions for 10 seconds restarts the drive, runs a reference run and activates the 30-minute maintenance
interval. The drive then communicates for the next 30 minutes in a 2 minute interval. The ambient temperature
is the effective measured temperature of the ambient sensor. After the maintenance interval, the temperature
approximation and smoothing function restarts. Existing teach-in connections to the room controller and
remote commissioning settings are retained during manual RESET.
4.1 Picture MVA005 with dial for
local control
Dial for local control with +/- marking.
One Red and Green LED are
positioned below the cover at marked
positions. The ambient temperature
sensor is centrally positioned between
both LEDs.
LED GREEN
Temperature Sensor
below the cover
LED RED
Dial

MVA005
User manual and Datasheet
MAR 2019 Page 7 / 33 MVA005_1DS_0319v2e.docx
5 Energy-supply through thermal Energy Harvesting
The actuator generates the necessary electrical energy for operation by means of a thermoelectric generator
(TEG), which gains electrical energy from the temperature difference between radiator flow and room
temperature. During the heating season, excess energy is accumulated in the internal storage for operation in
transition periods and summer. The energy balance of the actuator is designed to allow operation through 365
days per year when used in typical radiator heating installations.
If, in exceptional cases, the storage voltage drop below a certain limit, the actuator reports this status to the
room controller and takes the protection position (50% valve opening or maintains the set value, whichever is
the higher). Subsequently, the actuator goes to sleep and waits until the memory is re-charged by the
thermoelectric generator back to a sufficient level. As soon as enough energy is available, the actuator
resumes normal operation.
The protection position ensures that the heating valve cannot calcify in an end position and freeze protection
is ensured. Unexpected room temperatures will occur.

MVA005
User manual and Datasheet
MAR 2019 Page 8 / 33 MVA005_1DS_0319v2e.docx
6 User Control - Quick overview table
6.1 Installation with Manual Pairing (Teach-In)
No Objective Button
No.
Action LED or Tone
activity
Reasons for
failure
1 Pairing from
mounting
position
(OFF)
OR from
normal
operation
Turn dial to
end position
Left OR Right
and hold 5
seconds.
Unit transmits a teach telegram
(1x green LED), connects with
the controlling unit and confirms
the successful teach-in with a
second flash green LED.
The unit remains in mounting
position. Any actuator not in
mounting position will activate
the motor and return to
mounting position to switch off
the device.
After 5
seconds 1x
green LED for
teach sent
Teach-in
successful:
1x green LED
Failure (not
teached):
3x red LED
No tone
signals.
Controller or
gateway either
not present or
not in pairing
mode, so that
pairing fails
2 Mounting Mount the actuator before
executing run-in sequence and
normal operation.
Consider required adapter
(Section 14)
3 Reference run
and normal
operation
Turn to end
position
Left OR Right
for short press
(< 1 second)
Unit executes run-in sequence
and enters normal operation.
Radio communication will occur
every 2 minutes and for a time
duration of 30 minutes after
activation. Communication after
30 minutes follow the 4BS
settings transmitted by the room
control unit.
Success:
1x green LED
Failure:
3x red LED
No tone
signals
Mounting
failure (e.g.
missing
adapter),
Motor failure,
Gear failure
Unmounted will
return the
motor to
mounting
position and
switch off the
device.
6.2 Local offset
1 Local Offset
Operation in
Temperature
Setpoint (°C)
(Internal
control loop)
Turn to end
position
Left OR Right
for short
press.
Turn dial left for 1 or up to 5
times until its end position:
Every successful actuation will
decrease the actual setpoint
temperature by 1°C and transmit
the new setpoint as absolute
value.
Turn dial right for 1 or up to 5
times until its end position:
Every successful actuation will
increase the target temperature
by 1°C.
Success:
1 … 5 tone
signals
according the
number of
inputs
Failure:
Red flashing
LED for 2
seconds. (Left
and right
No tone
signals:
No local
actuation
detected or
accepted.
Device is in
mounting
position.

MVA005
User manual and Datasheet
MAR 2019 Page 9 / 33 MVA005_1DS_0319v2e.docx
The temperature setpoint may
be changed by up to +/- 5°C.
Multiple local inputs within one
cycle time frame of 5 seconds
are internally cumulated to one
desired target value.
Individual local input cycles are
open for a max. time window of
5 seconds and concluded with a
telegram transmit including the
desired target temperature as
absolute °C temperature value.
Resulting changes in motor
position will only be executed
when the room controller
confirms the local change with
its responding and next data
telegram.
inputs in one
cycle).
Wait for 10
seconds.
2 Local Offset
Operation in
Valve Position
(%)
Turn to end
position
Left OR Right
for short
press.
Turn dial left for 1 or up to 5
times until its end position:
Every successful actuation will
signalize the controller the
desired reduction in target
temperature with a relative value
(e.g. 0x7F for -1)
Turn dial right for 1 or up to 5
times until its end position:
Every successful actuation will
signalize the controller the
desired increase in target
temperature with a relative
value. (0x01 when +1)
The desired temperature
setpoint change communicated
to the controller may be
changed by up to +/- 5.
Multiple local inputs within one
cycle time frame of 5 seconds
are internally cumulated to one
desired target value.
Individual local input cycles are
open for a max. time window of
5 seconds and concluded with a
telegram transmit including the
desired target temperature as
absolute °C temperature value.
Resulting changes in motor
position will be executed when
the room controller confirms the
local change with its responding
and next data telegram.
Success:
1 … 5 tone
signals
according the
number of
inputs
Failure:
Red flashing
LED for 2
seconds. (Left
and right
inputs in one
cycle).
Wait for 10
seconds.
No tone
signals:
No local
actuation
detected or
accepted.
Device is in
mounting
position.

MVA005
User manual and Datasheet
MAR 2019 Page 10 / 33 MVA005_1DS_0319v2e.docx
6.3 Deactivation and RESET
1 Deactivate,
Move to
mounting
position,
Switch off
Disassembly
Turn to end
position
Left OR Right
and hold for at
least 5 sec.
Green LED appears, than
release.
3x red LED indicates teach-in
failure which however does not
play any role when deactivating
the device. Motor moves back to
mounting position and device
switches off.
Reactivation in mounted position
will restart the device with no
changes to previously set
parameters including link table
settings to enter normal
operation.
Success:
After 5
seconds 1x
green LED
followed by 3x
red LED
Failure:
No LED
No tone
signals
No LEDs:
Try again and
hold the dial
end position
tight. Do not
release during
the 5 seconds
time period.
2 RESET
followed by
normal
operation.
Turn to end
position
Left OR Right
and hold for
10sec.
Turn dial to left or right until its
end position and hold for at least
10 seconds until the 2nd green
LED appears, than release.
When mounted, teached and
active:
Device enters installation radio
cycle of 2 minutes for a 30
minutes duration. Transmitted
ambient temperature is the raw
and actual temperature (no
approximation, no smoothing).
In case of Radio communication
failure: Device switches to
Temperature setpoint and 21°C.
Success:
1x green LED
after 5
seconds
followed by a
2nd green
LED after
another 5
seconds
(10 seconds
in total).
No LEDs:
Try again and
hold the dial
end position
tight. Do not
release during
the 10 seconds
time period.

MVA005
User manual and Datasheet
MAR 2019 Page 11 / 33 MVA005_1DS_0319v2e.docx
6.4 Installation through SIGNAL telegram and Remote Commissioning
In order to teach and configure the drive via ReCom, it is mandatory to change the default security code first!
No Objective Button
No.
Action LED or Tone
activity
Reasons for
failure
1 Change
security code
from
mounting
position
Turn dial to
end position
Left OR Right
for short
press.
The drive is activated and sends
a SIGNAL telegram. The room
controller changes the default
security code of the drive and
prepares it for the configuration.
The device then carries out a
reference run. When mounted,
the drive activates and transmits
a 4BS telegram every 2 minutes,
as well as every 12 hours
(default) a SIGNAL telegram.
Unmounted: Device goes into
the mounting position and shuts
off.
NONE
If the drive
does not react
to ReCom
communicatio
n, then the
change in the
security code
may have
failed.
2 SIGNAL
and
ReCom from
mounting
position
(Security
code has
been
changed)
Turn to end
position
Left OR Right
for short
press.
The unit activates and transmits
one single SIGNAL telegram to
allow the controller to change
desired Linktable and/or
parameter.
Device executes Reference run
to either activate (mounted) or
return to mounting position and
switch off (unmounted). Each
Signal telegram will be followed
by standard 4BS telegram.
No tone
signals
Successful
execution of
device
internal
ReCom
Parameter:
green-red-
red
If the drive
cannot be
configured, the
security code
may not be
changed
successfully
1
&
2
The commands SEC CODE change, write link table, write parameters can also be performed in a
single ReCom session (note TCM Maturity Time).
3 Configuration
with SIGNAL
and ReCom
from normal
operation
(Security
code has
already been
changed)
NONE The drive sends a SIGNAL
telegram every 12h (default
interval), giving the room
controller the opportunity to
configure.
Thereafter, the drive continues
its normal operation
Successful
execution of
device
internal
ReCom
Parameter:
green-red-
red
All further standard installation and use procedures are identical with manual teach-in (Sections 6.2 and 6.3):
Assembly
Reference run →Normal operation
Setpoint adjustment
Mounting position = Off →Disassemble
Manual reset

MVA005
User manual and Datasheet
MAR 2019 Page 12 / 33 MVA005_1DS_0319v2e.docx
Note: As long as the link table is not correctly described (no teach-in), the drive will remain in self-controlled
mode at 21°C and does ignore any room controller. Local inputs / changes to the setpoint temperature on the
dial are possible. Local entries lead to the immediate transmission of a data telegram.
6.5 Remarks Remote Commissioning
The ReCom specification of the EnOcean Alliance applies
ReMan / ReCom processes are executed in response to the signal sent by the drive (SIG)
SIG telegrams are sent:
oEvery time the drive is started from the installation position
oFor drives in operation: Deactivate the drive by turning it against the left or right stop, hold
for 5 seconds until 1x green LED, release, 3x red LED
oCyclic, during operation and parallel to regular 4BS communication in a default time interval
of 12 hours
NOTE: The SIG telegram interval can only be changed by means of ReCom (see product
specification).
The maximum waiting time for an UNLOCK response to a signal telegram is 1 second
NOTE: Analogous to 4BS communication on A5-20-01 and A5-20-06
ReCom starts with an UNLOCK, the required Default Security Code (SC) is 0x53C65E34
Writing the link table and parameters requires prior modification of the Default Security Code
Invalid SCs (0x00000000 and 0xFFFFFFFF) are automatically reset to the default SC
Changing the SC plus writing the link table plus writing parameters can be done in one pass.
The sequence of processing individual parameters or sequence of link table / parameter is freely
selectable.
NOTE: Note the Maturity time of the radio module with successive commands.
The maximum available time window between UNLOCK and LOCK is 8 seconds
If there is physical access to the device, the SEC CODE can be manually reset to its default value
Proceed as follows:
1st. Bring the device into the assembly position
2nd. Turn the adjusting wheel to the left against the stop and hold
→After 5 seconds 1x green LED, after another 5 second 1x green LED
3rd. Turn to the right within one second and hold for 5 seconds
→1x green LED
4th. Within 2 seconds, turn 2x briefly to the left against the stop
→2x green LED
→The SEC CODE has been reset to its default value 0x53C65E34

MVA005
User manual and Datasheet
MAR 2019 Page 13 / 33 MVA005_1DS_0319v2e.docx
6.6 Flowchart Remote Commissioning
6.6.1 Typical ReCom-procedure
6.6.1 Reset Security code through invalid SEC CODE values
Wait for SIGNAL Telegram
(RORG SIG)
UNLOCK 0x0001
SET CODE 0x0003
SEC CODE already
changed?
NO (Default SEC CODE = 0x53C65E34)
YES
SET LINK TABLE 0x0212
GET LINK TABLE 0x0211
SET DEVICE CONFIG. 0x0231
GET DEVICE CONFIG. 0x0230
GET PRODUCT ID 0x0227
LOCK 0x002
MAX. TIME WINDOW
BETWEEN UNLOCK AND
LOCK = 8 SECONDS
Signal Telegrams are transmitted:
a. Instantly when device is activated from mounting position. To
deactivate: Turn local control device to end position left or right and
hold for 5 seconds until 1x green LED followed by 3x red LED. To
activate the device turn to end position left or right for short press
(<1 second).
b. Periodically and independent from 4BS telegrams. Default cycle time
is 12h.
Signal Telegramme werden gesendet:
a. Sofort bei Aktivierung aus der Montagepositon. Gerät deaktivieren in
die Montageposition durch Stellrad nach Links oder Rechts bis
Anschlag und 5 Sekunden halten bis 1x grüne LED gefolgt von 3x
rote LED. Aktivieren durch kurzes halten des Stellrades nach Links
oder Rechts (< 1 Sekunde).
b. Periodisch und unabhängig von 4BS Telegrammen. Default
Command sequence in any order
(Refer to Section 9)
Kommandos in beliebiger Reihenfolge
(Siehe auch Abschnitt 9)
MAX. TIME WINDOW TO
UNLOCK = 1 SECOND
Wait for SIGNAL Telegram
(RORG SIG)
UNLOCK 0x0001
SET CODE 0x0003
0xFFFFFFFF OR
0x00000000
NO
Default SEC CODE = 0x53C65E34
SEC CODE already
changed?
YES
EXAMPLE 0x78DC9AB9
SEC CODE is RESET to
manufacturer Default value =
0x53C65E34
INVALID / UNGÜLTIGE
SEC CODES

MVA005
User manual and Datasheet
MAR 2019 Page 14 / 33 MVA005_1DS_0319v2e.docx
6.7 Flowchart Manual RESET
.. mounted
correctly
...isinmountingposition
(novalidzero pointreference)
.. notmounted
correctly
..released
.. held
After5sec1xgreenLED
User‐
input
Afterfurther5sec1xgreen LED,
releasedial
Dial..
TurnDialtoleftor
rightuntil itsend
position ..
2xredLED
(ProcessorRestart)
Motorexecutes
referencerun
Motormovesto
mountingposition
3x redLED
(novalvedetected)
Motormovesbackto
mountingposition
Motormovesto
50%position
Device
is..
1x greenLED
(referenceruncorrect)
Deviceisin
normal
operation
Device for30min.in
maintenancemode*
2xredLED
(ProcessorRestart)
..hasvalidzeroreference*
Motormovestoend
position
Deviceisin
mountingposition
=off
Deviceisin
mountingposition
=off
Device ..
..andrelease
..andhold
Activationlocaloffset
ManualTeach &
mountingposition
activatewithmanual
action onitsdial

MVA005
User manual and Datasheet
MAR 2019 Page 15 / 33 MVA005_1DS_0319v2e.docx
6.8 Flowchart Teach-In, Mounting position and activation
* Remarks to the flowcharts 6.5 and 6.6
"no response within 1 sec” Device has received no radio answer and therefore transmits the user
offset a second time.
With radio answer from the controller, only one telegram is sent
"does (not) have a valid zero point
reference”
The device receives its zero reference by a reference run. He loses it by
driving in mounting position.
Note: A device that has been unscrewed from the valve without moving to
mounting position retains its zero reference!
"maintenance mode" In this mode, the device communicates the actual measured
uncompensated ambient temperature. In addition, the radio period is 2
min.
After 30 minutes, the device switches to normal operation.
activatewithmanual
action onitsdial
..correction
withnew
input
..instant
response
..noresponse
within1sec*
..confirmed
..notconfirmed
.. mounted
.. notmounted
..mountingposition(off)
..normaloperation
Local offset
Motormovesto
mountingposition
Radiotransmits
Teach‐InRequest
Teach‐In..
1x greenLED
3xredLED
Deviceisin
mountingposition
=off
Tonesignal
1xtone
Deviceisin
normal
operation
Deviceis
in..
Motorexecutes
referencerun
1x greenLED
(successfulreference
run)
Device is
..
3x redLED
(no valvedetected)
Motormovesbackto
mountingposition
Device isin
mountingposition
=off
Radiotransmits
User‐Offset
Radio
receives ..
Radiotransmits
User‐Offsetagain
5sec
watingtime
User..
Device for30min.in
maintenancemode*
..released
..holdfor 10sec.
..andrelease
..held
After5sec1xgreenLED
User‐
input
Dial..
TurnDialtoleftor
rightuntil itsend
position ..
ManualRESET
Activationlocaloffset
ManualTeach &
mountingposition
Activation
activatewithmanual
action onitsdial
1x greenLED
teach‐telegram
transmitted

MVA005
User manual and Datasheet
MAR 2019 Page 16 / 33 MVA005_1DS_0319v2e.docx
7 Notes on radio operation
7.1 Transmission range
The radio transmission range is limited by both the distance between transmitter and receiver, and by
interference. Indoors, building materials play an important role. Major reflections and signal losses are due to
metallic parts, such as reinforcements in walls and metallized foils, which are used on thermal insulation
products.
Penetration of radio signals:
Material Penetration
Wood, gypsum, uncoated glass 90..100 %
Brick, chipboard 65.. 95 %
Reinforced concrete 10.. 90 %
Metal, aluminum facings 0.. 10 %
For an evaluation of the environment, please see guide values listed below:
Conditions Range / penetration
Line-of-sight Typ 30 m range in passages, up to 100 m in
halls
Plasterboard and wood walls Typ 30 m range through max. 5 walls
Brick and foamed concrete walls Typ 20 m range through max. 3 walls
Reinforced concrete walls & ceilings Typ 10 m range through max. 1 ceiling
Supply blocks and lift shafts should be treated as shields.
In addition, the angle at which the signal enters the wall has to be considered. A shallow angle increases the
effective wall strength as well as the attenuation of the signal. Whenever possible, signals should enter walls
perpendicularly. Alcoves should be circumvented.
For additional information, refer to the EnOcean White Paper “EnOcean Wireless
Systems – Range Planning Guide”.
7.2 Other interference sources
Common sources of interference are devices that generate high-frequency signals. These are typically
computers, audio-/video systems, electronic transformers and ballasts. The distance of the actuator to such
devices should be more than 0.5 m.
7.3 Loss of communication with the room controller
If the actuator cannot establish a dependable radio communication with the room controller, i.e. more than 6
times in sequence the room controller does not receive a radio signal, then the actuator switches to a
reduced radio pattern. The typical 10 minute radio period is extended to one transmission every hour,
reducing the energy consumption while radio contact is interrupted. In addition, the actuator enters the safe
position. Once the radio contact to the room controller recovers, the actuator reverts to requesting
instructions from the controller every 10 minutes.

MVA005
User manual and Datasheet
MAR 2019 Page 17 / 33 MVA005_1DS_0319v2e.docx
8 EnOcean Equipment Profile EEP A5-20-06
Radio communication is periodically and bidirectional exclusively following the Micropelt designed and
MVA005 customized EnOcean Equipment Profile EEP A5 20-06 (Harvesting-powered actuator with local
temperature offset control (BI-DIR).
8.1 Protocol data overview
From MVA005 to Control unit: (DIRECTION-1: TRANSMIT DATA - FROM ACT to RCU)
Offset Size Bit-
range
Data Short-
Cut
Description
V
alid
Range
Scale Unit
0 8
DB3.7...
DB3.0 Current value CV Current Valve
position
0…100dec 0…100 %
101…255 (0x65…0xFF) reserved
8 1 DB2.7
Local Offset
Mode LOM
Local Offset Mode
defines the format of
LO
0 = LO is relative
(temperature offset)
1 = LO is absolute
(temperature with offset)
9 7
DB2.6 …
DB2.0 Local Offset LO
LOM =1, use with temperature setpoint mode (DIR-2,
DB1.2, SPS = 1)
Current temperature
set-point plus /
minus local offset
are communicated
as an absolute
temperature value
[°C]
Temperature setpoint °C +/- local
offset °C
0…80dec 0…+40 ºC
81…255 (0x51…0xFF)
reserved
LOM = 0, use with valve position mode (DIR-2, DB1.2,
SPS = 0)
Local offset setting
is communicated
directly
0x0: 0 °C (Default)
0x1: 1 °C
0x2: 2 °C
0x3: 3 °C
0x4: 4 °C
0x5: 5 °C
0x7B:-5 °C
0x7C:-4 °C
0x7D:-3 °C
0x7E:-2 °C
0x7F:-1 °C
16 8
DB1.7…
DB1.0 Temperature TMP
Local Ambient
or
Feed temperature
(Selected by
Direction 2, DB1.1)
Local ambient temperature:
0…80dec 0…+40 °C
81…254 (0x51…0xFE) reserved
Feed temperature:
0…160dec 0…+80 °C
161…254 (0xA1…0xFE) reserved
0xFF = Sensor failure or out of
range (either ambient or feed or
both of them)
24 1 DB0.7
Temperature
Selection TSL
Indicates which
sensor is used for
TMP
0: Ambient sensor temp
1: Feed sensor temperature
25 1 DB0.6
Energy Input
Enabled ENIE Harvesting status 0: Not harvesting
1: Harvesting active
26 1 DB0.5 Energy
Storage ES Charge level of
energy storage
0: Low, almost discharged
1: Sufficiently charged

MVA005
User manual and Datasheet
MAR 2019 Page 18 / 33 MVA005_1DS_0319v2e.docx
27 1 DB0.4
Window open
detection DWO Window open
detection
0: No open window detected
1: Open window detected
28 1 DB0.3 LRN Bit LRNB Telegram type 0: Teach-in telegram
1: Data telegram
29 1 DB0.2
Radio Com
Error RCE
Indicates radio
communication
errors
0: Radio communication is stable
1: Six or more consecutive radio
communication errors have
occurred
30 1 DB0.1
Radio Signal
Strength RSS Weak radio signal
warning
0: Radio signal is strong
1: Radio signal is weak
(-77 dBm or less)
31 1 DB0.0 Actuator
obstructed ACO
Reports blocked
actuator (motor)
Reference run not
successfully
completed
0: Actuator working correctly
1: Actuator is blocked
From Control unit to MVA005: (DIRECTION-2 RECEIVE DATA - FROM RCU TO ACT)
Offset Size Bit-
range
Data Short-
Cut
Description
V
alid
Range
Scale Unit
0 8
DB3.7…
DB3.0
Valve position
or
Temperature
Setpoint
SP
Valve Position
or
Temperature
Setpoint
Selection with
DB1.2
0..100dec 0…100 %
101…255 (0x65…0xFF)
reserved
Or
0…80dec 0…+40 ºC
81…255 (0x51…0xFF) reserved
8 8
DB2.7…
DB2.0
Temperature
from RCU TMP
Room temperature
from room control
unit (RCU)
0..160dec 0…+40 °C
161…254 (0xA1…0xFE)
reserved
Special values 0 and 0xFF:
IF SPS=1, use actuator-internal
temperature sensor.
16 1 DB1.7
Reference
Run REF Execute reference-
run
0: Normal operation
1: Reference-run
17 3
DB1.6…
DB1.4
RF
Communicatio
n interval
RFC
Radio duty cycle
selection.
Find additional
information in the
Appendix
0b000: AUTO (default)
2, 5 or 10 minutes
0b001: 2 minutes
0b010: 5 minutes
0b011: 10 minutes
0b100: 20 minutes
0b101: 30 minutes
0b110: 60 minutes
0b111: 120 minutes
20 1 DB1.3 Summer Bit SB
Initiate summer
mode (reduced
communication)
0: Normal operation
1: Summer mode with
8h radio duty cycle
21 1 DB1.2
Set Point
Selection SPS Setpoint selection
for DB3
0: Valve position mode
(0…100%)
1: Temperature setpoint
(0…40°C), actuator-
internal temperature
controller is used

MVA005
User manual and Datasheet
MAR 2019 Page 19 / 33 MVA005_1DS_0319v2e.docx
22 1 DB1.1
Temperature
Selection TSL
Temperature
requested from the
actuator
(DB1.7…DB1.0,
DIR-1, TMP)
0: Request ambient
temperature
1: Request feed
temperature
23 1 DB1.0 Standby SBY
Enter standby
mode, refer to
Appendix
0: Normal operation
1: Standby
24 4
DB0.7…
DB0.4 Not used Set to 0
28 1 DB0.3 LRN Bit LRNB LRN Bit 0: Teach-in telegram
1: Data telegram
29 3
DB0.2…
DB0.0 Not used Set to 0
Further details can be found on www.enocean-alliance.org.
Other manuals for iTRV MVA 005
1
Table of contents
Other Micropelt Controllers manuals

Micropelt
Micropelt iTRV User manual

Micropelt
Micropelt MVA004 EnOcean Application guide

Micropelt
Micropelt MVA003 EnOcean User manual

Micropelt
Micropelt MLR003 User manual

Micropelt
Micropelt iTRV MVA 005 User manual

Micropelt
Micropelt MVA004 EnOcean Application guide

Micropelt
Micropelt MVA003 EnOcean User manual

Micropelt
Micropelt EnOcean MVA003E Application guide