19
18
WEAK/BAD BATTERY
TheUPS automaticallyteststhebattery’s conditionandwillilluminate the Weak/
Bad Battery icon and sound the alarm. This alarm will be repeated until the
batteries pass a self test. If the battery is weak, bad or disconnected, the
Weak/BadBatteryiconwillilluminateandthealarm will beep three times every
five-minutes until the battery is reconnected or replaced. It is recommended
thattheUPSbeallowedtochargeovernightbeforeperforming a battery test to
confirm a Weak/Bad Battery condition.
OVERLOAD
When the amount of load attached to the UPS exceeds 110% of its power
rating;theOverloadiconwillflashOffandOn,alloftheLEDsintheLoadLevel
Bar Graph will be illuminated and the UPS will sound a constant alarm. This
alarmwill remain on until the excessload is removed or the UPS’sself protec-
tion circuit shuts the UPS down. If the UPS shuts down because of an Over-
load condition, the UPS must perform an Inverter function or a Self Test to
cleartheOverloadAlarm.
ALARMS
ON BATTERY
WhentheUPSis operating on the batteries, the On-Battery icon willilluminate
and the audible alarm will sound once every ten-seconds. The alarm will stop
once the UPS returns to theAC normal mode.
LOW BATTERYWARNING
The UPS will sound two beeps every five-seconds when the battery reserve
runs low. This condition will continue untilAC returns or the UPS shuts down
frombatteryexhaustion.
UPS FAULT
When the UPS detects a hardware fault, the Fault icon will illuminate and the
UPSwill sound a constant alarm. The faultcondition, in some instances, may
be reset by turning the UPS off and then on.
RJ11 REPO (Remote Emergency Power Off) PORT
Connect one end of the RJ11 cable to the REPO port and the other end of the
RJ11 cable to the EPO switch. In the AC or the Battery mode short pin4 to
pin5 for approximately 0.5-seconds to shutdown the UPS. The UPS must be
turned off and then back on again to restart the UPS. The LCD will display
EPo for this function.
NOTE: TheLCDbacklight will illuminate for 1-minute when theUPS switches
to the Battery mode. When the UPS has an event and/or an error code the
LCD backlight will turn on and remain on to alert the user that an event has
occurred.
ErrorCode: E01. UPSisshut-
down.
Symptom / Error Code Cause / What To Do
PresstheOn/Off/Test button and release after one beep.
UPS will not turn on. Reset the input circuit breaker by pressing the plunger back in. If
theinput circuit breaker trips afterUPSrestarts, reduce the load on
the UPS.
UPSoperatesinbatterymode
only, even though there isAC
present.
The AC normal icon is illumi-
nated, but there is no output. Disconnectthecomputer cable from the UPS, press the Onbutton.
If UPS works normally, the software has control of the UPS.
Charge the batteries for 8-hours and retest. If the runtime is still
less than expected, the batteries may need to be replaced.
UPSdoes not provide
expectedruntime.
The AC Normal icon is blink-
ing. The UPS is in either the Boost or the Buck mode. It is performing
its intended function.
TheUPS has an internal problem. Call for service.
Faulticon is illuminated and a
constantalarm.
Error Code: E02. Overload
iconisilluminatedanda con-
stant alarm.
Check the specifications and remove part of the load. If the UPS
shuts down because of an Overload, the UPS must perform an
Inverter function or a Self Test to clear the Overload Alarm.
The UPS has detected a short-circuit on its output. Check the at-
tachedload.
ErrorCode: E03.UPSis shut-
down. Theinternal or ambinettemperature has exceeded thetemperature
ratings. Check the specifications.
Error Code: E04. Input Over
CurrentProtection Warning. Check the specifications and remove part of the load.
ErrorCode: E11:Inverter/Out-
putFailure Shutdown. The UPS has an internal fault. Call for service.
Error Code: E12. DCBUS
OVPShutdown. The UPS has an internal fault. Call for service.
Error Code: E13. Fan Fail
Warning. Thefan has either failed or has stopped duetoexessive dirt. If the
fanhasfailed,call forservice. Ifthe fanis dirty,use acan of"Canned
Air" to clean the fan.
ErrorCode:E14. ChargerFail-
ureWarning. The charger has failed, call for service.
Error Code: E16. SWF icon
is illuminated. Havea qualified electrician correct the service wiring.
Error Code: E15. Weak/Bad
Battery icon is illuminated. Check the battery connections, charge the batteries for 8-hours
and retest, or replace the batteries.
ErrorCode: E17. Low
BatteryWarning. TheUPS'sbatteryreserve is low. This condition will continue until
AC returns or the UPS shuts down from battery exhaustion.
ErrorCode: E18. Low
Battery Capacity.
ErrorCode:E05. Inputvoltage
outof range. One of the following Errors has occurred E06, E12, or E13. The
AVR andtheBattery mode functions will not work.Call for service.
Error Code: E06. Ambient
OverTemperatureProtection. Theinternaltemperature of the UPS has exceeded the safe oper-
ating range for the UPS. Check the specifications.
The UPS's battery capacity is low. Charge the batteries for 24-
hours.
OPTION SLOT
The option slot on the rear panel of the UPS is for option cards. Contact your
local dealer for the available option cards.