MEES20K033
PEFY-P-VMA3-E
3
1. SPECIFICATIONS Ceiling concealed (Medium static pressure type)
Model PEFY-P50VMA3-E PEFY-P63VMA3-E PEFY-P71VMA3-E PEFY-P80VMA3-E
Power source 1-phase 220-230-240 V 50/60
Hz
1-phase 220-230-240 V 50/60
Hz
1-phase 220-230-240 V 50/60
Hz
1-phase 220-230-240 V 50/60
Hz
Cooling capacity *1 kW 5.6 7.1 8.0 9.0
(Nominal) *1 kcal/h 4,800 6,100 6,900 7,700
*1 BTU/h 19,100 24,200 27,300 30,700
*2 Power input kW 0.360 0.360 0.360 0.360
*2 Current input A 2.21 2.21 2.21 2.21
Heating capacity *3 kW 6.3 8.0 9.0 10.0
(Nominal) *3 kcal/h 5,400 6,900 7,700 8,600
*3 BTU/h 21,500 27,300 30,700 34,100
*2 Power input kW 0.340 0.340 0.340 0.340
*2 Current input A 2.10 2.10 2.10 2.10
External finish Galvanized steel plate Galvanized steel plate Galvanized steel plate Galvanized steel plate
External dimension H x W x D mm 250 x 1,600 x 732 250 x 1,600 x 732 250 x 1,600 x 732 250 x 1,600 x 732
in. 9-7/8 x 63 x 28-7/8 9-7/8 x 63 x 28-7/8 9-7/8 x 63 x 28-7/8 9-7/8 x 63 x 28-7/8
Net weight kg (lbs) 46 (102) 46 (102) 46 (102) 46 (102)
Heat exchanger Cross fin (Aluminum fin and
copper tube)
Cross fin (Aluminum fin and
copper tube)
Cross fin (Aluminum fin and
copper tube)
Cross fin (Aluminum fin and
copper tube)
FAN Type x Quantity Sirocco fan x 2 Sirocco fan x 2 Sirocco fan x 2 Sirocco fan x 2
*4 External static press. Pa <35> - 50 - <70> - <100> -
<125>
<35> - 50 - <70> - <100> -
<125>
<35> - 50 - <70> - <100> -
<125>
<35> - 50 - <70> - <100> -
<125>
mmH2O<3.6> - 5.1 - <7.1> - <10.2> -
<12.7>
<3.6> - 5.1 - <7.1> - <10.2> -
<12.7>
<3.6> - 5.1 - <7.1> - <10.2> -
<12.7>
<3.6> - 5.1 - <7.1> - <10.2> -
<12.7>
Motor Type DC motor DC motor DC motor DC motor
Motor output kW 0.244 0.244 0.244 0.244
Driving mechanism Direct-driven by motor Direct-driven by motor Direct-driven by motor Direct-driven by motor
Air flow rate (Low-Mid-High) (Low-Mid-High) (Low-Mid-High) (Low-Mid-High)
m3/min 29.5 - 35.5 - 42.0 29.5 - 35.5 - 42.0 29.5 - 35.5 - 42.0 29.5 - 35.5 - 42.0
L/s 492 - 592 - 700 492 - 592 - 700 492 - 592 - 700 492 - 592 - 700
cfm 1,042 - 1,254 - 1,483 1,042 - 1,254 - 1,483 1,042 - 1,254 - 1,483 1,042 - 1,254 - 1,483
Sound pressure level (measured in anechoic room) (Low-Mid-High) (Low-Mid-High) (Low-Mid-High) (Low-Mid-High)
*2, 5 dB <A> 36-41-45 36-41-45 36-41-45 36-41-45
*2, 6 33-37-42 33-37-42 33-37-42 33-37-42
Insulation material EPS, Polyethylene foam, Ure-
thane foam
EPS, Polyethylene foam, Ure-
thane foam
EPS, Polyethylene foam, Ure-
thane foam
EPS, Polyethylene foam, Ure-
thane foam
Air filter PP honeycomb fabric. PP honeycomb fabric. PP honeycomb fabric. PP honeycomb fabric.
Protection device Fuse Fuse Fuse Fuse
Refrigerant control device LEV LEV LEV LEV
Connectable outdoor unit R410A CITY MULTI R410A CITY MULTI R410A CITY MULTI R410A CITY MULTI
Refrigerant piping Liquid mm (in.) 6.35 (1/4)Brazed 9.52 (3/8)Brazed 9.52 (3/8)Brazed 9.52 (3/8)Brazed
diameter Gas mm (in.) 12.7 (1/2)Brazed 15.88 (5/8)Brazed 15.88 (5/8)Brazed 15.88 (5/8)Brazed
Field drain pipe size mm (in.) O.D.32 (1-1/4) O.D.32 (1-1/4) O.D.32 (1-1/4) O.D.32 (1-1/4)
Drawing External KS94C654 KS94C654 KS94C654 KS94C654
Wiring KS94C652 KS94C652 KS94C652 KS94C652
Refrigerant cycle ----
Standard attachment Document Installation Manual, Instruc-
tion Book
Installation Manual, Instruc-
tion Book
Installation Manual, Instruc-
tion Book
Installation Manual, Instruc-
tion Book
Accessory
Insulation pipe for refrigerant
pipe, Washer, Drain hose, Tie
band
Insulation pipe for refrigerant
pipe, Washer, Drain hose, Tie
band
Insulation pipe for refrigerant
pipe, Washer, Drain hose, Tie
band
Insulation pipe for refrigerant
pipe, Washer, Drain hose, Tie
band
Optional parts Filter box PAC-KE95TB-E PAC-KE95TB-E PAC-KE95TB-E PAC-KE95TB-E
Remarks * Details on foundation work,
duct work, insulation work,
electrical wiring, power source
switch, and other items shall
be referred to the Installation
Manual.
* Details on foundation work,
duct work, insulation work,
electrical wiring, power source
switch, and other items shall
be referred to the Installation
Manual.
* Details on foundation work,
duct work, insulation work,
electrical wiring, power source
switch, and other items shall
be referred to the Installation
Manual.
* Details on foundation work,
duct work, insulation work,
electrical wiring, power source
switch, and other items shall
be referred to the Installation
Manual.
Notes: Unit converter
1.Nominal cooling conditions
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B. (95°FD.B.)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.The values are measured at the factory setting of external static pressure.
3.Nominal heating conditions
Indoor: 20°CD.B. (68°FD.B.), Outdoor: 7°CD.B./6°CW.B. (45°FD.B./43°FW.B.)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
4.The factory setting of external static pressure is shown without < >.
Refer to "Fan characteristics curves", according to the external static pressure, in DATA BOOK for the usable
range of air flow rate.
5.Measured in anechoic room with a 1 m air inlet duct and 2 m air outlet duct attached to the unit and 1.5 m below
the unit.
6.Measured in anechoic room with a 2 m air inlet duct and 2 m air outlet duct attached to the unit and 1.5 m below
the unit.
* PEFY-P50, 63, 71, 80VMA3-E cannot be connected to PUMY-SP112, 125, 140VKM/YKM and PUMY-P112, 125, 140VKM5/YKM(E)4.
* PEFY-P50, 71, 80VMA3-E cannot be connected to PUMY-P200YKM2.
kcal/h =kW x 860
BTU/h =kW x 3,412
cfm =m3/min x 35.31
lbs =kg/0.4536
*Above specification data is
subject to rounding variation.
0000005969.BOOK 3 ページ 2020年9月2日 水曜日 午後2時38分