EN
EN-1
Contents
1. Safety precautions ......................................................................................... 1
2. Selecting the installation location................................................................... 2
3. Installation diagram........................................................................................ 3
4. Installing the indoor unit................................................................................. 3
5. Refrigerant piping work.................................................................................. 5
6. Drainage piping work..................................................................................... 7
7. Electrical work................................................................................................ 8
8. Test run ........................................................................................................ 15
9. System control ............................................................................................. 17
10. Installing the grille........................................................................................ 17
11. Easy maintenance function.......................................................................... 20
1. Safety precautions
►Beforeinstallingtheunit,makesureyoureadallthe“SafetyPrecautions”.
►The“SafetyPrecautions”provideveryimportantpointsregardingsafety.Makesureyoufollowthem.
►Pleasereporttoyoursupplyauthorityorobtaintheirconsentbeforeconnectingthisequipmenttothepowersupplysystem.
Symbolsusedinthetext
Warning:
Describesprecautionsthatshouldbeobservedtopreventdangerofinjuryor
deathtotheuser.
Caution:
Describesprecautionsthatshouldbeobservedtopreventdamagetothe
unit.
Symbolsusedintheillustrations
: Indicates a part which must be grounded.
: Be sure not to do.
After installation work has been completed, explain the “Safety Precautions,” use,
and maintenance of the unit to the customer according to the information in the
Operation Manual and perform the test run to ensure normal operation. Both the
Installation Manual and Operation Manual must be given to the user for keeping.
These manuals must be passed on to subsequent users.
MEANINGSOFSYMBOLSDISPLAYEDONTHEUNIT
WARNING
(Risk of re)
This mark is for R32 refrigerant only. Refrigerant type is written on nameplate of outdoor unit.
In case that refrigerant type is R32, this unit uses a ammable refrigerant.
If refrigerant leaks and comes in contact with re or heating part, it will create harmful gas and there is risk of re.
Read the OPERATION MANUAL carefully before operation.
Service personnel are required to carefully read the OPERATION MANUAL and INSTALLATION MANUAL before operation.
Further information is available in the OPERATION MANUAL, INSTALLATION MANUAL, and the like.
Warning:
• Carefullyreadthelabelsafxedtothemainunit.
• Askadealeroranauthorizedtechniciantoinstall,relocateandrepairthe
unit.
• Theusershouldneverattempttorepairtheunitortransferittoanotherlo-
cation.
• Donotaltertheunit.
• Forinstallationandrelocationwork,followtheinstructionsintheInstalla-
tionManualandusetoolsandpipecomponentsspecicallymadeforuse
withrefrigerantspeciedintheoutdoorunitinstallationmanual.
• Theunitmustbeinstalledaccordingtotheinstructionsinordertomini-
mizetheriskofdamagefromearthquakes,typhoons,orstrongwinds.An
incorrectlyinstalledunitmayfalldownandcausedamageorinjuries.
• Theunitmustbesecurelyinstalledonastructurethatcansustainits
weight.
• Theapplianceshallbestoredinawell-ventilatedareawheretheroomsize
correspondstotheroomareaasspeciedforoperation.
• Iftheairconditionerisinstalledinasmallroomorclosedroom,measures
mustbetakentopreventtherefrigerantconcentrationintheroomfrom
exceedingthesafetylimitintheeventofrefrigerantleakage.Shouldthe
refrigerantleakandcausetheconcentrationlimittobeexceeded,hazards
duetolackofoxygenintheroommayresult.
• Keepgas-burningappliances,electricheaters,andotherresources(igni-
tionsources)awayfromthelocationwhereinstallation,repair,andotherair
conditionerworkwillbeperformed.
Ifrefrigerantcomesintocontactwithaame,poisonousgaseswillbere-
leased.
• Ventilatetheroomifrefrigerantleaksduringoperation.Ifrefrigerantcomes
intocontactwithaame,poisonousgaseswillbereleased.
• Allelectricworkmustbeperformedbyaqualiedtechnicianaccordingto
localregulationsandtheinstructionsgiveninthismanual.
• Useonlyspeciedcablesforwiring.Thewiringconnectionsmustbemade
securelywithnotensionappliedontheterminalconnections.Also,never
splicethecablesforwiring(unlessotherwiseindicatedinthisdocument).
Failuretoobservetheseinstructionsmayresultinoverheatingorare.
•
Wheninstallingorrelocating,orservicingtheairconditioner,useonlythe
speciedrefrigerantwrittenonoutdoorunittochargetherefrigerantlines.Do
notmixitwithanyotherrefrigerantanddonotallowairtoremaininthelines.
Ifairismixedwiththerefrigerant,thenitcanbethecauseofabnormalhigh
pressureinthe refrigerant line,andmay resultinan explosion andother
hazards.
Theuseofanyrefrigerantotherthanthatspecifiedforthesystemwill
causemechanicalfailureorsystemmalfunctionorunitbreakdown.Inthe
worstcase,thiscouldleadtoaseriousimpedimenttosecuringproduct
safety.
• Theapplianceshallbeinstalledinaccordancewithnationalwiringregula-
tions.
• Thisapplianceisnotintendedforusebypersons(includingchildren)with
reducedphysical,sensoryormentalcapabilities,orlackofexperienceand
knowledge,unlesstheyhavebeengivensupervisionorinstructioncon-
cerninguseoftheappliancebyapersonresponsiblefortheirsafety.
• Childrenshouldbesupervisedtoensurethattheydonotplaywiththeap-
pliance.
• Theterminalblockcoverpaneloftheunitmustbermlyattached.
• Ifthesupplycordisdamaged,itmustbereplacedbythemanufacturer,its
serviceagentorsimilarlyqualiedpersonsinordertoavoidahazard.
• UseonlyaccessoriesauthorizedbyMitsubishiElectricandaskadealeror
anauthorizedtechniciantoinstallthem.
• Afterinstallationhasbeencompleted,checkforrefrigerantleaks.Ifrefrig-
erantleaksintotheroomandcomesintocontactwiththeameofaheater
orportablecookingrange,poisonousgaseswillbereleased.
• Donotuse means toacceleratethe defrostingprocessor to clean,other
thanthoserecommendedbythemanufacturer.
• Theapplianceshallbestoredinaroomwithoutcontinuouslyoperatingig-
nitionsources(forexample:openames,anoperatinggasapplianceoran
operatingelectricheater).
• Donotpierceorburn.
• Beawarethatrefrigerantsmaynotcontainanodour.
• Pipe-workshallbeprotectedfromphysicaldamage.
• Theinstallationofpipe-workshallbekepttoaminimum.
• Compliancewithnationalgasregulationsshallbeobserved.
• Keepanyrequiredventilationopeningsclearofobstruction.
• Donotuselowtemperaturesolderalloyincaseofbrazingtherefrigerant
pipes.
• Whenperformingbrazingwork,besuretoventilatetheroomsufciently.
Makesurethattherearenohazardousorammablematerialsnearby.
Whenperformingthe workinaclosed room,smallroom, or similarloca-
tion,makesurethattherearenorefrigerantleaksbeforeperformingthe
work.
Ifrefrigerantleaksandaccumulates,itmayigniteorpoisonousgasesmay
bereleased.
Note:
Thephrase“Wiredremotecontroller”inthisinstallationmanualrefersonlytothePAR-33MAA.Ifyouneedanyinformationfortheotherremotecontroller,
pleaserefertoeithertheinstallationmanualorinitialsettingmanualwhichareincludedintheseboxes.
For safe and correct use, please read this manual and the outdoor unit installation manual thoroughly before installing the air-conditioner unit.
BH79A367W01_01En.indd 1 2018/05/30 9:17:34