Motrona touchMATRIX MX350 User manual

Operating Manual
motrona GmbH, Zeppelinstraße 16, DE - 78244 Gottmadingen, Tel. +49 (0) 7731 9332-0, Fax +49 (0) 7731 9332-30, [email protected], www.motrona.com
touchMATRIX®Indicator MX350 / MX355
Frequency counter, tachometer and speed indicator with touchscreen and graphic display
Product features:
Multifunction unit with operating modes for incremental encoders (tachometer, pulse counter, position
indicator)
- Operating modes as frequency display and / or position display (pulse counter)
- Universal incremental inputs (HTL / TTL / RS422) for NPN / PNP / NAMUR encoders and sensors
- Functions such as links (eg A+B, A-B, ...), scaling, filters, start-up delay, ...
Bright and high-contrast display with event controlled color variations
Emulation of a 7-segment display inclusively icons and units
Intuitive and easy parameterization by plain text and touchscreen
5 / 24 V auxiliary output for encoder supply
Input frequencies up to 1 MHz
Linearization with 24 interpolation points
96 x 48 mm (3.78 x 1.89 inch) norm panel housing and IP65 protection
Available options:
MX350: Basic unit with HTL inputs (A, B), 3 control inputs
MX355: Basic unit with HTL/RS422 inputs (A, /A, B, /B), 3 control inputs
Option AC: Power supply 115 … 230 VAC
Option AO: 16 bit analog output, 4 control outputs, serial RS232 interface
Option AR: 16 bit analog output, 4 control outputs, serial RS485 interface
Option CO: 4 control outputs, serial RS232 interface
Option CR: 4 control outputs, serial RS485 interface
Option RL: 2relay outputs
Options can be combined

Mx350_01a_oi_e.docx / Nov-19 page 2 / 72
Die deutsche Beschreibung ist verfügbar unter:
https://www.motrona.com/fileadmin/files/bedienungsanleitungen/Mx350_d.pdf
The English description is available at:
https://www.motrona.com/fileadmin/files/bedienungsanleitungen/Mx350_e.pdf
La description en français est disponible sur:
https://www.motrona.com/fileadmin/files/bedienungsanleitungen/Mx350_f.pdf
Version:
Description
MX350_01a_oi/mbo/Nov-19
First Version
Legal notices:
All contents included in this manual are protected by the terms of use and copyrights of motrona
GmbH. Any reproduction, modification, usage or publication in other electronic and printed media as
well as in the internet requires prior written authorization by motrona GmbH.

Mx350_01a_oi_e.docx / Nov-19 page 3 / 72
Table of Contents
Safety Instructions and Responsibility.......................................................................... 5
General Safety Instructions.............................................................................................................5
Use according to the intended purpose ..........................................................................................5
Installation .......................................................................................................................................6
Cleaning, Maintenance and Service Notes.....................................................................................6
Introduction.................................................................................................................. 7
Operation mode ...............................................................................................................................7
Function diagram .............................................................................................................................8
Electrical Connections.................................................................................................. 9
DC Power Supply .............................................................................................................................9
Auxiliary Voltage Output..................................................................................................................9
MX350: Incremental Input A, B .....................................................................................................10
MX355: Incremental Input A, /A, B, /B .........................................................................................11
Control Inputs.................................................................................................................................12
Analog Output (Option AO/AR)......................................................................................................12
Serial interface (Option AO/AR/CO/CR)........................................................................................13
Control-Output (AO/AR/CO/CR).....................................................................................................13
AC Power supply (Option AC) ........................................................................................................14
Relay-Output (Option RL) ...............................................................................................................14
Display and touch screen ........................................................................................... 15
Screen structure for parametrization ............................................................................................15
Screen structure in operation........................................................................................................16
Error messages ..............................................................................................................................18
Parameter / Overview-Menu Structure....................................................................... 19
General Menu ................................................................................................................................21
Speed A Settings ...........................................................................................................................23
Speed B Settings ...........................................................................................................................26
Counter A Settings.........................................................................................................................29
Counter B Settings.........................................................................................................................33
Collection Settings.........................................................................................................................36
Scaling Settings.............................................................................................................................37
Preselection Values .......................................................................................................................38
Preselection 1 Menu......................................................................................................................39
Preselection 2 Menu......................................................................................................................43
Preselection 3 Menu......................................................................................................................44
Preselection 4 Menu......................................................................................................................45
Serial Menu ...................................................................................................................................46
Analog Menu .................................................................................................................................48
Command Menu.............................................................................................................................50
Display Menu.................................................................................................................................53
Linearization Menu ........................................................................................................................57
Appendix.................................................................................................................... 58
Data readout via serial interface...................................................................................................58
Modbus RTU Interface...................................................................................................................59
Parameter setting ....................................................................................................................................... 59
Modbus Communication............................................................................................................................. 60

Mx350_01a_oi_e.docx / Nov-19 page 4 / 72
Diagnostics ................................................................................................................................................. 62
Parameter / serial codes................................................................................................................62
Linearization...................................................................................................................................68
Dimensions ....................................................................................................................................70
Technical specifications ................................................................................................................71

Mx350_01a_oi_e.docx / Nov-19 page 5 / 72
Safety Instructions and Responsibility
General Safety Instructions
This operation manual is a significant component of the unit and includes important rules and hints about
the installation, function and usage. Non-observance can result in damage and/or impairment of the
functions to the unit or the machine or even in injury to persons using the equipment!
Please read the following instructions carefully before operating the device and observe all safety and
warning instructions! Keep the manual for later use.
A pertinent qualification of the respective staff is a fundamental requirement in order to use these
manual. The unit must be installed, connected and put into operation by a qualified electrician.
Liability exclusion: The manufacturer is not liable for personal injury and/or damage to property and for
consequential damage, due to incorrect handling, installation and operation. Further claims, due to errors
in the operation manual as well as misinterpretations are excluded from liability.
In addition the manufacturer reserves the right to modify the hardware, software or operation manual at
any time and without prior notice. Therefore, there might be minor differences between the unit and the
descriptions in operation manual.
The raiser respectively positioner is exclusively responsible for the safety of the system and equipment
where the unit will be integrated.
During installation or maintenance all general and also all country- and application-specific safety rules
and standards must be observed.
If the device is used in processes, where a failure or faulty operation could damage the system or injure
persons, appropriate precautions to avoid such consequences must be taken.
Use according to the intended purpose
The unit is intended exclusively for use in industrial machines, constructions and systems. Non-
conforming usage does not correspond to the provisions and lies within the sole responsibility of the
user. The manufacturer is not liable for damages which have arisen through unsuitable and improper use.
Please note that device may only be installed in proper form and used in a technically perfect condition
(in accordance to the Technical Specifications). The device is not suitable for operation in explosion-proof
areas or areas which are excluded by the EN 61010-1 standard.

Mx350_01a_oi_e.docx / Nov-19 page 6 / 72
Installation
The device is only allowed to be installed and operated within the permissible temperature range. Please
ensure an adequate ventilation and avoid all direct contact between the device and hot or aggressive
gases and liquids.
Before installation or maintenance, the unit must be disconnected from all voltage-sources. Further it
must be ensured that no danger can arise by touching the disconnected voltage-sources.
Devices which are supplied by AC-voltages must be connected exclusively by switches, respectively
circuit-breakers with the low voltage network. The switch or circuit-breaker must be placed as near as
possible to the device and further indicated as separator.
Incoming as well as outgoing wires and wires for extra low voltages (ELV) must be separated from
dangerous electrical cables (SELV circuits) by using a double resp. increased isolation.
All selected wires and isolations must be conform to the provided voltage- and temperature-ranges.
Further all country- and application-specific standards, which are relevant for structure, form and quality
of the wires, must be ensured. Indications about the permissible wire cross-sections for wiring are
described in the Technical Specifications.
Before first start-up it must be ensured that all connections and wires are firmly seated and secured in
the screw terminals. All (inclusively unused) terminals must be fastened by turning the relevant screws
clockwise up to the stop.
Overvoltages at the connections must be limited to values in accordance to the overvoltage category II.
For placement, wiring, environmental conditions as well as shielding and earthing/grounding of the supply
lines the general standards of industrial automation industry and the specific shielding instructions of the
manufacturer are valid. Please find all respective hints and rules on
https://www.motrona.com/en/support --> “[General EMC Rules for Wiring, Screening and Earthing]”.
Cleaning, Maintenance and Service Notes
To clean the front of the unit please use only a slightly damp (not wet!), soft cloth. For the rear no
cleaning is necessary. For an unscheduled, individual cleaning of the rear the maintenance staff or
assembler is self-responsible.
During normal operation no maintenance is necessary. In case of unexpected problems, failures or
malfunctions the device must be shipped for back to the manufacturer for checking, adjustment and
reparation (if necessary). Unauthorized opening and repairing can have negative effects or failures to the
protection-measures of the unit.

Mx350_01a_oi_e.docx / Nov-19 page 7 / 72
Introduction
This series of display unit is suitable for HTL impulse signals and panel mounting. It is very versatile in
use, due to the intuitive handling and the extensive range of functions and options.
Operation mode
All functions are can be configured in the parameter menu.
The device can be set to one of the following operation modes:
• Operation as frequency display for incremental input signals
-Measurement of frequency / RMP indicator
-Tachometers / speed indicator
-Monitoring functions for speed and standstill
-Possibility of linking (A+B, B/A, ...) of both channels
(e.g., ratio or percentage deviation)
• Operation as position indicator / counter for incremental input signals
-Pulse counter
-Up- or down counter
-Position indicator
-Protractor
-Quadrature counter
-Batch counter / total counter
-Possibility of linking (A+B, B/A, ...) of both channels
(e.g., ratio or percentage deviation)
• Operation as speed- and position indicator for incremental input signals

Mx350_01a_oi_e.docx / Nov-19 page 8 / 72
Function diagram

Mx350_01a_oi_e.docx / Nov-19 page 9 / 72
Electrical Connections
The terminal screws should be tightened with a slotted screwdriver (blade width 2mm).
MX350 MX355
DC Power Supply
The unit accepts DC supply from 18 to 30 V at the terminals 1 and 2. The power consumption depends on
the level of the supply voltage with aprox. 100 mA and the additional current required at the Auxiliary
Voltage Output.
All GND terminals are internally interconnected.
Auxiliary Voltage Output
Terminal 3 and 4 provide an auxiliary output for supply of sensors and encoders.
The output voltage depends on the power supply.
DC version
AC version
The encoder voltage is approx. 1 V lower than
the power supply voltage at terminal 1 and 2
and should be loaded with max. 250 mA.
The encoder voltage is 24 VDC (± 15%) and
should be loaded with max. 150 mA up to 45
degrees Celsius. At higher temperature the
maximum output current is reduced to 80 mA.
At MX355 devices, the auxiliary voltages output is switchable from 24 VDC to 5 VDC.

Mx350_01a_oi_e.docx / Nov-19 page 10 / 72
MX350: Incremental Input A, B
The unit provides two inputs at terminal 5 and 7 for HTL signals.
The characteristics of the incremental input (PNP, NPN, Namur or Tri-State) can be set in the GENERAL
MENU.
Wiring of the incremental inputs:
PNP
NPN
Namur
Tri-State
Unconnected PNP inputs are always “LOW” and unconnected NPN inputs are always “HIGH”.
All inputs are designed to receive impulses from electrical impulse sources.
Notice for mechanical switching contacts:
When exceptionally mechanical contacts are used, please connect an external capacitor between GND (-)
and the corresponding input (+). A capacity of 10 µF will reduce the input frequency to
20 Hz and miscounting due to contact bouncing will be eliminated.

Mx350_01a_oi_e.docx / Nov-19 page 11 / 72
MX355: Incremental Input A, /A, B, /B
The unit provides two pulse inputs at terminal 5, 6, 7 and 8 for HTL/RS422 signals.
The characteristics of the incremental input can be set in the GENERAL MENU.
Wiring of the incremental inputs:
RS422
HTL DIFFERENTIAL
HTL PNP, single ended
HTL NPN, single ended
Unconnected PNP inputs are always “LOW” and unconnected NPN inputs are always “HIGH”.
All inputs are designed to receive impulses from electrical impulse sources.

Mx350_01a_oi_e.docx / Nov-19 page 12 / 72
Control Inputs
The three control inputs at terminal 10, 11 and 12 have HTL PNP characteristics.
In the COMMAND MENU the programmable functions for the control inputs can be assigned. Available
functions are: reset the display value, display switching, locking the touch screen or release the lock
function of the control or relay outputs.
Wiring of the control inputs:
Unconnected control inputs are always “LOW”.
All inputs are designed to receive impulses from an electronic impulse source.
Notice for mechanical switching contacts:
When exceptionally mechanical contacts are used, please connect an external capacitor between GND (-)
and the corresponding input (+). A capacity of 10 µF will reduce the input frequency to
20 Hz and miscounting due to contact bouncing will be eliminated.
Analog Output (Option AO/AR)
A 16 bit analog output is available at terminal 13 and 14 / 15
This output can be configured and scaled in the ANALOG MENU.
The following configuration is possible:
•Voltage output: -10 … +10 V
•Current output: 0 … 20 mA
•Current output: 4 … 20 mA
The analog output is proportional to the reference source and is referenced to potential AGND.
AGND and GND are internally interconnected.
Important:
A parallel operation with voltage and current output at the analog output is not allowed.

Mx350_01a_oi_e.docx / Nov-19 page 13 / 72
Serial interface (Option AO/AR/CO/CR)
A serial interface (RS232 or RS485) is available at terminal 16, 17 und 18.
This interface can be configured in the SERIAL MENU.
The serial interface RS232 or RS485 can be used:
for easy setup and commissioning of the units
to modify settings and parameters during operation
to read out internal states and actual measuring values by PC or PLC
The following drawing shows the connection to a PC by using a standard Sub-D-9 connector:
Connection of the RS232 interface:
Connection of the RS485 interface:
Control-Output (AO/AR/CO/CR)
Four control outputs are available at terminal 20, 21, 22 and 23.
Switching conditions can be set in the PRESELECTION MENU. The output Ctrl. Out1 –4 are fast PNP
outputs with a switching capability of 5 –30 Volt / 200 mA per channel. The switching states is displayed
(display with unit and status bar) as C1 … C4.
The switching voltage of the outputs must be applied to input terminal 19 (COM+).
In case of switching inductive loads it is advisable to use external filtering of the coils.

Mx350_01a_oi_e.docx / Nov-19 page 14 / 72
Wiring of the control-outputs:
AC Power supply (Option AC)
The unit accepts AC supply from 115 to 230 V at the terminals 24 and 25. The power consumption
depends on the level of the supply voltage with aprox. 3VA and the additional current required at the
auxiliary voltage output.
Devices with option AC can also be supplied with a DC voltage between 18 and 30 VDC at terminals 1
and 2.
Relay-Output (Option RL)
Two relay outputs with potential-free changeover contacts are available at terminal 27, 28, 28, 30, 31, 32.
Switching conditions can be set in the PRESELECTION MENU. The switching states are displayed (display
with unit and status bar) as K1 and K4.
AC-switching capacity max. 250 VAC/ max. 3 A / 750 VA
DC-switching capacity max. 150 VAC/ max. 2 A / 50 W
Wiring of the relay outputs

Mx350_01a_oi_e.docx / Nov-19 page 15 / 72
Display and touch screen
Screen structure for parametrization
The parameter menus and the parameters are described in chapter 5.
Start setup procedure:
To edit the parameters,
press the touchscreen for 3 seconds.
Menu selection:
Select the parameter menu via arrow buttons and
confirm with “OK”.
The menu selection can be terminated
with „C“.
Parameter selection:
Select the parameter via arrow buttons and
confirm with „OK“.
The parameter selection can be terminated with
„C“.
Parameter editing:
Edit the parameter via arrow button up and down,
shift cursor via left and right and save with „OK“.
The parameter editing can be terminated with
„C“.
Parameter changes becomes active only after closing the menu selection.

Mx350_01a_oi_e.docx / Nov-19 page 16 / 72
Screen structure in operation
The following screens are available during operation. Depending on the device version and the selected
operation mode, not all displays will be shown.
Display with unit and status bar
To switch to the next display, press the
touch screen.
Control - or Relay status are only shown with
option AO, AR, CO, CR or RL.
Large Display (4 digits)
To switch to the next display, press the top of the
screen.
This is only possible with activated parameter
„LARGE DISPLAY“.
Two-line display without units
To switch to the next display, press the top of the
screen.
Two-line display with units
To switch to the next display, press the top of the
screen.
Display with command keys
To switch to the next display, press the top of the
screen.

Mx350_01a_oi_e.docx / Nov-19 page 17 / 72
Continuation „Screen structure in operation“:
Display for quick start for enter or display
preselection values (PRESELECTION VALUES 1-4)
The desired command key ("Edit Presel." or "Show
Presel.") can be set in the display menu via the
parameter "QUICKSTART BUTTON".
To switch to the next display, press the top of the
screen or the “skip” button.
This is only possible with option AO, AR, CO, CR
or RL
Display with minimum and maximum value
To switch to the next display, press the top of the
screen or the “skip” button.
The minimum and maximum evaluation refers to
the reference source set in the "SOURCE SINGLE"
parameter.

Mx350_01a_oi_e.docx / Nov-19 page 18 / 72
Error messages
If a measurement result, which is shown on the display, is outside the displayable display range, an error
screen is briefly displayed every two seconds. In this appears, which display value was exceeded or
fallen below.
The error messages described are automatically reset as soon as the corresponding
display value is within the representable range.

Mx350_01a_oi_e.docx / Nov-19 page 19 / 72
Parameter / Overview-Menu Structure
This section provides an overview of the menus and their parameters. The menu names are printed bold
and the associated parameters are listed under the menu name. Depending on the device version and the
selected operation mode, only the necessary menus / parameters are shown.
Menu / Parameter
GENERAL MENU
OPERATIONAL MODE
ENCODER PROPERTIES
ENCODER SUPPLY
COUNTING DIRECTION
LINEARIZATION MODE
PIN PRESELECTION
PIN PARAMETER
BACK UP MEMORY
FACTORY SETTINGS
SPEED A SETTINGS
DISPLAY VALUE
BASE FREQUENCY
DECIMAL POINT
SAMPLING TIME
WAIT TIME
STANDSTILL TIME
AVERAGE FILTER
SCALE UNITS
SPEED B SETTINGS
DISPLAY VALUE
BASE FREQUENCY
DECIMAL POINT
SAMPLING TIME
WAIT TIME
STANDSTILL TIME
AVERAGE FILTER
SCALE UNITS
Menu / Parameter
COUNTER A SETTINGS
FACTOR
SET VALUE
DECIMAL POINT
SCALE UNITS
SECOND MODE
SECOND SET VALUE
SECOND DECIMAL POINT
SECOND SCALE UNITS
COUNTER B SETTINGS
FACTOR
SET VALUE
DECIMAL POINT
SCALE UNITS
SECOND MODE
SECOND SET VALUE
SECOND DECIMAL POINT
SECOND SCALE UNITS
COLLECTION SETTINGS
DECIMAL POINT FREQUENCY
SCALE UNITS FREQUENCY
DECIMAL POINT COUNTER
SCALE UNITS COUNTER
SCALING SETTINGS
SOURCE
FACTOR
DIVIDER
ADDITIVE VALUE

Mx350_01a_oi_e.docx / Nov-19 page 20 / 72
Menu / Parameter
PRESELECTION VALUES
PRESELECTION 1
PRESELECTION 2
PRESELECTION 3
PRESELECTION 4
PRESELECTION 1 MENU
SOURCE 1
MODE 1
HYSTERESIS 1
PULSE TIME 1
OUTPUT TARGET 1
OUTPUT POLARITY 1
OUTPUT LOCK 1
START UP DELAY 1
EVENT COLOR 1
PRESELECTION 2 MENU
SOURCE 2
MODE 2
HYSTERESIS 2
PULSE TIME 2
OUTPUT TARGET 2
OUTPUT POLARITY 2
OUTPUT LOCK 2
START UP DELAY 2
EVENT COLOR 2
PRESELECTION 3 MENU
SOURCE 3
MODE 3
HYSTERESIS 3
PULSE TIME 3
OUTPUT TARGET 3
OUTPUT POLARITY 3
OUTPUT LOCK 3
START UP DELAY 3
EVENT COLOR 3
PRESELECTION 4 MENU
SOURCE 4
MODE 4
HYSTERESIS 4
PULSE TIME 4
OUTPUT TARGET 4
OUTPUT POLARITY 4
OUTPUT LOCK 4
START UP DELAY 4
EVENT COLOR 4
Menu / Parameter
SERIAL MENU
UNIT NUMBER
SERIAL BAUD RATE
SERIAL FORMAT
SERIAL INIT
SERIAL PROTOCOL
SERIAL TIMER
SERIAL VALUE
MODBUS
ANALOG MENU
ANALOG SOURCE
ANALOG FORMAT
ANALOG START
ANALOG END
ANALOG GAIN
ANALOG OFFSET
COMMAND MENU
INPUT 1 ACTION
INPUT 1 CONFIG
INPUT 2 ACTION
INPUT 2 CONFIG
INPUT 3 ACTION
INPUT 3 CONFIG
DISPLAY MENU
START DISPLAY
SOURCE SINGLE
SOURCE DUAL TOP
SOURCE DUAL TOWN
LARGE DISPLAY
COLOR
BRIGHTNESS
CONTRAST
SCREEN SAVER
UP-DATE-TIME
FONT
QUICKSTART BUTTON
LINEARISATION MENU
SOURCE
P1(X)
P1(Y)
P2(X)
P2(Y)
…
P23(X)
P23(Y)
P24(X)
P24(Y)
This manual suits for next models
1
Table of contents
Other Motrona Measuring Instrument manuals

Motrona
Motrona AX 342 User manual

Motrona
Motrona TouchMATRIX DM350 User manual

Motrona
Motrona touchMATRIX DP350 User manual

Motrona
Motrona AX 346 User manual

Motrona
Motrona touchMATRIX PN350 User manual

Motrona
Motrona AX020 User manual

Motrona
Motrona SD Series User manual

Motrona
Motrona AX 345 User manual

Motrona
Motrona AX320 User manual

Motrona
Motrona DS230 Series User guide