MSA FS-EZX-KNX-BAC User guide

EZ Gateway Start-up Guide 0
Start-up Guide
EZ Gateway KNX to BACnet
FS-EZX-KNX-BAC
FS-QS-1011/12X0/12X1/1X50/1X51
MSAsafety.com
Document Revision: 8.A
T18605
APPLICABILITY & EFFECTIVITY
Effective for all systems manufactured after January 2021.

EZ Gateway Start-up Guide 2
MSA Safety
1991 Tarob Court
Milpitas, CA 95035
Website: www.MSAsafety.com
U.S. Support Information:
+1 408 964-4443
+1 800 727-4377
Email: [email protected]
EMEA Support Information:
+31 33 808 0590
Email: [email protected]

EZ Gateway Start-up Guide 3
Table of Contents
1About the EZ Gateway.....................................................................................................................6
1.1 Supplied Equipment .................................................................................................................6
1.2 Certification...............................................................................................................................6
1.2.1 BTL Mark –BACnet Testing Laboratory..................................................................................6
2Equipment Setup..............................................................................................................................7
2.1 Mounting...................................................................................................................................7
2.2 Dimension Drawing FS-EZX-KNX-BAC...................................................................................8
3Installing the EZ Gateway................................................................................................................9
3.1.1 KNX Connection R2 Port .........................................................................................................9
3.1.2 RS-485 Connection R1 Port.....................................................................................................9
3.2 R1 Port Small DIP Switches...................................................................................................10
4Operation.........................................................................................................................................11
4.1 Power Up the Device..............................................................................................................11
4.2 Connect the PC to the EZ Gateway Over the Ethernet Port..................................................11
4.3 Connecting to the EZ Gateway...............................................................................................12
4.3.1 Using the FieldServer Toolbox to Discover and Connect to the EZ Gateway.......................12
4.3.2 Using a Web Browser to Connect to the EZ Gateway...........................................................12
5Setup Web Server Security ...........................................................................................................13
5.1 Login to the FieldServer .........................................................................................................13
5.2 Select the Security Mode........................................................................................................15
5.2.1 HTTPS with Own Trusted TLS Certificate .............................................................................16
5.2.2 HTTPS with Default Untrusted Self-Signed TLS Certificate or HTTP with Built-in Payload
Encryption ..............................................................................................................................16
6Configuring the EZ Gateway.........................................................................................................17
6.1 Controls, Status and Log Functions.......................................................................................17
6.2 EZ Gateway Connection Setup..............................................................................................18
6.3 BACnet Connection Setup......................................................................................................19
6.3.1 All Connections Settings........................................................................................................19
6.3.2 BACnet/IP Connection Settings.............................................................................................20
6.3.3 BACnet MS/TP Connection Settings .....................................................................................20
6.4 BACnet Device Setup.............................................................................................................21
6.4.1 Table Editing Options.............................................................................................................21
6.5 KNX Network Mapping...........................................................................................................22
6.5.1 KNX Mapping Method 1: Import Group Addresses................................................................22
6.5.2 KNX Mapping Method 2: Setup on Web Configurator GUI....................................................29
6.6 BACnet Network Mapping......................................................................................................30
6.6.1 Table Editing Options.............................................................................................................30
6.7 Alarm Settings ........................................................................................................................31
6.8 State Tables............................................................................................................................32
6.9 Save KNX to BACnet Mapping...............................................................................................33
6.10 Test and Commission the EZ Gateway..................................................................................34
6.10.1 Accessing SMC Cloud ...........................................................................................................34
7Troubleshooting.............................................................................................................................35
7.1 Communicating with the EZ Gateway Over the Network.......................................................35
7.2 Taking a FieldServer Diagnostic Capture...............................................................................36
7.2.1 Taking a Capture with Older Firmware..................................................................................37
7.3 Notes Regarding Subnets and Subnet Masks .......................................................................39
7.4 LED Functions........................................................................................................................39
7.5 KNX Commissioning...............................................................................................................40
7.6 Internet Browser Software Support ........................................................................................40

EZ Gateway Start-up Guide 4
8Additional Information...................................................................................................................41
8.1 Change Web Server Security Settings After Initial Setup......................................................41
8.1.1 Change Security Mode...........................................................................................................42
8.1.2 Edit the Certificate Loaded onto the FieldServer...................................................................43
8.2 Change User Management Settings......................................................................................44
8.2.1 Create Users..........................................................................................................................45
8.2.2 Edit Users...............................................................................................................................46
8.2.3 Delete Users...........................................................................................................................47
8.2.4 Change FieldServer Password ..............................................................................................48
8.3 Specifications..........................................................................................................................49
8.4 Compliance with UL Regulations............................................................................................50
8.5 Supported KNX Data Types...................................................................................................50
9Limited 2 Year Warranty................................................................................................................51

EZ Gateway Start-up Guide 5
List of Figures
Figure 1: DIN Rail..........................................................................................................................................7
Figure 2: EZ Gateway Dimension Drawing...................................................................................................8
Figure 3: R2 Port Connection........................................................................................................................9
Figure 4: R1 Port Connection........................................................................................................................9
Figure 5: Bias Resistor DIP Switches & EOL..............................................................................................10
Figure 6: Connecting Power........................................................................................................................11
Figure 7: Ethernet Port................................................................................................................................11
Figure 8: Web Server Security Unconfigured Window ...............................................................................13
Figure 9: Connection Not Private Warning .................................................................................................13
Figure 10: Warning Expanded Text............................................................................................................14
Figure 11: FieldServer Login.......................................................................................................................14
Figure 12: Security Mode Selection Screen................................................................................................15
Figure 13: Security Mode Selection Screen –Certificate & Private Key....................................................16
Figure 14: EZ Gateway Landing Page........................................................................................................17
Figure 15: Gateway Network Settings ........................................................................................................18
Figure 16: BACnet Connection Settings.....................................................................................................19
Figure 17: BACnet Device Settings ............................................................................................................21
Figure 18: ETS4 Export Window.................................................................................................................24
Figure 19: Data Map Page..........................................................................................................................25
Figure 20: KNX Import Missing Fields ........................................................................................................28
Figure 21: Mapping BACnet Addresses to the KNX Registers...................................................................29
Figure 22: Creating an Item on the Data Map.............................................................................................29
Figure 23: Mapping BACnet Fields.............................................................................................................30
Figure 24: Defining Parameters of Notification Class.................................................................................31
Figure 25: Setting Alarm Parameters..........................................................................................................31
Figure 26: Saved Data Map........................................................................................................................33
Figure 27: FS-GUI Connections Screen.....................................................................................................34
Figure 28: Ethernet Port Location...............................................................................................................37
Figure 29: LED Allocation ...........................................................................................................................39
Figure 30: KNX Port Location.....................................................................................................................40
Figure 31: QuickServer Landing Page........................................................................................................41
Figure 32: FS-GUI Page .............................................................................................................................41
Figure 33: FS-GUI Security Setup..............................................................................................................42
Figure 34: FS-GUI Security Setup –Certificate Loaded.............................................................................43
Figure 35: FS-GUI User Management........................................................................................................44
Figure 36: Create User Window..................................................................................................................45
Figure 37: Setup Users...............................................................................................................................46
Figure 38: Edit User Window ......................................................................................................................46
Figure 39: Setup Users...............................................................................................................................47
Figure 40: User Delete Warning .................................................................................................................47
Figure 41: FieldServer Password Update via FS-GUI................................................................................48
Figure 42: Specifications.............................................................................................................................49

Description
EZ Gateway Start-up Guide 6
1About the EZ Gateway
EZ Gateway is a high performance,cost effective Building and Industrial Automation multi-protocol gateway
providing protocol translation between serial and Ethernet, devices and networks.
NOTE: For troubleshooting assistance refer to Section 7, or any of the troubleshooting
appendices in the related driver supplements. Check the MSA Safety website for technical
support resources and documentation that may be of assistance.
The EZ Gateway is cloud ready and connects with MSA Safety’s SMC Cloud. See Section 6.10.1 for further
information.
1.1 Supplied Equipment
EZ Gateway
•Preloaded with the KNX and BACnet drivers.
•All instruction manuals, driver manuals, support utilities are available on the USB drive provided in
the optional accessory kit, or on the MSA website.
Accessory kit (optional) (Part # FS-8915-36-QS) includes:
•7-ft Cat-5 cable with RJ45 connectors at both ends
•Power Supply - 110/220V (p/n 69196)
•DIN rail mounting bracket
•Screwdriver for connecting to terminals
•USB Flash drive loaded with:
oKNX to BACnet Start-up Guide
oFieldServer Configuration Manual
oAll FieldServer Driver Manuals
oSupport Utilities
oAny additional folders related to special files
configured for a specific EZ Gateway
oAdditional components as required - See Driver Manual Supplement for details
1.2 Certification
1.2.1 BTL Mark –BACnet Testing Laboratory
1
The BTL Mark on EZ Gateway is a symbol that indicates that a product has
passed a series of rigorous tests conducted by an independent laboratory
which verifies that the product correctly implements the BACnet features
claimed in the listing. The mark is a symbol of a high-quality BACnet product.
Go to www.BACnetInternational.net for more information about the BACnet
Testing Laboratory. Click here for the BACnet PIC Statement.
1
BACnet is a registered trademark of ASHRAE.

Equipment Setup
EZ Gateway Start-up Guide 7
2Equipment Setup
2.1 Mounting
The following mounting options are available:
•Product comes with tabs for wall or surface mount. These can be snapped off if not required.
•DIN rail mounting bracket –Included in the accessory kit or ordered separately
(part # FS-8915-35-QS).
WARNING: Install only as instructed, failure to follow the installation guidelines or using screws
without the DIN rail mounting bracket could result in permanent damage to the product. If the
FieldServer is removed from the DIN rail, use the original screws to reattach. Only screws
supplied by MSA Safety should be used in the holes found on the back of the unit when
attaching the optional DIN Rail bracket. USE OF ANY OTHER SCREWS MAY DAMAGE THE
UNIT.
Tab
Din Rail
Figure 1: DIN Rail

Equipment Setup
EZ Gateway Start-up Guide 8
2.2 Dimension Drawing FS-EZX-KNX-BAC
R1 Port
R2 Port
Figure 2: EZ Gateway Dimension Drawing

Installation
EZ Gateway Start-up Guide 9
3Installing the EZ Gateway
3.1.1 KNX Connection R2 Port
Connect to the 3 pins on the left side of the 6-pin connector as shown (pins labelled 6-4).
3.1.2 RS-485 Connection R1 Port
Connect to the 3-pin connector as shown.
The following baud rates are supported on the R1 Port for BACnet MS/TP:
9600, 19200, 38400, 76800
Pin
Connection
1
Frame ground
2
- Power
3
+ Power
4
No connection
5
KNX -
6
KNX+
Figure 3: R2 Port Connection
Figure 4: R1 Port Connection
+ - GND

Installation
EZ Gateway Start-up Guide 10
3.2 R1 Port Small DIP Switches
Gently remove the FieldServer enclosure to access the small DIP switches for the R1 Port.
•If more than one RS-485 device is connected to the network, then the field bias resistor switch
needs to be enabled to ensure proper communication. See Figure 5 for the orientation of switch
positions referenced below.
oThe default factory setting is OFF (switch position = right side)
oTo enable biasing, turn the bias switch ON (switch position = left side)
NOTE: Biasing only needs to be enabled on one device. The FieldServer has 510 ohm resistors
that are used to set the biasing.
•If the FieldServer is the last device on the trunk, then the end of line (EOL) termination switch needs
to be enabled. See Figure 5 for the orientation of switch positions referenced below.
oThe default factory setting is OFF (switch position = right side)
oTo enable the EOL termination, turn the EOL switch ON (switch position = left side)
Figure 5: Bias Resistor DIP Switches & EOL
Bias Resistor Switch
End of Line Switch

Operation
EZ Gateway Start-up Guide 11
4Operation
4.1 Power Up the Device
Apply power to the device. Ensure that the power supply used complies with the specifications provided.
Ensure that the cable is grounded using the “Frame GND” terminal. The EZ Gateway is factory set for
9-30V DC or 12-24V AC.
NOTE: A KNX compatible power supply is required on the KNX network.
4.2 Connect the PC to the EZ Gateway Over the Ethernet Port
•Connect an Ethernet cable between the PC and EZ Gateway or connect the EZ Gateway and the
PC to the switch using a straight Cat-5 cable.
•The Default IP Address of the EZ Gateway is 192.168.2.101, Subnet Mask is 255.255.255.0.
Ethernet Port
Figure 6: Connecting Power
Figure 7: Ethernet Port
PWR+ PWR- FG

Operation
EZ Gateway Start-up Guide 12
4.3 Connecting to the EZ Gateway
4.3.1 Using the FieldServer Toolbox to Discover and Connect to the EZ Gateway
•Install the Toolbox application from the USB drive or download it from the MSA Safety website.
•Use the FS Toolbox application to find the EZ Gateway and launch the FS-GUI.
NOTE: If the connect button is greyed out, the EZ Gateway’s IP Address must be set to be on the
same network as the PC. (Section 4.3.2)
4.3.2 Using a Web Browser to Connect to the EZ Gateway
•Open a web browser and connect to the EZ Gateway’s default IP Address. The default IP Address
of the FieldServer is 192.168.2.101, Subnet Mask is 255.255.255.0.
•If the PC and the EZ Gateway are on different IP networks, assign a static IP Address to the PC
on the 192.168.2.X network.

Setup Web Server Security
EZ Gateway Start-up Guide 13
5Setup Web Server Security
5.1 Login to the FieldServer
The first time the FieldServer GUI is opened in a browser, the IP Address for the gateway will appear as
untrusted. This will cause the following pop-up windows to appear.
•When the Web Server Security Unconfigured window appears, read the text and choose whether
to move forward with HTTPS or HTTP.
•When the warning that “Your connection is not private” appears, click the advanced button on the
bottom left corner of the screen.
Figure 9: Connection Not Private Warning
Figure 8: Web Server Security Unconfigured Window

Setup Web Server Security
EZ Gateway Start-up Guide 14
•Additional text will expand below the warning, click the underlined text to go to the IP Address. In
the Figure 10 example this text is “Proceed to 10.40.50.94 (unsafe)”.
•When the login screen appears, put in the Username (default is “admin”) and the Password (found
on the label of the FieldServer).
NOTE: There is also a QR code in the top right corner of the FieldServer label that shows the
default unique password when scanned.
NOTE: A user has 5 attempts to login then there will be a 10-minute lockout. There is no timeout
on the FieldServer to enter a password.
NOTE: To create individual user logins, go to 8.2.
Figure 11: FieldServer Login
Figure 10: Warning Expanded Text

Setup Web Server Security
EZ Gateway Start-up Guide 15
5.2 Select the Security Mode
On the first login to the FieldServer, the following screen will appear that allows the user to select which
mode the FieldServer should use.
NOTE: Cookies are used for authentication.
NOTE: To change the web server security mode after initial setup, go to Section 8.1.
The sections that follow include instructions for assigning the different security modes.
Figure 12: Security Mode Selection Screen

Setup Web Server Security
EZ Gateway Start-up Guide 16
5.2.1 HTTPS with Own Trusted TLS Certificate
This is the recommended selection and the most secure. Please contact your IT department to find out
if you can obtain a TLS certificate from your company before proceeding with the Own Trusted TLS
Certificate option.
•Once this option is selected, the Certificate, Private Key and Private Key Passphrase fields will
appear under the mode selection.
•Copy and paste the Certificate and Private Key text into their respective fields. If the Private Key is
encrypted type in the associated Passphrase.
•Click Save.
•A “Redirecting” message will appear. After a short time, the FieldServer GUI will open.
5.2.2 HTTPS with Default Untrusted Self-Signed TLS Certificate or HTTP with Built-in
Payload Encryption
•Select one of these options and click the Save button.
•A “Redirecting” message will appear. After a short time, the FieldServer GUI will open.
Figure 13: Security Mode Selection Screen –Certificate & Private Key

Configuring the Gateway
EZ Gateway Start-up Guide 17
6Configuring the EZ Gateway
Once the web server setup is complete, the EZ Gateway landing page will appear.
NOTE: The SMC Cloud™ tab (see Figure 14) allows users to connect to the
SMC Cloud, MSA Safety’s device cloud solution for IIoT. The SMC Cloud enables secure
remote connection to field devices through a FieldServer and its local applications for
configuration, management, maintenance. For more information about the SMC Cloud,
refer to the SMC Cloud Start-up Guide.
6.1 Controls, Status and Log Functions
Along the right side of every Web Configurator GUI page is a column of buttons and event generated
messages.
•Controls Panel –Contains the following four buttons:
oReload –Resets all settings to the last saved configuration
oDefaults –Resets all settings to the default configuration
oSave –Records all settings
oRestart –Reboots the Gateway
•Status Information –Shows Gateway messages such as whether the Gateway is online, element
validation status, unsaved settings, etc.
•Log Messages –Lists last five events and when they were performed.
Figure 14: EZ Gateway Landing Page

Configuring the Gateway
EZ Gateway Start-up Guide 18
6.2 EZ Gateway Connection Setup
•Open the KNX EZ Gateway Web Configurator GUI in a local web browser (Section 4.3.2).
NOTE: The browser should open in the “Gateway” tab, as shown on the left side of the page
(Figure 15). If navigating from another page in the Web Configurator GUI, click the
Gateway tab.
•Specify the Gateway’s Title and a System ID Number.
oThe System ID Number is a unique number to identify the EZ Gate way and is used as the
default Device Instance if there are no nodes configured on the BACnet connection
•Click Save button in the Controls Panel once edits are completed to record changes.
Figure 15: Gateway Network Settings

Configuring the Gateway
EZ Gateway Start-up Guide 19
6.3 BACnet Connection Setup
•Click on the Enable checkbox under the ‘BACnet/IP or BACnet MS/TP Connection’ heading to
configure the BACnet connections. The gateway has a BACnet MS/TP (R1) and BACnet/IP
connection (N1).
•Enter the required BACnet/IP or BACnet MS/TP settings and click the Save button in the
Controls Panel once all edits are completed to record changes.
6.3.1 All Connections Settings
Network Number –Set up the BACnet network number for the connection. Legal values are 1-
65534. Each network number must be unique across the entire BACnet internetwork.
Enable –Enable or disable the connection.
Figure 16: BACnet Connection Settings

Configuring the Gateway
EZ Gateway Start-up Guide 20
6.3.2 BACnet/IP Connection Settings
IP Port –The BACnet/IP default is 47808 (0xBAC0), but a different port may be specified.
Enable BBMD –Select this checkbox to enable the EZ Gateway to act as a BBMD.
Public IP Address and Port –If the BBMD is being accessed across a NAT Router, then these
values must be configured with the public IP address and Port by which the BBMD can be reached
from across the NAT Router. The Public IP Address and Port would also be used in the BDT of
remote BBMD's that need to reach this BBMD across the NAT Router. If no NAT Router is being
used, these fields can be left blank.
Broadcast Distribution Table –Click the edit button (pencil icon) to change the IP Address, IP
Port and Distribution Mask. Thefollowing buttons are also available along the bottom of the window:
oAdd Button - Add additional broadcasts, opening a new row of fields
oSave Button (floppy disk icon) - Save broadcast settings
oReset Fields Button (cycle icon) - Clear fields
6.3.3 BACnet MS/TP Connection Settings
Baud Rate –The serial baud rate used on the network.
Mode –Select Master or Slave.
MAC Address –Legal values are 0 to 127. Address must be unique on the physical network.
Max Master –The highest MAC address to scan for other MSTP master devices. The default of
127 is guaranteed to discover all other MSTP master devices on the network.
Max Info Frames –The number of transactions the Router may initiate while it has the MSTP
token. Default is 50.
Table of contents
Other MSA Gateway manuals

MSA
MSA fieldserver ProtoAir FPA-C41 User manual

MSA
MSA fieldserver QuickServer FS-QS-2 0 Series User guide

MSA
MSA MultiGard 5000 User manual

MSA
MSA fieldserver ProtoNode FPC-N54 User guide

MSA
MSA FieldServer ProtoNode FPC-N34 User guide

MSA
MSA FieldServer FGFD ProtoAir User manual

MSA
MSA fieldserver EZ Series User manual

MSA
MSA QuickServer FS-QS-2XX0 User manual

MSA
MSA fieldserver ProtoCarrier User manual

MSA
MSA FieldServer ProtoCarrier FPC-C34 User guide