11 – English
EN
5.1 - Insights on certain programmable functions and options
5.1.1 - Dip-switches 1 and 2 (for the Stop input)
- NO (normally open) contact.
- NC (normally closed) contact.
5.1.2 - Dip-switch 5 (for the SbS input)
> Open > Stop > (again...)
ON, during use of the automation it will not be possible to command the closing of the door. This command can only be given by programming
the automatic re-closing (dip-switch 8 set to ON), or through a radio transmitter.
5.1.3 - Dip-switch 6
• During an opening manoeuvre: if the condominium function is enabled (dip-switch 6 set to ON), it prevents the stoppage of the manoeuvre
after an opening or step-by-step command is sent, or its inversion prior to terminating at the limit switch.
• During a closing manoeuvre: if the condominium function is enabled (dip-switch 6 set to ON), the sending of an opening or step-by-step
command stops the manoeuvre and inverts its movement, making the door open.
5.2 - Memorisation of the dip-switch settings
After setting all the dip-switches (or later on, whenever the user wishes to modify the setting of one or more dip-switches), it is necessary to
switches has been shifted. Therefore, to memorise the new setting press and hold button T1 on the control unit, until the remains
steady lit green. Subsequently, release the button.
5.3 - Programming the “Work TimePause Time
are two basic parameters of the control unit and are programmed one after the other, with the same
procedure. These parameters can only be programmed once all the dip-switches have been set and memorised.
This duration must be long enough for the motor to complete the manoeuvre (up to the limit switch). The default setting (or after the memory
reason it is necessary to measure the most strenuous manoeuvre for the gate (i.e. the slowest one), which normally corresponds to the start of