Norton LEO 5710 Series User manual

Series 5710–Door Openings 85° to 110° or 111° to 180°
Rigid Arm and Slide Track Application
Maximum Hinge Side Frame Reveal to 1/8” (3mm)
Hinge (Pull) Side of Door Installation
80-9357-0110-020 Rev. A
80-9357-0110-020 Rev. A
WARNING
120 VOLT POTENTIAL PRESENT. MAKE SURE
POWER ISTURNED OFF DURING
INSTALLATION PROCEDURE.
An incorrectly installed or improperly
adjusted door operator can cause property
damage or personal injury. These
instructions should be followed to avoid the
possibility of misapplication or
misadjustment.
CAUTION
CAUTION
Right Hand Door Left Hand Door
Left
Hand
Door
Right
Hand
Door
5700 LEO Low Energy Power Operator
Installation Instructions
™
• U.L. labeled fire or smoke barrier door assemblies require that
the 120VAC (60Hz) power input to the door operator be
supplied through normally closed alarm contacts of the alarm
system/alarm panel.
• Power input to door operator must be 120 VAC (60Hz) to
terminals HOT and COM at terminal strip T1. Earthground
(GND) to green screw on Backplate.
• All wiring must conform to standard wiring practice in
accordance with national and local wiring codes.
• Note: Unless otherwise noted, all dimensions are given in
inches (millimeters).
• Minimum suggested and required material thickness for hollow
metal frames (skin plus reinforcement) is charted on Page 2.
• For wiring refer to Wiring Instructions on Pages 5 thru 8.
• Unit is Non-Handed.
• Door must be hung on butt hinges [5" (127mm) max. width] or
3/4" (19mm) offset pivots. A separate door and frame
preparation template will be supplied for other conditions.
• Door must swing freely through the entire opening and closing
cycle before beginning the installation.
• Use of a supplemental door stop is always recommended.
LEO
LEO
Requirements
Requirements
Installation Template
Component Layout
Installation Sequence
General Templating Information
Installation Sequence Continued
General Electrical Data
Input Power Configuration
Inverter Details
Wiring Diagram - Standard Function with Switches
Wiring Diagram - Optional Radio Frequency Function
Wiring Diagram - Fail Safe / Fail Secure Electric Strike
Wiring Diagram - Fail Safe Electromagnetic Lock
A.D.A / UL Information
1
2
2
3
3
4
5
5
6
6
7
7
8
8
1-1/2”(38mm)
Min. Frame
Face Frame
Reveal
Door
6”(152mm)
Min. Ceiling
Clearance
1-3/4”(44mm) Min.
2-1/4”(57mm) Max.
DoorThickness

80-9357-0110-020 Rev. A
2
Door Opening
Angle Dim“A”
Up to 110°
111° to 180° 15-1/2 (394)
13-1/4 (337)
GeneralTemplating Information Fasteners for Frame
• Before beginning the installation, verify that the door frame is
properly reinforced and is well anchored in the wall.
• Concealed electrical conduit and concealed switch or sensor
wires should be pulled to the frame before proceeding.
• Unreinforced hollow metal frames and aluminum frames should
be prepared and fitted with 1/4-20 blind rivet nuts, furnished by
others.
• 1/4-20 Machine screws for hollow metal and aluminum.
• No. 14x2-3/4" (70mm) long sheet metal screws for wood.
Fasteners for Door
• 1/4-20 Machine screws.
• 3/8" diameter x 1-5/8" (41mm) long sex nut.
WARNING: Make sure that (120V, 60Hz) input power is turned off at facility’s circuit breaker before proceeding with installation.main
Notes:
• All dimensions are given in inches (mm).
• Thickness recommended for reinforcements in hollow metal
doors and frames is charted at the left of this page.
• Do not scale drawing.
• Left hand door shown.
• Maximum frame reveal is 6-7/8” (175mm) for this application.
• This template information based upon use of 5" (127mm)
maximum width butt hinges. A separate template will be
supplied for other conditions.
• Conduit hole nearest the hinge is suggested for 120 VAC power
input.
Hollow Metal Door Frame Reinforcing
Frame
Material
12 Ga.
.1046
14 Ga.
.0747
16 Ga.
.0598
18 Ga.
.0478
(2.66)
(1.90)
(1.52)
(1.21)
12 Ga.
.1046
10 Ga.
.1343
10 Ga.
.1343
8 Ga.
.1644
(2.66)
(3.41)
(3.41)
(4.18)
18 Ga.
.0478
12 Ga.
.1046
12 Ga.
.1046
10 Ga.
.1343
(1.21)
(2.66)
(2.66)
(3.41)
Reinforcing
Recommended Min. Required
Template
1-1/8”
(29)
1-1/4
(32) 1-7/16
(37)
11
(279) 22
(559)
7-9/16
(192)
13-7/16
(341)
1-1/8
(29)
C
LHinge or Pivot
1/4-20 Machine Screws
or No. 14Wood Screws
(6 Places)
7/8 (23) Dia.
(2 Places)
3/8 Dia.
Sex Nuts
(3 Places)
Frame
Rabbet
Frame
Stop/Soffit
3
(76)
13-13/16
(350)
1/2
(13)
A
11-11/16
(297)
6”
Min.
Clearance
General Templating Information
14-3/16
(360)
12-15/16
(329) 13-13/16
(351)

Step1:
Step2:
ConcealedWired Units Only: Two (2)
NOTE:
three (3)
Step3:
Step4:
ConcealedWiredUnitsOnly:
SurfaceWired Units Only:
Step5:
Step 6:
DeterminehandofdoorfromillustrationonPage1.
Using template, (Page 2), locate and prepare holes in the
frame&door:
B. 7/8"(22mm) diameter
holesforconduit,forpowerinputandforswitch/sensorwires.
On new construction these holes will generally be
drilled by the frame supplier at their shop or at the time the
frameisinstalledinthewall.
C. Prepare holes for 3/8" diameter sex nuts.Standard
units are supplied with sex nuts and screws for 1-3/4"
(44mm) thick door. Sex nuts and screws for other door
thicknessesareavailabletoorder.
Remove cover from the unit and set cover & cover screws
aside.
Mountunittodoorframe.SelectAorBbelow.
A.
B.
Mounttrack assemblyto door using 3 1/4-20 screws&sex
nuts with buffer assembly toward hinge. Open part of
tracktofacetopofdoor.
Insert slide arm rod into slide arm tube setting the
distance between the pinion square and the slide stud
at 13-1/2” (343). Install 9/64” hex drive socket head
screw from screw pack. (See illustration upper right)
Frame
Door
A. Prepare holes for 1/4-20 machine screws or
No. 14 x 2-3/4" (70mm) wood screws. Blind rivet nuts (by
others) are suggested for unreinforced hollow metal frames
orforaluminumframes.
six (6)
Connectconduittoframeside
ofbackplate. Fastenunittodoorframe(sevenscrews).
Fasten unit to door frame (seven
screws). Mount conduit bracket (found in screw pack) to
unit’s backplate with two screws provided. Connect wiring
conduittobracket.
Installation Sequence
Step 7: Using an adjustable wrench, rotate pinion 45 toward
hinge, as shown below. With the arm assembly parallel
to the door, secure arm to pinion when square of the
pinion aligns with the square in the arm. Secure with
countersunk washer and 1/4-20 Flat Head Screw (with
thread lock) provided. Tighten screw with 7/16” wrench
or socket.
°
Step 8: Insert arm stud into slide block in track assembly.
Secure by pushing in on the retainer clip that extends
from the slide block in the track, until it is flush with the
slide block (see illustration below).
Component Layout
80-9357-0110-020 Rev. A 3
2
1
Attaching Arm Stud to Slide
Retainer Clip
BACKPLATE
REED SWITCH
CHAIN
RF POWER SUPPLY
(optional)
BREAKER SWITCH
OPEN / CLOSE POSITIONING ASSEMBLY
PINION EXTENSION / CLUTCH ASSEMBLY
1600 SERIES
CLOSER BODY INVERTER
MOTOR ASSEMBLY
POWER SWITCH
9/64” HEX
DRIVE SOCKET
SCREW
SLIDE ARM
TUBE
SLIDE ARM
ROD
13-1/2
(343)
Note: Center threaded hole of slider arm should
align with seventh hole of the slider tube
SLIDE TRACK
ASSEMBLY
SLIDER
BUFFER STOP
VIEW FROMTOP OF RIGHT HAND DOOR
Pinion
“T1” POWER INPUT
TERMINAL (3-POSITION)
ACCESSORY
TERMINAL
(4-POSITION)

Step 9:
to increase door closing power. Door control is shipped
set at midpoint of power setting.Maximum closing
power can be achieved with 8 (360°) clockwise turns of
the power adjustment screw.
Adjust closing power of unit (See Fig.3) - Using a 1/8”
allen wrench, turn the power adjustment shaft clockwise
Adjust Hydraulic valves using a 1/8” hex wrench to
obtain proper door closing speeds. See following
Step 10:
Step 13:
Step 13:
OFF
Step 14:
Step 15:
Step 16:
Step 17:
Step 18:
Step 19:
Step 20:
Step 21:
Step 22:
Turn power to unit on at the Unit Power Switch and turn the
Breaker Switch to “RESET”.
Using a short jumper cable, jump terminals 1 and 2, see Fig.
6 below, to activate unit. When door reaches 20 , switch
Breaker Switch to “ ” position cutting power to the unit.
Allow door to fully close (door may be manually pulled
closed).
Once door has fully closed, manually open door slightly and
insert a 1/8” allen wrench (provided with screw pack) into the
clutch assembly as shown below to create a small gap
between the two clutch components.
Manually close door and remove allen wrench from clutch
assembly.
Adjust Closing Ring Position (See Fig.8) - Loosen 8-32 set
screw located on Close Position Ring with 5/64” hex wrench
provided. Rotate Assembly until Closed Position Magnet
aligns with Reed Switch.
Adjust Open Ring Position - Loosen 8-32 set screw located
on Open Position Ring with 5/64” hex wrench provided.
Rotate Ring Assembly until Open Position Magnet is
approximately 180° from Closed Position Magnet.
Flip Breaker Switch to “RESET” to turn power on. Jump
terminals 1 and 2 (as shown in Step 13) to activate door.
Note open position of the door. Allow door to close.
Loosen and readjust Open Position Ring as necessary to
obtain desired door open position. Tighten set screw.
Make all connections necessary for any accessories to the
4-position Accessory Terminal (see Pages 6 - 8).
Make necessary adjustments to inverter (see Page 6).
Replace cover and cover screws.
°
Installation Sequence Continued
Power Adjustment
1/8"
Hex
Key
Increase
Power
Decrease
Power
80-9357-0110-020 Rev. A
4
Closing Cycle – Make adjustments, as necessary, to the Sweep
Speed "S" valve and Latch Speed "L" valve. See Fig. 4 below for
location of valves.Turn valves clockwise to reduce speed, counter
clockwise to increase speed.
1/8"
Hex
Key
Slower
Closing
Faster
Closing Closing Cycle
Closed
10°
L
a
t
c
h
R
a
n
g
e
S
w
e
e
p
R
a
n
g
e
Opening Cycle – Adjust Backcheck, "B" valve, as necessary, for
hydraulic resistance to door opening in the backcheck range. See
illustrationinFig.4atbottomofthispageforlocationofvalve.
1/8"
Hex
Key
Increase
Cushion
Decrease
Cushion
Opening Cycle
B
a
c
k
c
h
e
c
k
O
p
e
n
i
n
g
NOTE:ToomuchBackcheck,"B"valve,canaffect heoperation
of the units pump, preventing units from fully opening the
door. This valve may require fine tuning after all other
adjustmentshavebeenmade.
t
Note: A.D.A. requires that from an open position of
70°, the door will take at least 3 seconds to move to
a point 3”(75mm) from the latched position
measured at the leading edge of the door.
Step 11:
,
Make wiring connections using Wiring Instructions
on Page 5.
Step 12:Turn on facility’s main circuit breaker.
Figure 3
Sweep Valve
Latch Valve
Backcheck
Valve
Figure 4
Breaker
Switch
Unit Power Switch
Figure 5
1
2
3
4
1
2
3
4
Figure 6
1/8” Allen Wrench
Clutch Assembly
Figure 7
Reed Switch
Closing Position
Magnet
Closing Position
Adjustment
Opening Position
Magnet
Opening Position
Adjustment
Figure 8

Low Voltage
Control
Wiring
Incoming
Power
Input Power Configurations
CONCEALEDWIRING
Thread conduit fitting(s) into backplate as shown. A
second conduit fitting is required for low voltage
control wiring. CHECK LOCAL CODES. Pull conduit
out of header and attach to conduit fittings before
mounting Operator to door frame. Attach incoming
ground wire to backplate with ground screw as
illustratedbelow.
SURFACE WIRING
Anoptionalbracket isprovidedforusewithsurface
wiring. Remove the two cable clamps screws and
slip the bracket under the cable clamps. Push the
cable clamp screw through the bracket holes and
tighten. ½” conduit fittings can now be installed on
thebracket.
Optional Bracket
(for surface wiring) Ground
Lead Power
Leads
Ground
Screw
(Green)
Cable
Clamps Conduit
by Others
(from top)
“T1” Power
Input
Terminal
80-9357-0110-020 Rev. A 5
GroundWire Connection – Ground wire must be secured to backplate under head of (green) ground screw nearest to“T1” Power Input
Terminal. Screwlabeled“GND”.
General Electrical Data
Maximum current draw of unit is 0.6 amps.
Breaker Switch protects the motor assembly and inverter and
has a 5 amp rating.
Maximum wire size is:
12AWG at terminals HOT and COM on “T1” Power Input
Terminal.
14AWG at terminals 1 thru 4 on Accessory Terminal .
18AWG at terminals 22 thru 25 on “T1” Power Input
Terminal.
24
23
22
25
HOT
COM
Terminal Description
HOT
25
23
24
22
COM Commonpowerlead
Hotpowerlead
CircuitBreaker
Switch
CircuitBreaker
Common connection to Circuit Breaker /
Inverter

CL MAX MIN DEC/B ACC COMP
Component LayoutInverter Details
80-9357-0110-020 Rev. A
6
Standard Function with Switches
1
2
3
4
1
2
3
4
Notes:
1.Power input to Door Operator Unit is at
“T1” Power InputTerminal (not shown)
120VAC 60Hz.
Wall Switch, Card
Reader, Key Switch,
etc.
Normally Open Momentary
dry contacts
Wall Switch, Card
Reader, Key Switch,
etc.
Normally Open Momentary
dry contacts
Operation:
Doors arenormallyclosed.
Activating either switch will open both doors. Door will
closeafterholdopentimedelayhaselapsed.
1
2
3
4
1
2
3
4
Door 1 Door 2
POT FUNCTIONDESCRIPTION
CL Obstruction Detection on Open CW - Increase
CCW - Decrease
MAX Door Open Speed CW - Increase
CCW - Decrease
MIN Motor Reversing Speed CW - Increase
CCW - Decrease
DEC/B Hold Open Time (5 - 30 Seconds) CW - Increase
CCW - Decrease
ACC Door Mounting (Factory Set) Full CW - Push
Full CCW - Pull
COMP Motor Torque at Hold Open
Position CW - Increase
CCW - Decrease
Trimpot Adjuster
Inverter Adjustments:
Based on function adjustment desired, use table above to determine
which POT is to be adjusted.
Using Trimpot Adjuster, shown below and supplied with screw pack,
adjust the appropriate POT using illustration on the left.
Note: Trimpot may be
adjusted through slot
in finger guard.

Radio Frequency Function Option
80-9357-0110-020 Rev. A 7
Fail Secure / Fail Safe Electric Strike 24VDC Wiring
1
2
3
4
1
2
3
4
Optional Door 2
1
2
3
4
1
2
3
4
Door 1
ORANGE
BLACK
BROWN/WHITE
RED
RF
RECEIVER
BOARD
(PART OF
OPERATOR
UNIT)
WIRING FOR
MOMENTARY
HOLD OPEN
FUNCTION
Notes:
1.Power input to Door Operator Unit is at
“T1” Power InputTerminal (not shown)
120VAC 60Hz.
2. Radio Frequency Feature can be
purchased as a separate kit.
Operation:
Door is normally closed.
Activating wireless switch or hand held
wireless transmitter will open the door.
Door will close after hold open delay
elapses.
1
2
3
4
1
2
3
4
120VAC
Supplied by
Others
-+
24VDC Out
24 VDC
Electric Strike
+
-
Wall Switch, Card
Reader, Key Switch,
etc.
Normally Open Momentary
dry contacts
Notes:
1.Power input to Door Operator Unit is at
“T1” Power InputTerminal (not shown)
120VAC 60Hz.
View of Jumper in
Normally Open
Position For Use With
“Fail Safe” Strike
View of Jumper in
Normally Closed
Position For Use With
“Fail Secure”Strike
Jumper
(top pin
open)
Jumper
(bottom pin
open)
Operation:
Doorisnormallyclosedandlatched.
Activatingswitchwill unlocktheelectricstrikeand
the door will automatically open. Door will close
afterholdopentimedelayhaselapsed.
- The door will remain
duringpowerfailure.
- The door will remain
duringpowerfailure.
For Fail Secure Strike
locked
For Fail Safe Strike
unlocked
Normally
Open
Relay
Normally
Closed
Relay
Ground
COM
HOT 120
VAC

80-9357-0110-020 Rev. A
8
U.L.Listing Underwriters Laboratories,Inc. listed for use on
fire and smoke barrier door assemblies when the
120VAC (60Hz) power input is supplied through
the normally closed alarm contacts of a
compatible U.L. Listed alarm system or alarm
panel.
AmericansWithDisabilitiesAct(A.D.A.)
ANSIStandards
ANSI A117.1
providing
accessibility and usability for physically
handicappedpeople"
• ANSI A156.19"for power assist and low energy power
operateddoors"
Thesedooroperatorscanbeinstalled andadjustedtoconformwith
A.D.A.regulations.
– These door operators permit door
assemblies to conform to the requirements of this
specification "for buildings and facilities –
.
– These products are designed to conform to this
specification .
– "PAS" Function is designed to meet or exceed all of the
requirementsforthe"PowerAssistDoor".
– "POR" Function is designed to meet or exceed all of the
requirementsforthe"LowEnergyPowerOperatedDoor".
CUS
UL
®
An ASSAABLOY Group Co.
1902 Airport Road, Monroe, NC
Telephone:(800)-438-1951; Fax: (800)-338-0965
www.nortondoorcontrols.com
Door Controls
An ASSAABLOY Group Co.
Fail Safe Electromagnetic Lock 24VDC Wiring
1
2
3
4
1
2
3
4
120VAC
Supplied by
Others
-+
24VDC Out
Wall Switch, Card
Reader, Key Switch,
etc.
Normally Open Momentary
dry contacts
Notes:
1.Power input to Door Operator Unit is at
“T1” Power InputTerminal (not shown)
120VAC 60Hz.
2. Current draw must not exceed 1.200
Amps at Accessory Terminal 3.
+
-
24VDC Electromagnetic Lock
(Fail Safe)
A.D.A / UL
View of Jumper in
Normally Closed
Position
Jumper
(top pin
open)
Operation:
Doorisnormallyclosedandlatched.
Activating switch will cut power to mag lock and
the door will automatically open. Door will close
afterholdopentimedelayhaselapsed.
Thedoorwill duringpowerfailure.
unlock
Normally
Open
Relay

DATE
TEMPLATE NUMBER
80-7357-0110-020 (8-05)
7357-0110 8-05
www.nortondoorcontrols.com
Norton Door Controls
Series 5710 LEO™ – Door Openings 85° to 110° or 111° to 180°
Rigid Arm and SlideTrack Application
Maximum Hinge Side Frame Reveal to 1/8” (3mm)
Hinge (Pull) Side of Door Installation
Door Opening
Angle Dim“A”
Up to 110°
111° to 180° 15-1/2 (394)
13-1/4 (337)
Notes:
• Do not scale drawing.
• Left hand door shown from Pull
Side.
• All dimensions are given in inches
and millimeters (mm).
• This template information based
upon use of 5" (127mm) maximum
width butt hinges. This template not
for use with offset pivots.
• Ceiling clearance of 6” (152 mm)
from frame rabbet is required for
this application.
• Maximum frame reveal is 1/8” (3
mm) for this application.
• Conduit hole nearest hinge is
suggested for 120 VAC power input.
• Thickness recommended for
reinforcements in hollow-metal
doors and frames should provide a
combined material thickness of
.164” (4.2 mm) MIN.
2”(51mm)
Min.
Frame Face
1-1/8”
(29)
1-1/4
(32) 1-7/16
(37)
11
(279) 22
(559)
7-9/16
(192)
13-7/16
(341)
1-1/8
(29)
C
LHinge
1/4-20 Machine Screws
or No. 14Wood Screws
(6 Places)
7/8 (23) Dia.
(2 Places)
3/8 Dia.
Sex Nuts
(3 Places)
Frame
Rabbet
Frame
Stop/Soffit
3
(76)
13-13/16
(350)
1/2
(13)
A
11-11/16
(297)
6”
(152mm)
Min.
Clearance
14-3/16
(360)
12-15/16
(329) 13-13/16
(351)
5/8”(16)
Stop

DATE
TEMPLATE NUMBER
80-7357-0130-020 Rev. A
7357-0130 Rev A 10-04
www.nortondoorcontrols.com
Norton Door Controls
Series 5730 LEO™ – Door Openings 85° to 110° or 111° to 180°
Double Lever Arm Application for Frame Reveals 3” (76) to 7”(178mm)
Stop (Push) Side of Door Installation
1-11/16
(43)
1-1/4
(32) 11/16
(17.5)
1-3/4
(44)
12-15/16
(329)
7-9/16
(192)
13-7/16
(341)
3/8
(10)
C
LHinge or Pivot
1/4-20 Machine Screws
or No. 14Wood Screws
(6 Places)
7/8
(22)
(Conduit Holes -
2 Places)
Dia.
Sex Nuts
(2 Places)
Frame
Rabbet
Frame
Stop/Soffit
A
13-13/16
(351)
1/2
(13)
B
5-1/4”
Min.
Clearance
11-11/16
(297)
3/8
(19)
14-3/16
(360) 13-13/16
(351)
Door Opening
Angle Dim“A” Dim“B”
Up to 110°
111° to 170° 12 (305)
9-1/2 (241) 13-1/4 (337)
15-3/4 (400)
Frame Rabbet
REVEAL
Notes:
• Do not scale drawing.
• Left hand door shown from Push Side.
• All dimensions are given in inches and
millimeters (mm).
• This template information based upon
use of 5" (127 mm) maximum width
butt hinges or 3/4” (19 mm) offset
pivots.
• Ceiling clearance of 5-1/4” (133 mm)
from frame rabbet is required for this
application.
• Frame reveal range for this application
is 3” (76 mm) to 7” (178 mm) for this
application.
• Conduit hole nearest hinge is
suggested for 120 VAC power input.
• Thickness recommended for
reinforcements in hollow-metal doors
and frames should provide a combined
material thickness of .164” (4.2 mm)
MIN.

Series 5730–Door Openings 85° to 110° or 111° to 180°
Double Lever Arm Application for Frame Reveals 3” (76) to 7” (178mm)
Stop (Push) Side of Door Installation
80-9357-0130-020 Rev. A
Right Hand DoorLeft Hand Door
80-9357-0130-020 Rev. A
WARNING
120 VOLT POTENTIAL PRESENT. MAKE SURE
POWER ISTURNED OFF DURING
INSTALLATION PROCEDURE.
An incorrectly installed or improperly
adjusted door operator can cause property
damage or personal injury. These
instructions should be followed to avoid the
possibility of misapplication or
misadjustment.
CAUTION
CAUTION
5700 LEO Low Energy Power Operator
Installation Instructions
™
Left
Hand
Door
Right
Hand
Door
• U.L. labeled fire or smoke barrier door assemblies require that
the 120VAC (60Hz) power input to the door operator be
supplied through normally closed alarm contacts of the alarm
system/alarm panel.
• Power input to door operator must be 120 VAC (60Hz) to
terminals HOT and COM at terminal strip T1. Earthground
(GND) to green screw on Backplate.
• All wiring must conform to standard wiring practice in
accordance with national and local wiring codes.
• Note: Unless otherwise noted, all dimensions are given in
inches (millimeters).
• Minimum suggested and required material thickness for hollow
metal frames (skin plus reinforcement) is charted on Page 2.
• For wiring refer to Wiring Instructions on Pages 5 thru 8.
• Unit is Non-Handed.
• Door must be hung on butt hinges [5" (127mm) max. width] or
3/4" (19mm) offset pivots. A separate door and frame
preparation template will be supplied for other conditions.
• Door must swing freely through the entire opening and closing
cycle before beginning the installation.
• Use of a supplemental door stop is always recommended.
LEO
LEO
Requirements
Requirements
Installation Template
Component Layout
Installation Sequence
General Templating Information
Installation Sequence Continued
General Electrical Data
Input Power Configuration
Inverter Details
Wiring Diagram - Standard Function with Switches
Wiring Diagram - Optional Radio Frequency Function
Wiring Diagram - Fail Safe / Fail Secure Electric Strike
Wiring Diagram - Fail Safe Electromagnetic Lock
A.D.A / UL Information
1
2
2
3
3
4
5
5
6
6
7
7
8
8
1-1/2”(38mm)
Min. Frame
Face Frame
Reveal
Door
5-1/4”(133mm)
Min. Ceiling
Clearance
1-3/4”(44mm) Min.
2-1/4”(57mm) Max.
DoorThickness

80-9357-0130-020 Rev. A
2
Door Opening
Angle Dim“A” Dim“B”
Up to 110°
111° to 170° 12 (305)
9-1/2 (241) 13-1/4 (337)
15-3/4 (400)
GeneralTemplating Information Fasteners for Frame
• Before beginning the installation, verify that the door frame is
properly reinforced and is well anchored in the wall.
• Concealed electrical conduit and concealed switch or sensor
wires should be pulled to the frame before proceeding.
• Unreinforced hollow metal frames and aluminum frames should
be prepared and fitted with 1/4-20 blind rivet nuts, furnished by
others.
• 1/4-20 Machine screws for hollow metal and aluminum.
• No. 14x2-3/4" (70mm) long sheet metal screws for wood.
Fasteners for Door
• 1/4-20 Machine screws.
• 3/8" diameter x 1-5/8" (41mm) long sex nut.
WARNING: Make sure that (120V, 60Hz) input power is turned off at facility’s circuit breaker before proceeding with installation.main
Notes:
• All dimensions are given in inches (mm).
• Thickness recommended for reinforcements in hollow metal
doors and frames is charted at the left of this page.
• Do not scale drawing.
• Left hand door shown.
• Maximum frame reveal is 7” (178mm) for this application.
• This template information based upon use of 5" (127mm)
maximum width butt hinges or 3/4" (19mm) offset pivots. A
separate template will be supplied for other conditions.
• Conduit hole nearest to hinge is suggested for 120 VAC power
input.
Hollow Metal Door Frame Reinforcing
Frame
Material
12 Ga.
.1046
14 Ga.
.0747
16 Ga.
.0598
18 Ga.
.0478
(2.66)
(1.90)
(1.52)
(1.21)
12 Ga.
.1046
10 Ga.
.1343
10 Ga.
.1343
8 Ga.
.1644
(2.66)
(3.41)
(3.41)
(4.18)
18 Ga.
.0478
12 Ga.
.1046
12 Ga.
.1046
10 Ga.
.1343
(1.21)
(2.66)
(2.66)
(3.41)
Reinforcing
Recommended Min. Required
Template
1-11/16
(43)
1-1/4
(32) 11/16
(17.5)
1-3/4
(44)
12-15/16
(329)
7-9/16
(192)
13-7/16
(341)
3/8
(10)
C
LHinge or Pivot
1/4-20 Machine Screws
or No. 14Wood Screws
(6 Places)
7/8
(22)
(Conduit Holes -
2 Places)
Dia.
Sex Nuts
(2 Places)
Frame
Rabbet
Frame
Stop/Soffit
A
13-13/16
(351)
1/2
(13)
B
5-1/4”
Min.
Clearance
11-11/16
(297)
3/8
(19)
General Templating Information
14-3/16
(360) 13-13/16
(351)

BACKPLATE
REED SWITCH
CHAIN
INVERTER
MOTOR ASSEMBLY
Component Layout
Adjusting
Rod
Arm
Slide
Door
Shoe
Main
Arm
BACKPLATE
REED SWITCH
CHAIN
RF POWER SUPPLY
(Optional - For RF
Units Only)
“T1” POWER INPUT
TERMINAL (3-POSITION)
OPEN / CLOSE POSITION RINGS
PINION EXTENSION /
CLUTCH ASSEMBLY
1600 SERIES
CLOSER BODY
INVERTER
MOTOR ASSEMBLY
POWER SWITCH
Figure 2
Step1:
Step2:
ConcealedWired Units Only: Two (2)
NOTE:
two (2)
Step3:
Step4:
Concealed Wired Units Only:
Surface Wired Units Only:
Step5:
DeterminehandofdoorfromillustrationonPage1.
Using template, (Page 2), locate and prepare holes in the
frame&door:
B. 7/8"(22mm) diameter
holesforconduit,forpowerinputandforswitch/sensorwires.
On new construction these holes will generally be
drilled by the frame supplier at their shop or at the time the
frameisinstalledinthewall.
C. Prepare holes for 3/8" diameter sex nuts. Standard
units are supplied with sex nuts and screws for 1-3/4"
(44mm) thick door. Sex nuts and screws for other door
thicknessesareavailabletoorder.
Remove cover from the unit and set cover & cover screws
aside.
Mountunittodoorframe.SelectAorBbelow.
A.
B.
Install main arm onto pinion shaft of unit at a 90° angle to
the door frame. Align arm mark “S”with the flat corner of
thepinionshaftsquare. (SeeFig.1,upperright.)
Frame
Door
A. Prepare holes for 1/4-20 machine screws or
No. 14 x 2-3/4" (70mm) wood screws. Blind rivet nuts (by
others) are suggested for unreinforced hollow metal frames
orforaluminumframes.
six (6)
Connect conduit to frame
sideofbackplate. Fastenunittodoorframe(sixscrews).
Fasten unit to door frame (six
screws). Mountconduitbracket(foundinscrewpack)touni’t
backplatewith two screwsprovided. Connectwiring conduit
tobracket.
Installation Sequence
Step 6: Secure main arm to pinion with 1/4-20 Flange Head
Screw provided. Tighten screw with 7/16" wrench or
socket.
Step 7:
Step 8:
Mount arm shoe to door using 2 1/4-20 screws & sex
nuts provided with screw pack.
PRELOAD ARM (See Fig.2, below): Remove 1/4-20
hex head screw on adjusting rod and insert adjusting
rod into arm slide. Reinstall 1/4-20 screw and leave
loose. Rotate main arm in direction away from the hinge
edge until the adjusting rod and arm slide are
perpendicular (at a 90° angle) to the door frame.Tighten
the 1/4-20 hex head screw on the adjusting rod to
secure arm in this new position.
Left hand door shown
viewed from ceiling
looking down on unit.
R
L
Y
S
Z
Arm Mark Pinion Flat
Figure 1
Component Layout
80-9357-0130-020 Rev. A 3
Adjusting
Rod
Arm
Slide
Door
Shoe
Main
Arm
MAIN ARM / SLIDE
UNIT ASSEMBLY
SHOE
SHOE / ADJUSTING
ROD FOREARM
SCREW
BREAKER SWITCH
ACCESSORY
TERMINAL
(4-POSITION)

Installation Sequence Continued
Step 9:
to increase door closing power. Door control is shipped
set at midpoint of power setting. Maximum closing
power can be achieved with 8 (360°) clockwise turns of
the power adjustment screw.
Adjust closing power of unit (See Fig.3) - Using a 1/8”
allen wrench, turn the power adjustment shaft clockwise
Adjust Hydraulic valves using a 1/8” hex wrench to
obtain proper door closing speeds. See following
Step 10:
Power
Adjustment
1/8"
Hex
Key
Increase
Power
Decrease
Power
Closing Cycle – Make adjustments, as necessary, to the Sweep
Speed "S" valve and Latch Speed "L" valve. See Fig. 4 below for
location of valves.Turn valves clockwise to reduce speed, counter
clockwise to increase speed.
1/8"
Hex
Key
Slower
Closing
Faster
Closing Closing Cycle
Closed
10°
L
a
t
c
h
R
a
n
g
e
S
w
e
e
p
R
a
n
g
e
Opening Cycle – Adjust Backcheck, "B" valve, as necessary, for
hydraulic resistance to door opening in the backcheck range. See
illustrationatbottomofthispageforlocationofvalve.
1/8"
Hex
Key
Increase
Cushion
Decrease
Cushion
Opening Cycle
B
a
c
k
c
h
e
c
k
O
p
e
n
i
n
g
NOTE:ToomuchBackcheck,"B"valve,canaffect heoperation
of the units pump, preventing units rom fully opening the
door. This valve may require fine tuning after all other
adjustmentshavebeenmade.
t
f
Sweep Valve
Latch Valve
Backcheck
Valve
80-9357-0130-020 Rev. A
4
Step 13:
Step 13:
OFF
Step 14:
Step 15:
Step 16:
Step 17:
Step 18:
Step 19:
Step 20:
Step 21:
Step 22:
Turn power to unit on at the Unit Power Switch and turn the
Breaker Switch to “RESET”.
Using a short jumper cable, jump terminals 1 and 2, see Fig.
6 below, to activate unit. When door reaches 20 , switch
Breaker Switch to “ ” position cutting power to the unit.
Allow door to fully close (door may be manually pulled
closed).
Once door has fully closed, manually open door slightly and
insert a 1/8” allen wrench (provided with screw pack) into the
clutch assembly as shown below to create a small gap
between the two clutch components.
Manually close door and remove allen wrench from clutch
assembly.
Adjust Closing Ring Position (See Fig. 8) - Loosen 8-32 set
screw located on Close Position Ring with 5/64” hex wrench
provided. Rotate Assembly until Closed Position Magnet
aligns with Reed Switch.
Adjust Open Ring Position - Loosen 8-32 set screw located
on Open Position Ring with 5/64” hex wrench provided.
Rotate Ring Assembly until Open Position Magnet is
approximately 180° from Closed Position Magnet.
Flip Breaker Switch to “RESET” to turn power on. Jump
terminals 1 and 2 (as shown in Step 13) to activate door.
Note open position of the door. Allow door to close.
Loosen and readjust Open Position Ring as necessary to
obtain desired door open position. Tighten set screw.
Make all connections necessary for any accessories to the
4-position terminal on “T1” bracket (see Pages 6 - 8).
Make necessary adjustments to inverter (see Page 6).
Replace cover and cover screws.
°
Breaker
Switch
Unit Power Switch
Figure 3
Figure 4
Note: A.D.A. requires that from an open position of
70°, the door will take at least 3 seconds to move to
a point 3”(75mm) from the latched position
measured at the leading edge of the door.
Step 11:
,
Make wiring connections using Wiring Instructions
on Page 5.
Step 12:Turn on facility’s main circuit breaker.
Figure 5
1
2
3
4
1
2
3
4
Figure 6
1/8” Allen Wrench
Clutch Assembly
Figure 7
Reed Switch
Closed Position
Magnet
Close Position Ring
Open Position
Magnet
Open Position Ring
Figure 8

Low Voltage
Control
Wiring
Incoming
Power
Input Power Configurations
CONCEALEDWIRING
Thread conduit fitting(s) into backplate as shown. A
second conduit fitting is required for low voltage
control wiring. CHECK LOCAL CODES. Pull conduit
out of header and attach to conduit fittings before
mounting Operator to door frame. Attach incoming
ground wire to backplate with ground screw as
illustratedbelow.
SURFACE WIRING
Anoptionalbracket isprovidedforusewithsurface
wiring. Remove the two cable clamps screws and
slip the bracket under the cable clamps. Push the
cable clamp screw through the bracket holes and
tighten. ½” conduit fittings can now be installed on
thebracket.
Optional Bracket
(for surface wiring) Ground
Lead Power
Leads
Ground
Screw
(Green)
Cable
Clamps Conduit
by Others
(from top)
“T1” Power
Input
Terminal
80-9357-0130-020 Rev. A 5
GroundWire Connection – Ground wire must be secured to backplate under head of (green) ground screw nearest to“T1” Power Input
Terminal. Screwlabeled“GND”.
General Electrical Data
Maximum current draw of unit is 0.6 amps.
Breaker Switch protects the motor assembly and inverter and
has a 5 amp rating.
Maximum wire size is:
12AWG at terminals HOT and COM on “T1” Power Input
Terminal.
14AWG at terminals 1 thru 4 on Accessory Terminal .
18AWG at terminals 22 thru 25 on “T1” Power Input
Terminal.
24
23
22
25
HOT
COM
Terminal Description
HOT
25
23
24
22
COM Commonpowerlead
Hotpowerlead
CircuitBreaker
Switch
CircuitBreaker
Common connection to Circuit Breaker /
Inverter

CL MAX MIN DEC/B ACC COMP
Component LayoutInverter Details
80-9357-0130-020 Rev. A
6
Standard Function with Switches
1
2
3
4
1
2
3
4
Notes:
1.Power input to Door Operator Unit is at
Power Input Terminal (not shown)
120VAC 60Hz.
Wall Switch, Card
Reader, Key Switch,
etc.
Normally Open Momentary
dry contacts
Wall Switch, Card
Reader, Key Switch,
etc.
Normally Open Momentary
dry contacts
Operation:
Doors arenormallyclosed.
Activating either switch will open both doors. Door will
closeafterholdopentimedelayhaselapsed.
1
2
3
4
1
2
3
4
Door 1 Door 2
POT FUNCTIONDESCRIPTION
CL Obstruction Detection on Open CW - Increase
CCW - Decrease
MAX Door Open Speed CW - Increase
CCW - Decrease
MIN Motor Reversing Speed CW - Increase
CCW - Decrease
DEC/B Hold Open Time (5 - 30 Seconds) CW - Increase
CCW - Decrease
ACC Door Mounting (Factory Set) Full CW - Push
Full CCW - Pull
COMP Motor Torque at Hold Open
Position CW - Increase
CCW - Decrease
Trimpot Adjuster
Inverter Adjustments:
Based on function adjustment desired, use table above to determine
which POT is to be adjusted.
Using Trimpot Adjuster, shown below and supplied with screw pack,
adjust the appropriate POT using illustration on the left.
Note: Trimpot may be
adjusted through slot
in finger guard.

Radio Frequency Function Option
80-9357-0130-020 Rev. A 7
Fail Secure / Fail Safe Electric Strike 24VDC Wiring
1
2
3
4
1
2
3
4
Optional Door 2
1
2
3
4
1
2
3
4
Door 1
ORANGE
BLACK
BROWN/WHITE
RED
RF
RECEIVER
BOARD
(PART OF
OPERATOR
UNIT)
WIRING FOR
MOMENTARY
HOLD OPEN
FUNCTION
Notes:
1.Power input to Door Operator Unit is at
Power Input Terminal (not shown)
120VAC 60Hz.
2. Radio Frequency Feature can be
purchased as a separate kit.
Operation:
Door is normally closed.
Activating wireless switch or hand held
wireless transmitter will open the door.
Door will close after hold open delay
elapses.
1
2
3
4
1
2
3
4
120VAC
Supplied by
Others
-+
24VDC Out
24 VDC
Electric Strike
+
-
Wall Switch, Card
Reader, Key Switch,
etc.
Normally Open Momentary
dry contacts
View of Jumper in
Normally Open
Position For Use With
“Fail Safe” Strike
View of Jumper in
Normally Closed
Position For Use With
“Fail Secure”Strike
Jumper
(top pin
open)
Jumper
(bottom pin
open)
Operation:
Doorisnormallyclosedandlatched.
Activatingswitchwill unlocktheelectricstrikeand
the door will automatically open. Door will close
afterholdopentimedelayhaselapsed.
- The door will remain
duringpowerfailure.
- The door will remain
duringpowerfailure.
For Fail Secure Strike
locked
For Fail Safe Strike
unlocked
Notes:
1.Power input to Door Operator Unit is at
Power Input Terminal (not shown)
120VAC 60Hz.
Ground
COM
HOT 120
VAC
Normally
Open
Relay
Normally
Closed
Relay

80-9357-0130-020 Rev. A
8
U.L.Listing Underwriters Laboratories,Inc. listed for use on
fire and smoke barrier door assemblies when the
120VAC (60Hz) power input is supplied through
the normally closed alarm contacts of a
compatible U.L. Listed alarm system or alarm
panel.
AmericansWithDisabilitiesAct(A.D.A.)
ANSIStandards
ANSI A117.1
providing
accessibility and usability for physically
handicappedpeople"
• ANSI A156.19"for power assist and low energy power
operateddoors"
Thesedoor operatorscanbe installedandadjustedto conformwith
A.D.A.regulations.
– These door operators permit door
assemblies to conform to the requirements of this
specification "for buildings and facilities –
.
– These products are designed to conform to this
specification .
– "PAS" Function is designed to meet or exceed all of the
requirementsforthe"PowerAssistDoor".
– "POR" Function is designed to meet or exceed all of the
requirementsforthe"LowEnergyPowerOperatedDoor".
CUS
UL
®
An ASSA ABLOY Group Co.
1902 Airport Road, Monroe, NC
Telephone:(800)-438-1951; Fax: (800)-338-0965
www.nortondoorcontrols.com
Door Controls
An ASSA ABLOY Group Co.
Fail Safe Electromagnetic Lock 24VDC Wiring
1
2
3
4
1
2
3
4
120VAC
Supplied by
Others
-+
24VDC Out
Wall Switch, Card
Reader, Key Switch,
etc.
Normally Open Momentary
dry contacts
View of Jumper in
Normally Closed
Position
Jumper
(top pin
open)
Operation:
Doorisnormallyclosedandlatched.
Activating switch will cut power to mag lock and
the door will automatically open. Door will close
afterholdopentimedelayhaselapsed.
Thedoorwill duringpowerfailure.
unlock
Notes:
1.Power input Door Operator Unit is at
Power Input Terminal Strip (not shown)
120VAC 60Hz.
2.Current draw must not exceed 1.200
amps at Accessory Terminal 3.
+
-
24VDC Electromagnetic Lock
(Fail Safe)
A.D.A / UL
Normally
Open
Relay
Table of contents
Other Norton Door Opening System manuals

Norton
Norton CloserPlus CLP7570 Series User manual

Norton
Norton Tri-Style 1600 Series User manual

Norton
Norton 8380 User manual

Norton
Norton 1600 Series User manual

Norton
Norton 6900 PowerMatic User manual

Norton
Norton PR7570 Series User manual

Norton
Norton Power Track Series User manual

Norton
Norton tri-style 1603BC User manual

Norton
Norton Assa Abloy D6001DE-L Series User manual

Norton
Norton Power Track Master Unit PTD Series User manual