
Page 9
10. Inspect the system to determine if complete pumping may be required. See "System Pumping" section of this document.
11. Upon completion of the inspection, insure that all access covers are properly reinstalled. Any missing or damaged
access covers should be immediately replaced. DANGER: Make sure the system access covers are in good
condition and securely installed on the mounting castings. Never allow access risers to be left uncovered
or partially covered. Failure to secure access covers and safety nets could result in bodily injury, illness or
death. Riser safety nets are available from Norweco for concrete or plastic risers.
12. Approved replacement parts are available from the authorized system dealer listed on the control center cover.
System Pumping
1. The Hydro-Kinetic system is a biological treatment device and will not require pumping as often as a septic tank.
Pumping of the system will likely be required at 3 to 5 year intervals depending upon system usage, loading and
treatment requirements. If pumping is required more frequently than every 2 years, there is an operational problem
with the system and it should be evaluated in greater detail.
2. If the service technician suspects that the system may require pumping, a settleable solids test should be performed on a
sample from the aeration chamber. The air pump must be removed from the aeration chamber riser to perform this test.
3. Immediately after removing air pump, dip a graduated cone or other clear container into the aeration chamber to a
depth of 2½ feet. Set the container on a level surface and then allow the solids to settle for 30 minutes while you
complete the service inspection. Do not disturb the container during the test.
4. After 30 minutes, read the level of solids and compare it with the total liquid volume in the container. Calculate the
percentage of settled solids volume (i.e. ½ full of solids equals 50%). If the settled material contains large pockets
of clear liquid, estimate the volume of these pockets and reduce the settled solids reading by that amount. A settled
solids reading of up to 80% indicates no adjustments are necessary. A settled solids level greater than 80% in the
aeration chamber indicates excessive solids and that the system should be pumped.
5. If it is determined that pumping is required, contact a tank pumping service licensed by the local regulatory agency.
The septage or biosolids from the system must be removed and disposed of in a manner consistent with federal, state
and local regulations. Advise the pumping service that they will be pumping approximately 1,500 gallons.
6. Turn o the air pump and recirculation pump before tank pumping.
7. Remove the access cover from the aeration and clarication chambers. Unplug the air pump and disassemble the
union located on the primary air connection. Remove the air pump, primary air connection and support base from
the aeration riser. Use the universal tool to bend exible diuser tubing and remove the diuser drop pipe assembly.
Connect the suction hose to the pump being used to evacuate the chamber.
8. Activate the pump and remove the aeration chamber contents. Pump the aeration chamber from the top down, to remove
biologically inactive material. Feed the hose down as the liquid is being evacuated from the aeration chamber. It is not
necessary to wash down the sidewalls or tank bottom. Pump only 75% of the volume out of the aeration chamber to
facilitate plant re-start. Replace the diuser drop pipe assembly. Reinstall the support base, primary air connection and
air pump. Reassemble the union in the primary air connection and plug in the air pump. Replace both access covers.
9. The Bio-Film Reactor tank should be pumped after the aeration chamber. Remove the Bio-Film Reactor tank
access cover. Lower the hose into the inuent chamber until it contacts the bottom of the tank. Withdraw the hose
approximately 2 inches. Completely pump 100% of the contents from the chamber and rinse the media with a hose
during tank pumping. Replace the Bio-Film Reactor tank access cover.
10. Next, pump the anoxic chamber. Remove the anoxic chamber access cover. Use the universal tool to bend exible
mixing bar tubing and remove the mixing bar drop pipe to allow access for the suction hose. Lower the hose until it
contacts the bottom of the tank. Withdraw the hose approximately 2 inches. Completely pump 100% of the contents
from the chamber. Reinstall the mixing bar drop pipe assembly and replace the access cover.
11. The nal chamber to pump is the pretreatment chamber. Remove the pretreatment chamber access cover. Break
up the scum mat to facilitate pumping. Lower the hose until it contacts the bottom of the tank. Withdraw the hose
approximately 2 inches. Activate the pump and remove 100% of the chamber contents. It is not necessary to wash
down the sidewalls or tank bottom. If solids are so concentrated that the suction hose cannot withdraw them, tank
contents may be backushed to break up the solid matter. Replace the pretreatment chamber access cover.
12. After pumping, rell all chambers to capacity with clean water. Return all plumbing and equipment to its properly
installed location. Replace any access covers that were removed. Turn on power to the air pump and the recirculation