olympia electronics BS-694 User manual

http://www.facebook.com/OlympiaElectronics
http://twitter.com/olympiaelectro
http://www.linkedin.com/company/1967613?trk=tyah
http://www.youtube.com/channel/UCIINc4DGSYH_0loHJqwsgoQ
https://plus.google.com/105672704483774116420/posts
http://www.olympia-electronics.gr
GENERAL
BS-695 and BS-694 detectors are used to give
us a quick warning in case there is a natural gas
or LPG gas leak.
The installation must be done by a qualified
personnel. The instructions must be read first
before the installation.
Emergency actions
It is recommended that the following advice
should be given in the event of an alarm
sounding or the smell of gas even without an
alarm:
Keep calm, and carry out the following actions,
not necessarily in the order given:
- extinguish all naked flames, including
smoking material.
- turn off all gas appliances.
- do not switch on or off any electrical
equipment, including the gas detection
apparatus.
- turn off the gas supply at the gas main control
and/or ( with a LPG supply) the storage tank.
- open doors and windows to increase
ventilation;
- do not use a telephone in the building where
the presence of a gas is suspected.
If the alarm continues to operate, even after an
alarm resetting action where appropriate, and
the cause of the leak in not apparent and/or
cannot be corrected, vacate the premises and
IMMEDIATELY NOTIFY the gas supplier in
order that the installation may be tested and
made safe, and any necessary repair carried
out.
Placement
Depending on the monitored gas, the unit must
be placed 30cm from the ceiling (for methane,
natural gas) or 30cm from the floor (for propane,
butane, LPG). The horizontal distance should
not be more than 4 meters from the probable
gas leak point and the detectors must not be
placed in humid or drafty areas.
It is suggested that the detector is tested for
good operation every 6 months or if it is
changed position.
The unit must should not be sited:
- directly above cooking appliances.
- directly above sink.
- adjacent to extractor fans.
- in any outside location.
- where the environmental conditions are
outside the manufacturers operational
specification.
Installation
For the installation of the device first you must
remove the red plastic with a screwdriver as
shown in figure 1 and unscrew the screw in the
middle. Then with the help of figure 2 you can
connect the external devices.
Sensitivity
The BS-694 detectors are activated when the
220-240V AC/50-60Hz
Yes Yes
Relay (230V AC, 5Α)
Power LED , alarm LED , fault LED
IP40
5 years
EN 50194, EN 61000-3-2, EN 61000-3-3
o
0 to 60 C
Up to 95%
No No
5-15 % L.E.L. Propane 5-15 % L.E.L. Methane
145 x 85 x 45 mm
Bayblend FR3010
BS-694 BS-695
4VA
TECHNICAL CHARACTERISTICS
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
CONSTRUCTION MATERIALS
EXTERNAL DIMENSIONS
TYPICAL WEIGHT
GUARANTEE
OPERATION VOLTAGE
AVERAGE POWER CONSUMPTION
SENSITIVITY
OUTPUTS
ELECTRO VALVE OUTPUT
EXTERNAL BUZZER OUTPUT
SENSOR LIFETIME
INDICATIONS
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
2 years
270gr.
BS-694 Autonomous LPG detector
BS-695 Autonomous natural gas-methane detector
Page 1 from 4
Thank you for your trust in our products.
Olympia Electronics - European manufacturer.
921695000_09_009

content of gas (propane or butane), in the
monitored area, exceeds 5 - 15% of the lower
explosive level (L.E.L).
The BS-695 detectors are activated when the
content of gas (methane), in the monitored
area, exceeds 5 - 15% of the lower explosive
level (L.E.L). The same detectors can also be
used as an alcohol vapor detector.
They are connected and operate with the mains
power supply voltage of 230V AC, as shown in
figure 2.
When the detector is activated, an internal
sounder(buzzer) is sounded and the internal
relay is activated. The activation stops when
you push the test button or the gas content
drops below 5-15% of the L.E.L.
The electro-valve resets manually.
Indication LEDs and operation
The green LED shows the presence of the
mains power supply. When first installed, the
green LED blinks for 20 seconds until the
sensor compensates to its surroundings.
When the red LED is lit then the unit is in alarm
mode.
When the yellow LED is lit the unit has an fault.
A blinking red LED means that there was an
alarm condition but it has now passed. The
same applies for a blinking yellow LED and the
fault condition.
When the test button is pressed, the system is
tested and restarted. During the test the internal
circuits are checked, the relay is activated, and
the internal buzzer sounds. Also, during the test
all alarm and fault indications are reset.
After the test and if an electro-valve was
connected to the unit, a manual reset of the
electro-valve must be done.
Electro valve connections
The gas supply is automatically turn OFF in the
event of an alarm or fault condition. The electro-
valve can only be reset manually by the user, by
pressing on point “Α” as show in figure 1.
Depending on the type of electro-valve used,
the corresponding connection diagram is
shown in figure 5. Care must be taken to
position the link of JMP1 in the correct position.
It is suggested that this unit is used in
cooperation with Οlympia Electronics Electro-
valves type BS-684 (12V N.O.) Or BS-682 (
230V AC N.O.). The connection cable, when
you use BS-684, must be at least 2x2.5mm
diameter and no more than 4m length.
Figure 4 shows the connection of multiple
detectors in a network connection, for covering
a larger area and using one 12V DC NO
electro-valve.
Attention!! The position link of JMP1 set the
relay status.
If a link is set on A ( figure 4 ) the relay is
energized (NO) in normal condition and on
alarm or fault condition the relay is not
energized.
The opposite occurs if a link is set on B.
ATTENTION!! The devices must not be tested
using gas filled lighters because the sensor will
be destroyed.
Page 2 from 4
N.C.
Α
Figure 1. Diagram with manual reset
normally closed and normally open electro-valve
There is a screw behind the plastic cover
Remove the plastic cover
using a flat blade screw driver
921695000_09_009

Page 3 from 4
L NC NCNO
JMP1
AB
1
JMP1
AB
1
JMP1
AB
1
...
E.V. 12V DC N.O.
1st V 2nd
-OUT+
L NC NCNO L NC NCNOL NC NCNO L NC NCNO
Sensor
Power LED
Alarm LED
Fault LED
Button
SENSOR
-OUT+
L NC NCNO
LN
~230 V
Electro-valve ~230V
Diagram with manual reset and
normally open electro-valve
JMP1
AB
1
Diagram with manual reset and
normally closed electro-valve
E.V. ~230V N.C.
JMP1
AB
1
LN
~230 V
E.V. ~230V N.O.
LN
~230 V
L NC NCNO L NC NCNO
Figure 2. Connection diagram of a detector
Figure 3. Connecting multiple detectors in a network and using one
electro-valve 12VDC N.O.
Figure 5. Diagrams for connecting various types of electro-valves
921695000_09_009

Page 4 from 4
WARRANTY
Olympia Electronics guarantees the quality, condition and operation of the goods. The period of
warranty is specified in the official catalogue of Olympia Electronics and also in the technical leaflet,
which accompanies each product. This warranty ceases to exist if the buyer does not follow the
technical instructions included in official documents given by Olympia Electronics or if the buyer
modifies the goods provided or has any repairs or re-setting done by a third party, unless Olympia
Electronics has fully agreed to them in writing. Products that have been damaged can be returned to
the premises of our company for repair or replacement, as long as the warranty period is valid.
Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge
the buyer depending on the reason of defection. Olympia Electronics reserves the right to charge or
not the buyer the transportation cost.
HEAD OFFICE
72nd km. O.N.R. Thessaloniki-Katerini
P.C. 60300 P.O. Box 06 Eginio Pierias Greece
www.olympia-electronics.gr
Electro-valve 12V DC
Diagram with manual reset and
normally open electro-valve
JMP1
AB
1
LN
~230 V
E.V. 12VDC N.O.
L NC NCNO
-OUT+
921695000_09_009
This manual suits for next models
1
Other olympia electronics Gas Detector manuals
Popular Gas Detector manuals by other brands

Eastern Energy
Eastern Energy 7721 Operation manual

Lanberg
Lanberg SR-1005 user manual

Weatherford
Weatherford SLS Baseline 9000 FID manual

RKI Instruments
RKI Instruments GD-70D Series operating manual

Industrial Scientific
Industrial Scientific TANGO TX2 product manual

GASTRON
GASTRON GTD-1000T Series instruction manual