GENERAL
These luminaires are used in places
where emergency luminaires are needed.
Each luminaire must be permanently
connected to mains power supply. In
normal operation the led strip lights and
the battery is charging. In case of a
ma in s p ow er su pp ly fa il ur e t he
lum in a ir e wi ll lig ht t he led st r ip
automatically in emergency mode. When
the mains power supply is restored the
device turns to normal operation.
OPERATION
Battery Charging
The battery charging is completely
controlled by microprocessor and is
protected from completely discharge and
over charge.
Battery Cut-off
The luminaire enters in this operation
when the mains power supply fails and
battery has lost its energy. During this
operation the luminaire enters the idle
state and battery consumption is
negligible, in order to be protected from
deep discharge.
Manual Test
By pressing the test button briefly (less
than 5 seconds) an emergency operation
test is performed. The white LEDs will be lit
for approx. 3 seconds, the red LED will
flash during this test sequence.
Automatic Operational Test
This test includes all the operations that
provide the manual test and is conducted
automatically every 15 days. In order to be
performed, the mains power supply and the
battery should be connected.
Manual Autonomous Test
By pressing the test button for between 5
and 10 seconds a battery condition test is
performed. This test will last for the stated
duration and can only be performed when
the battery is fully charged (steady green
LED). The white LEDs will be lit and the red
LED will flash during this test sequence.
Automatic Autonomous Test
The Automatic Autonomous Test measures
SELF TESTING MAINTAINED EMERGENCY LUMINAIRIES WITH LEDs
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
VIEWING DISTANCE
EXTERNAL DIMENSIONS (LxHxW)
CONSTRUCTION MATERIALS
TYPICAL WEIGHT
GUARANTEE
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERY (Ni-MH)
CHARGING TIME
INDICATIONS - CONTROLS
BATTERY PROTECTION
MINIMUM AUTONOMOUS DURATION
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
LIGHT SOURCE INTENSITY (Mains/emerg.)
ILLUMINATION SOURCE
923064003_09_002
220-240V AC/50-60Hz
90 min 90 min 90 min180 min 180 min 180 min
435 x 280 x 55 mm 673 x 400 x 55 mm287 x 205 x 55 mm
4.8V/1.2Ah 4.8V/2.4Ah 4.8V/4Ah
4.8V/2Ah4.8V/1.2Ah
7W/7.4VA (PF=0.94) 9.3W/9.8VA (PF=0.94)6W/6.4VA (PF=0.94)
230lm / 300lm
26m 40m 64m
230lm / 123lm 370lm / 300lm 600lm / 500lm
24 h
Charge LED, Lamp fault LED, Battery Fault LED, TEST button
From overcharge and deep discharge
White LEDs
o
5 to 40 C
Up to 95%
3 years (1 year for the battery)
Aluminum, ABS/PC, PC, Plexiglass
IP 44
EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3, EN 1838
1503gr. 1650gr. 2777gr.1396gr.876gr.
TECHNICAL CHARACTERISTICS (for LED MO DULE Specs . s ee page 3)
LLB-26/90 LLB-26/180 LLB-40/180 LLB-64/180
LLB-40/90 LLB-64/90
Thank you for your trust in our products
Olympia Electronics - European manufacturer
Page 1 from 6