Omron F3SP-B1P User manual

*S1 Open: Normal light emission.
Close: Stop light emission.
●Wiring for Auto-reset mode.
●Wiring for Manual reset mode and the EDM function enabled
●Wiring when the EDM is not used.
●Wiring when the EDM is not used.
*S3 If the switch is not necessary,
connect between X1 and H1.
4Functions
Designation
The F3SP-B1P can construct the condition conforming to cat. 4 / PLe or cat.2 / PLc
requested by EN ISO13849-1 with combination as follows:
- Category 4 / PLe: Type F3SN-A□□□□P□□ or F3SH-A09P03 or F3SR-430B□□□□
or F3SJ-A□□□□P□□ or F3SJ-B□□□□P25
- Category 2 / PLc: Type F3SN-B□□□□P□□
Note: Category is not judeged only by the condition above, but is judged by the
condition of the whole control system.
- In order to be cat. 4/ PLe, or cat. 2/ PLc
1.The NC contact from a contactor is required to feed back signal.
(Refer to the application examples. For category 2, it is not mandatory.)
2. PE terminal should be connected to protective earth.
3. In application with long term operation of devices, the F3SP-B1P must have cyclic
operation every 24 hours at least in order to detect failures and a failure
accumulation.
Application examples
5
●Wiring for the Manual reset mode and the EDM function.
5-1 When in combination with the F3SN/F3SH/F3SJ
5-2 When in combination with the F3SR
Specications
●Characteristics
(1) When ready for wiring, the power source should be disconnected rst. Further, at operating
this unit, the terminal cover should be closed correctly in orde to prevent an electrical shock.
(2) Do not wire in case threat of Lightning. otherwise an electric shock may occur.
(3) Do not apply any excessive voltage or current to the input or output circuit the F3SP-B1P.
Doing so may result in damage to the F3SP-B1P or cause are.
(4) Do not apply any variable voltage, otherwise F3SP-B1P may malfunction.
(5) Do not connect any overload to the output circuit, otherwise the F3SP-B1P in operation will
generate excessive heat and the output elements of the F3SP-B1P may short-circuit or re
may result.
(6)The lifetime of F3SP-B1P depends on the conditions of switching of its outputs. Be sure to
conduct its test operation under actual operating conditions in advance and use it within
appropriate switching cycles. Change the F3SP-B1P before expected operation. Over
operation may cause may short-circuit or may malfunction.
(7) Do not operate the F3SP-B1P with ammable or explosive gass. An arc with operation and
the heat of relay will cause a re or an explosion.
(8) Do not disassemble, repair, or modify the F3SP-B1P, otherwise an electric shock may occur or
the F3SP-B1P may malfunction.
(9) Use protective device (Fuse etc) for short-circuit protection and ground fault protection,
otherwise a re may occur or the F3SP-B1P may malfunction.
(10) Be sure to wire correctly.The sensor connector is the same both the emitter and the
receiver.
(11) Do not dismantle, repair, or modify F3SP-B1P. it may lead to loss of its safety functions.
(1) For malfunctions in case that the power supply picks up gradually.
Malfunctions in case that the power supply picks up gradually. In case that the input circuits
close before the power supplies, internal logic may malfunction.
(2) Handling
Do not drop the F3SP-B1P or shock or vibrate the F3SP-B1P excessively. Doing so may result
in damage to the F3SP-B1P or cause F3SP-B1P to malfunction.
(3) For adhesion of solvent
Adhesion of solvent, likely Alcohol,Thinner,Trichloroethane, Gasoline, on the product should
be prohibited. Such solvent cause erasing the marking and being inferior of the parts.
(4)Take appropriate and sufcient countermeasures when installing systems in the following
locations. Inappropriate and insufcient measures may result in malfunction.
1. Locations subject to static electricity or other forms of noise.
2. Locations subject to possible exposure to radioactivity.
3. Locations close to power supplies.
(5) Wiring
1. Use the following to wire the F3SP-B1P.
- Stranded wire (Flexible wire): 0.75 to 1.5mm
2
- Solid wire: 1.0 to 1.5mm
2
2. The F3SP-B1P may malfunction or generate heat.
-Tighten each screw to a torque of 0.78 to 1.18N・m
3. PE is a ground terminal. When machine is grounded at the positive, the PE terminal
should not be grounded.
4. NC terminals do not have any function. Do not wire them.
The following functions of the sensor can be used. Refer to the instruction manual of
the sensor for detailed information.
・Auto reset/Manual reset (Interlock function)
・External device monitoring (EDM)
・External test (Light emission stop function by test input)
・Auxiliary output (PNP transistor output) (*)
*When in combination with the F3SR, "auxiliary output" can not be used.
The F3SP-B1P received the following approvals in combination with the
F3SN/F3SH/F3SR/F3SJ:
・From EU accredited bodyTUV-SUD Product Service GmbH:
- ECType-examination in accordance with the EU Machinery Directive
Approved standards: EN61496-1, CLC/TS 61496-2 (IEC61496-2)
・From theThird Party Assessment Body UL:
- UL Listed to U.S. and Canadian safety standards
Approved standards: IEC61496-1, IEC61496-2,
UL508, CAN/CSA C22.2 No.14, CAN/CSA C22.2 No.8
●Ratings
6
Thank you for purchasing F3SP-B1P Control Unit.
Please read and understand this manual before using the products.
Keep this manual ready to use whenever needed.
Only qualied person trained in professional electrical technique should handle F3SP-B1P.
Since this instruction sheet only provides general infomation, refer to the instruction
manual of the sensor.
Please consult your OMRON representative if you have any questions or comments.
Make sure that information written in this document are delivered to the nal user of the product.
USER'S MANUAL
Type F3SP-B1P
Jul. 2011
English
WARNING
Precaution for Safe Use
Indicates a potentially hazardous situation which, if not
avoided, will result in minor or moderate injury, or may
result in serious injury or death.
Additionally there may be signicant property damage.
Meanings of Signal Words
The following signal words are used in this manual.
Meaning of Alert Symbols
The following alert symbols are used in this manual.
Serious injury may possibly occur due to breakdown of safety outputs.
Do not connect loads beyond the rated value tothe safety outputs.
Serious injury may possibly occur due to loss of required safety functions.
Wire F3SP-B1P properly so that supply voltages or voltages for loads do
NOT touch the safety inputs accidentally or unintentionally.
WARNING
Alert Statements
Control Unit
F
or
F3SN-A□□□□P□□, F3SN-B□□P□□, F3SH-A09P03,
F3SR-430B□□□□, F3SJ-A□□□□P□□, F3SJ-B□□□□P25
Indicates prohibited actions Indicates mandatory actions
Precautions for Safe Use
Precautions for Correct Use
●Life expectancy
Electrical endurance
Mechanical endurance
100,000 operations MIN. Rated load
Switching frequency 1,800 operations/h
5,000,000 operations MIN.
Switching frequency 18,000 operations/h
●Isolation specication
Insulation resistance
Dielectric strength
Between different poles of output
Between different poles of output
Between inputs and outputs
Between inputs and outputs
100Mohm MIN.
(by 500VDC Megger)
2,500VAC 1min.
7Failure detection
Type F3SP-B1P can detect the failure for the safety of internal circuit, parts condition and
external wiring.
K1 and K2 LED
do not turn on. Failures of the parts
of the internal circuits. Replace with a new product.
Failures involving the wiring
of External input. (input line)
Failure indication
by LED Failure condition
K1 or K2 LED
does not turn on.
Power LED
does not turn on.
Checking points and measures
to take
Failures involving the wiring
of External input. (input line)
Failures of the parts of the
External devices. (Contactor etc)
Failures of the parts
of the internal circuits.
Replace with a new External devices.
(Contactor etc)
Failures of the parts
of the internal circuits.
Replace with a new product.
Supply voltage outside
the rated value. Check the supply voltage to
Expansion.
Failures involving the wiring
of External input. (output line)
Replace with a new product.
Check the wiring to External input.
(input line)
Check the wiring to External input.
(output line)
Check the wiring to External input.
(input line)
Failures of the parts of the
Protective device. (Fuse etc) Replace with a new Protective device.
(Fuse etc)
All LED turn on.
but the safety
output doesn't on.
Failures involving the wiring
of External input.
(input line / power line)
Check the wiring to External input.
(input line/power line)
Failures of the Sensor.
Failures of the Sensor. Check the Sensor.
Check the Sensor.
S1: External test switch
S2: Interlock / Lockout reset switch
S3: Lockout reset switch
KM1,KM2: Magnet contactor
M: 3-phase motor
S1: External test/Lockout reset switch
S2: Interlock reset switch
KM1,KM2: Magnet contactor
M: 3-phase motor
E1: 24 VDC power supply (S82K)
1.7W MAX. (Exclude sensor power)
24VDC
25VAC60VDC
5A
AC: 1250VADC: 150W
AC: 125VADC: 150W
TYPE F3SP-B1P
Rated power consumption
Rated supply voltage
Operating voltage range
Input
Rated load
Rated carry current
Max. switching voltage
Max. switching capacity
Output
For North
America
Rated load
Rated carry current
Max. switching voltage
Max. switching capacity
For Europe
5A
250VAC 5A cosφ=1 30VDC 5A L/R=0ms
250VAC 125VDC
-15% to +10% of rated supply voltage
25VAC 5A cosφ=1 30VDC 5A L/R=0ms
OMRON shall not be responsible for conformity with any standards, codes, or
regulations that apply to the combination of the products in the customer's
application or use of the product.
Take all necessary steps to determine the suitability of the product for the
systems, machines, and equipment with which it will be used. Know and
observe all prohibitions of use applicable to this product.
NEVER USETHE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK
TO LIFE OR PROPERTY WITHOUT ENSURING THATTHE SYSTEM AS A WHOLE
HAS BEEN DESIGNEDTO ADDRESSTHE RISKS, ANDTHATTHE OMRON
PRODUCT IS PROPERLY RATED AND INSTALLED FORTHE INTENDED USE
WITHINTHE OVERALL EQUIPMENT OR SYSTEM.
Suitability for Use
OMRON EUROPE B.V. (Importer in EU)
Wegalaan 67-69, NL-2132 JD Hoofddorp
THE NETHERLANDS
PHONE 31-2356-81-300 FAX 31-2356-81-388
OMRON SCIENTIFICTECHNOLOGIES INC.
6550 Dumbarton Circle, Fremont CA 94555-3605
U.S.A
PHONE 1-510-608-3400 FAX 1-510-744-1442
OMRON ASIA PACIFIC PTE. LTD.
438A Alexandra Road # 05-05/08,
Alexandra Technopark Singapore 119967
SINGAPORE
PHONE 65-6-835-3011 FAX 65-6-835-2711
Note: Specications subject to change without notice.
OMRON Corporation (Manufacturer)
Shiokoji Horikawa, Shimogyo-ku, Kyoto, 600-8530
JAPAN
Original instructions
EU Declaration of Conformity
Standards
OMRON declares that Type F3SP-B1P is in conformity with the requirements of
the following EU Directives:
- EMC Directive: 2004/108/EC
- Machinery Directive: 2006/42/EC
OMRON (CHINA) CO., LTD.
Room 2211, Bank of ChinaTower, 200 Yin Cheng Zhong Road,
PuDong New Area, Shanghai, 200120, China
PHONE 86-21-5037-2222 / FAX 86-21-5037-2200
●Protection class
Operation time 100ms MAX.
(exclude sensor response time)
Destruction: 300 m/s2
Malfunction: 100 m/s2
Ambient humidity
Ambient temperature
Shock resistance
Vibration resistance
Response time
-10 to 55℃
10ms MAX.
(exclude sensor response time)
35 to 85%RH
10 to 55Hz 0.35mm single amplitude
(0.7mm double amplitude)
IP20
IP40
3
2
Enclosure
Terminals
●Pollution degree
External
Internal
(6) Mounting multiple units
When mounting multiple units close to each other, the rated current will be 3A.
Do not apply a current higher than 3A.
(7) Operating and Storage Environment
Do not operate or store the F3SP-B1P under the following conditions.
Doing so may result in damage to the F3SP-B1P or cause the F3SP-B1P to malfunction.
1.The places with direct sunlight.
2.The places with ambient temperature ranges not within -25 to 55℃.
3.The places with rapid temperature changes resulting in condensation or relative humidity
ranges not within 35 to 85%RH.
4.The places with atmospheric pressure out of the range 86 to 106kpa.
5.The places with corrosive or inammable gas.
6.The places with water, oil, or chemical sprayed on the F3SP-B1P.
7. The places with vibration or shock affecting the F3SP-B1P.
8.The places with atmosphere containing dusts, saline or metal powder.
(8) DC power supply units
In order to conform to IEC61496-1 and UL508, DC power supply unit must satisfy all the
conditions mentioned in the instruction manual the sensor.
(9) Installation
1. Cabinet of F3SP-B1P should meet IP54 protection.
2. The F3SP-B1P is exclusively for F3SN-A□□□□P□□, F3SN-B□□□□P□□,
F3SH-A09P03, F3SR-430B□□□□, F3SJ-A□□□□P□□, F3SJ-B□□□□P25 series.
3.The following functions are set with two short pieces when delivered. Change wirings
depending on necessary functions.
- H1-X1 short: Auto reset mode.
-T31-T32 short: EDM function is inactive.

*
These combinations of wiring and function are for the use with the F3SN/F3SH or F3SJ.
When in combination with the F3SR, refer to Section 5.
(10) For feedback purpose use devices with contacts capable of switching micro loads of
24VDC, 5mA.
(11) This is a class A product. In residential areas it may cause radio interference, in which case
the user may be required to take adequate measures to reduce interference.
KM1
24VDC
KM1 KM2
KM2
S2
S1
PLC
EMITTER
RECEIVER
K1 K2
K1
K2
A1 H1 L1 J1 H1 X1
A2 PE
T31 T32
P1
41
33
23
13
42
34
24
14
INTERLOCK
TEST
RESET
AUXILIARY
EDM
OSSD2
OSSD1
S3
S1
H1 L1 J1 H1 X1
T31 T32
INTERLOCK TEST
RESET
KM1
M
KM2
0631530-0I
●Wiring when the EDM is used.
●Wiring for Auto-reset mode.
●Wiring for Auto-reset mode.
S1
S2
A1 H1 L1 J1 H1 X1 P1 13 23 33 41
KM1
KM2
Function
select input TEST RESET
Operating
range
select input
OSSD 1 OSSD 2
K1
K2
K1 K2
A2 PE T31 T32
EDM
14 24 34 42
KM1
KM2
KM1
KM2
F3SP-B1P
E1
24VDC
0V
M
Emitter
Receiver
Function
select input TEST
RESET
S1
H1 L1 J1 H1 X1
T31 T32
EDM
H1
Function
select input TEST RESET
S1
L1 J1 H1 X1
T31 T32
EDM
H1
1
External Physical Dimensions
2
●Unit
For safety category and PL
3
43
63
76 MAX.
9
7×5=35
13 MAX.
45 MAX.
R2.3 111 MAX.
5
5.6
9
4.6 dia.
35±0.3
5.9
24-M3
Emitter
Receiver
10.5 91
84±0.3
Two,4.2 dia. or M4
Mounting holes
Sensor connectors For Receiver(Black)
For Emitter(Gray)
Output terminals
Power input
terminal
Output terminals
Power input
terminal
Earth terminal
I/O terminals
Input power
indicator
Relay operation
indicators
I/O terminal
I/O terminals
I/O terminals
Type F3SP-B1P
13 23 33 41 H1 J1
NC NC L1 H1 X1 A1
14
13
24
23
34
33
42
41
P134 422414
A2
PE
T32T31
NC
NC
NC
PWR
K1
K2
No.
13 23 33 41
14 24 34 42
T31 T32
A1X1H1
H1 J1
L1NC NC
PENC NC A2
P1NC
24 VDC
SAFETY LIGHT CURTAIN
CONTROL UNIT
F3SP-B1P
●Connector Pin
No.
Signal Name
Receiver
1
2
4
5
6
7
3
RS-485 (A)
Auxiliary output
(* Operating rangeselect input)
OSSD 1
+24V
OSSD 2
EDM input
*Names used when connecting with the F3SR
0V
RS-485(B)
NC
RS-485(B)
RS-485(A)
Reset input
Test input
+24V
Interlock selection input
(* Function select input)
Emitter
0V
8
1
2
7
6
5
4
3
8
KM1
KM2
●オートリセットモード ●外部リレーモニタ機 能:有効
●オートリセットモード ●外部リレーモニタ機 能:無効
各部の名称
1
接続例
外形寸法
2
定格・性能
6
●ユニット
●コネクタ
DC1.7W以下 (センサの消費電力は含まず)
DC24V
100ms以下 (センサの応答時間は含まず)
出力端子
電源入力端子
出力端子
電源入力端子
アース端子
電源表示
動作表示
外部入力端子
外部入力端子
外部入力端子
センサ 用コネクタ 手 前:受光側(黒色:RECEIVER)
     奥:投光側(灰色:EMITTER)
外部入力端子
13 23 33 41 H1 J1
NC NC L1 H1 X1 A1
14
13
24
23
34
33
42
41
P134 422414
A2
PE
T32T31
NC
NC
NC
PWR
K1
K2
No.
13 23 33 41
14 24 34 42
T31 T32
A1X1H1
H1 J1
L1NC NC
PENC NC A2
P1NC
形F3SP-B1P
1
2
7
6
5
4
3
8
S1:外部テストスイッチ
S2:インターロック/ロックアウトリセットスイッチ
S3:ロックアウトリセットスイッチ
KM1,KM2:マグネットコンタクタ
M:3相モータ
機能
下記のセンサの機能を使用可能です。各機能の詳細は、センサの取扱説明書を参照下さい。
・オートリセット/マニュアルリセット(インターロック機能)
・外部リレーモニタ
・外部テスト(テスト入力による投光停止機能)
・補助出力(PNPトランジスタ出 力 )
(*)
 *形F3SRと組み合わせる場合、補助出力は使用できません。
*
S1:開放時に通常動作、短絡時に投光停止
5−1 形F3SN/形F3SH/形F3SJと組み合わせる場合の接続例
5−2 形F3SRと組み合わせる場合の接続例
●マニュアルリセットモード:外部リレーモニタ機能使用時
●オートリセットモード ●外部リレーモニタ機 能:無効
●外部リレーモニタ有効、マニュアルリセットで使用する場合
*
S3:スイッチが不要な場合、X 1とH 1を短 絡
定格通電電流
接点電圧の最大値
定格負荷 AC250V5A抵抗負荷
DC30V5A抵抗負荷
AC250V DC125V
5A
北米
向け
EU
向け 定格通電電流
接点電圧の最大値
定格負荷
AC25V DC60V
5A
開閉容量の最大値 AC:1250VA DC:150W
開閉容量の最大値 AC:125VA DC:150W
10〜55〜10Hz
片振幅0.35mm(複振幅0.7mm)
10ms以下 (センサの応答時間は含まず)
0631530-0I
●FAXによるお問い合わせは右記をご利用ください 。
 カスタマサポートセンタ お客様相談室 FAX055-982-5051
●その他のお問い合わせ先
 納期・価格・修理・サンプル・承認図は貴社のお取引先、または貴社担当オムロン営業員にご相談ください 。
●お問い合わせ先
カスタマサポートセンタ
携帯電話・PHSなどではご利用いただけませんので、その場合は下記電話番号へおかけください 。
電話055-982-5015(通話料がかかります )
【技術のお問い合わせ時間】
■営業時間:8:00〜21:00 ■営業日:365日
■上記フリーコール以外のFAシステム機器の技術窓口:
電話055-977-6389(通話料がかかります )
【営業のお問い合わせ時間】
■営業時間:9:00〜12:00/13:00〜17:30(土・日・祝祭日は休業)
■営業日:土・日・祝祭日/春期・夏期・年末年始休暇を除く
インダストリア ルオートメーションビジネスカンパニー
ご使用に際してのご承諾事項
本製品は機械安全用途に使用されるコンポーネント商品ですが、使い方によっては要求される安全性が確保
できない 場 合 があります 。セーフティコンポーネント総合カタログ巻頭の「警告」に記載されている「①リスクアセ
スメントの実施②安全方策③安全機器の役割④安全機器の設置⑤法令の遵守⑥使用上の注意事項⑦装
置・設備移転・譲渡」を遵守の上ご使用ください 。
a)屋外の用途、潜在的な化学的汚染あるいは電気的妨害を被る用途またはカタログ、取扱説明書等
 に記載のない条件や環境での使用
b)原子力制御設備、焼却設備、鉄道・航空・車両設備、医用機械、娯楽機械、および 行 政 機 関 や個 別 業 界
 の規制に従う設備
c)人命や財産に危害が及びうるシ ステ ム・機械・装置
d)ガス、水道、電気の供給システムや24時間連続運転システムなど高い信頼性が必要な設備
e)その他、上記a)〜d)に準ずる、高度な信頼性が必要とされる 用 途
*上記は適合用途の条件の一部です。当社のベスト、総合カタログ、データシート等最新版のカタログ、
 仕様書記載の保証・免責事項の内容をよく読 ん でご 使 用ください 。
形F3SP-B1P
はじめ に
このたびは、形F3SP-B1Pコントロー ル ユニットを お 買 い 上 げ い た だきまして、まことにありがとうござ
います。この取扱説明書では、形F3SP-B1Pを使用する上で、必要な機能、性能、使用方法などの
情報を記載しています。
形F3SP-B1Pをご使用に際して下記のことを守ってください 。
・形F3SP-B1Pは電気の知識を有する専門家が扱ってください 。
・この取扱説明書をよくお読みになり、十分にご理解のうえ、正しくご使用ください 。
・この取扱説明書はいつでも参照できるよう大切に保管ください 。
・取扱説明書では主な注意事項のみを記載しています。「センサ」の取扱説明書をあわせてご
 覧ください 。
コントロール ユ ニット
形F3SN-A□□□□P□□ 形F3SN-B□□□□P□□ 形F3SH-A09P03
形F3SR-430B□□□□ 形F3SJ-A□□□□P□□ 形F3SJ-B□□□□P25
故障検出について
故障表示 故障内容
K1,K2の
動作表示が点灯しない
外部接続機器
(コンタクタ等)の故障
電源表示が点灯しない
製品を交換してください 。
K1,K2の
動作表示の
どちらか が 点 灯しない
外部接続保護素子
(ヒューズ等 )の故障
7
内部回路の故障
電源電圧の不足
外部入力配線
(入力部)の異常
全表示が点灯している
が安全出力が出ない
外部入力配線
(出力部)の異常
外部入力配線
(入力部)の異常
内部回路の故障
内部回路の故障 製品を交換してください 。
製品を交換してください 。
外部入力配線(入力部)を確認してください 。
外部入力配線(入力部)を確認してください 。
外部入力配線(出力部)を確認してください 。
外部接続の保護素子(ヒューズ等)を
交換してください 。
外部接続機器(コンタクタ等)を交換してください 。
電源電圧を確認してください 。
対策
形F3SP-B1Pはリセットする際 、内部回路、部品、外部接続などの安全に対する故障検出が可能です。
外部入力配線
(入力部)の異常
外部入力配線(入力部および電源部)を
確認してください 。
安全カテゴリとPLについて
形F3SP-B1Pは、下記のセンサーとの組み合わせで、欧州規格EN ISO 13849-1より要求される
安全カテゴリ4/PLeまたは安全カテゴリ2/PLcのシステムに適用することができます。
 -カテゴリ4/PLe:
形F3SN-A□□□□P□□、形F3SH-A09P03、形F3SR-430B□□□□、
 形F3SJ-A□□□□P□□、形F3SJ-B□□□□P25との組合せ
 -カテゴリ2/PLc:形F3SN-B□□□□P□□との組み合わせ
注.安全カテゴリは上記条件だけではなく、安全制御システム全体で判定されます。
・安全カテゴリ4/PLe、安全カテゴリ2/PLc適用のために
 1.コンタクタのb接点の信号をT31,T32間に入力してください 。
 (回路例参照。カテゴリ2回路の場合、必須ではありません。)
 2.PE端子は必ずアースへ接続してください 。
 3.長期に渡り稼動される場合には、確実な故障検知を行うために、24時 間 に1回 の 割り合
いで、F3SP-B1Pを動作確認いただくことを推奨します。
3
AC25V5A抵抗負荷
DC30V5A抵抗負荷
インターロック
選択 テスト
リセット
(1)電源徐昇時の故障検知について
立ち上がり時間が長い電源でのご使用時に、入力が閉路のまま電源が投入されますと、内部回路
が電源電圧異常を検知し、製品は動作しません。製品には、電源電圧が定格電圧に達してから印
加してください 。
(2)取り扱いについて
製品を落下させたり、異常な振動衝撃を加えないでください 。故障や誤動作の原因となります 。
(3)溶剤の付着について
製品にアルコール、シンナー 、トリクロロエタン 、ガソリンなどの溶剤が付着しないようにしてください 。
溶剤により、マーキングの 消えや、部品の劣化を引き起こす原因となります 。
(4)次のような場所で使用する際は、遮蔽対策を十分に行ってください 。
1.静電気などによるノイズが発生する場所
2.放射能により被爆する恐れのある場所
3.電源線が近くを通る場所
(5)配線について
1.配線用電線サイズは下記のものをご使用ください 。
   ・ヨリ線(flexiblewire):0.75〜1.5mm2
   ・単線(steelwire):1.0〜1.5mm2
  2.端子ネジは誤動作、発熱などの原因にならないように 、規定のトルクで締め付けてください 。
   ・端子ネジ締め付けトルク:0.78〜1.18N・m
  3.PEはアース端子になります 。(+)側をアースされた設備には使用できません。
  4.NC端子は機能を有していませんので、配線しないでください 。
使用上の注意
(1)配線をおこなう場合には必ず電源を切った状態でおこなってください 。また通電中はカバーを取り付
けた状態とし、端子部には触れないで下さい。感電の恐れがあります 。
(2)落雷の恐れがある場合には配線作業を行わないでください 。感電の恐れがあります 。
(3)入力端子には規定の電圧を正しく印 加してください 。誤った電圧を印加されますと規定の機能が発揮
されず、製品自体の破損・焼損の原因になります 。
(4)電源電圧は規定電圧でご使用ください 。リップルの大きな電源や、断続的に異常電圧を発生する電源
での使用は行なわないでください 。
(5)開閉容量(接点電圧、接点電流)などの接点定格値を越える負荷に対しては、絶対に使用しないでくだ
さい。絶縁不良、接点溶着、接触不良など、規定の性能を損なうば かりでなく、破損、焼損の原因となり
ます。
(6)耐久性は開閉条件により大きく異 なります 。使用にあたっては必ず実使用条件にて実機確認をおこな
い、性能上問題のない開閉回数内にてご使用ください 。また 、性能が劣化した状態で引き続きご使用さ
れますと、最終的には回路間の絶縁破壊や、製品自体の焼損などの原因となります 。
(7)引火性ガス・爆発ガスなどの雰囲気では使用しないでください 。開閉にともなうアークやリレーの 発 熱
などにより、発火または爆発を引き起こす原因となります 。
(8) 落 下させたり内 部を分 解した 製 品 は 、使用しないでください 。特性を満足できないばかりでなく、破損、
焼損の原因となります 。
(9)負荷の短絡、地絡防護のため、必要に応じ適切な保護素子(ヒューズなど)を接続ください 。保護できな
い場合には、破損または焼損の可能性があります 。
(10)センサのコネクタは投光器・受光器共に同形状となっています。投/受光器をよくお確かめの上、接続
ください 。
(11)分解、修理、改造しないでください 。本来の安全機能が失われ危険です。
安全上の要点
Japanese
信号
No.
信号名称
受光器
1
2
4
5
6
7
3
RS-485(A)
補助出力
(検出距離選択入力)(*)
制御出力1
+24V
制御出力2
外部リレーモニタ入力
*形F3SRと組み合わせる場合は( )の表記となります
0V
RS-485(B)
NC
RS-485(B)
RS-485(A)
リセット入力
テスト入力
+24V
インターロック選択入力
(機能選択入力)(*)
投光器
0V
8
43
63
76以下
9
7×5=35
13以下
45以下 R2.3 111以下
5
5.6
9
φ4.6
35±0.3
5.9
24-M3
投光側(EMITTER)
受光側(RECEIVER)
10.5 91
84±0.3
2-φ4.2
またはM4
取付穴加工寸法
入力
出力
定格消費電力
●定格
●性能
動作時間
耐久300m/s
2誤動作100m/s
2
使用周囲湿度
使用周囲温度
耐衝撃
耐振動
応答時間
35〜85%RH
-25〜+55℃
電源電圧
許容電圧変動範囲 電源電圧の-15%+10%
端子部
ケース
●保護構造
IP20
IP40
●耐久性
電気的耐久性
機械的耐久性
10万回以上定格負荷開閉頻度:1,800回/h
500万回以上開閉頻度:18,000回/h
入出力間
出力異極間
入出力間
出力異極間
絶縁抵抗
●絶縁性能
耐電圧
100MΩ以上 DC500Vメガ
AC2500V1min.
●汚染度
外部 3
内部 2
形F3S-B1P
センサ の 異 常 センサを確 認してください 。
センサを確 認してください 。
センサ の 異 常
形F3SP-B1Pは形F3SN/形F3SH/形F3SR/形F3SJとの組み合わせで下記の認証を受けて
います。
・EU公認機関TUV-SUDProductServiceGmbHより
-機械指令に基づくEC形式試験
 適合規格:EN61496-1,CLC/TS61496-2(IEC61496-2)
・第三者評価機関ULより
-米国およびカナダ安全規格に対するリスティング認 定
 適合規格:IEC61496-1、IEC61496-2、
      UL508、CAN/CSAC22.2No.14,CAN/CSAC22.2No.8
24 VDC
SAFETY LIGHT CURTAIN
CONTROL UNIT
F3SP-B1P
S3
S1
4
5
H1 L1 J1 H1 X1
T31 T32
KM1
DC24V
KM1 KM2
KM2
S2
S1
PLC
投光器
受光器
K1 K2
K1
K2
A1 H1 L1 J1 H1 X1
A2 PE
T31 T32
P1
41
33
23
13
42
34
24
14
インターロック
選択 テスト
リセット
補助出力
外部リレー
モニタ
制御出力2
制御出力1
(6)多数個取付けについて
 密着取付する場合は、定格通電電流は、3Aとなります 。3A以下でご使用ください 。
(7)保管・設置場所について
  下記の場所には故障や誤動作の原因となりますので設置をしないでください 。
   1.直接日光が当たる場所。
   2.周囲温度が-25〜55℃の範囲を越える場所。
   3.相対湿度が35〜85%RHの範囲を越える場所、温度変化が急激で結露するような場所。 
   4.周囲気圧が86〜106kPaの範囲を越える場所。
   5.腐食性ガスや可燃性ガスのある場所。
   6.本体に定格値以上の振動や衝撃が伝わる場所。
   7.水、油、薬品などの飛沫がある場所。
   8.塵埃、塩分、鉄粉の多い場所。
(8)DC電源ユニットについて
  IEC61496-1及びUL508を満たすために、また感電保護のために、電源と負荷に関してはセン
  サ取扱説明書に記載の項目を満たすものをご使用ください 。
(9)取付けについて
  1.防塵、防水のため、制御ボックスは、IP54以上の保護構造を推奨します。
  2.本製品は、下記のセンサ専用のコントロー ル ユニットです 。
    -形F3SN-A□□□□P□□シリーズ -形F3SR-430B□□□□シリーズ
    -形F3SN-B□□□□P□□シリーズ -形F3SJ-A□□□□P□□シリーズ
    -形F3SH-A09P03シリーズ -形F3SJ-B□□□□P25シリーズ
  3.出荷時は、2本のショートバーにより下記の状態となっています。必要な機能に応じて配線
   を変更してください 。
   ・H1-X1ショート:オートリセットモード
   ・T31-T32ショート:外部モニタキャンセル
 *上 記 の配 線と機 能 の 組み合 わせは 、形F3SN/F3SH、F3SJとの接続で適用されます。
  F3SRとの接続は5項を参照ください 。
(10)フィードバック用の接点は微小負荷(DC24V、5mA)に適用できるものを使用してください 。
(11)この商品は「classA」(工業環境商品)です。住宅環境でご利用されると、電波妨害の原因
となる可能性があります 。その場合には電波妨害に対する適切な対策が必要となります 。
安全上のご注意
警 告
正しい取扱いをしなければ、この危険のために、軽傷・中程度の傷
害を負ったり、万一の場合には重傷や死亡に至る恐れがあります。
また、同様に重大な物的損害を受ける恐れがあります。
●禁止図記号の一般
特定しない一般的な禁止の通告。
●強制図記号の一般
特定しない一般的な使用者の行為を指示する図記号。
安全機能が損なわれ、重度の人身傷害が万一の場合起こる恐れがあります 。
安全出力が供給電源および負荷電源に短絡しないように 、適切に配線してください 。
出力が故障し、重度の人身傷害が万一の場合起こる恐れがあります 。
安全出力の定格値を超える負荷に対しては、絶対に使用しないでください 。
EU適合宣言
オムロンは形F3SP-B1Pが以下のEU指令要求に適合していることを宣 言します。
 -EMC指令2004/108/EC
 -機械指令2006/42/EC
規格
●警告表示の意味
●図記号の意味
●警告表示
KM1
KM2
KM1
M
KM2
S1:外部テスト/ロックアウトリセットスイッチ
S2:インターロックリセットスイッチ
KM1, KM2:マグネット・コンタクタ
M:3相モータ
E1:DC24V電源(形S82K)
S1
S2
A1 H1 L1 J1 H1 X1 P1 13 23 33 41
KM1
KM2
機能選択入力 テストリセット検出距離
選択入力
制御出力1 制御出力2
K1
K2
K1 K2
A2 PE T31 T32
外部リレーモニタ
14 24 34 42
KM1
KM2
KM1
KM2
形F3SP-B1P
E1
+DC24V
0V
M
投光器
受光器
機能選択
入力
テスト
リセット
S1
H1 L1 J1 H1 X1
T31 T32
外部リレーモニタ
H1
機能選択
入力 テストリセット
S1
L1 J1 H1 X1
T31 T32
外部リレーモニタ
H1

Other Omron Control Unit manuals

Omron GX-JC06 User manual

Omron

Omron GX-JC06 User manual

Omron CS1W-NC271 Quick guide

Omron

Omron CS1W-NC271 Quick guide

Omron 3G3FV-PDI16H2 User manual

Omron

Omron 3G3FV-PDI16H2 User manual

Omron SYSMAC CVM1-PRO01-V1 User manual

Omron

Omron SYSMAC CVM1-PRO01-V1 User manual

Omron CS1W-CLK12-V1 User manual

Omron

Omron CS1W-CLK12-V1 User manual

Omron C500-SNT31-V4 User manual

Omron

Omron C500-SNT31-V4 User manual

Omron SYSMAC C200H-NC112 User manual

Omron

Omron SYSMAC C200H-NC112 User manual

Omron C200H-MC221 - User manual

Omron

Omron C200H-MC221 - User manual

Omron SYSMAC C200H-PID01 User manual

Omron

Omron SYSMAC C200H-PID01 User manual

Omron CS1W-MC221 - User manual

Omron

Omron CS1W-MC221 - User manual

Omron CS1W-NC113 - REV 02-2008 User manual

Omron

Omron CS1W-NC113 - REV 02-2008 User manual

Omron CS1W-DRM21 User manual

Omron

Omron CS1W-DRM21 User manual

Omron NX Series User manual

Omron

Omron NX Series User manual

Omron SRM1-C01-V2 User manual

Omron

Omron SRM1-C01-V2 User manual

Omron CS1W-MC421-V1 User manual

Omron

Omron CS1W-MC421-V1 User manual

Omron NX Series User manual

Omron

Omron NX Series User manual

Omron 3G3AX-DI User manual

Omron

Omron 3G3AX-DI User manual

Omron CS1W-LC001 User manual

Omron

Omron CS1W-LC001 User manual

Omron DRT1-DA02 User manual

Omron

Omron DRT1-DA02 User manual

Omron NX Series User manual

Omron

Omron NX Series User manual

Omron EJ1 EtherCAT User manual

Omron

Omron EJ1 EtherCAT User manual

Omron SYSMAC CJ1W-NC113 User manual

Omron

Omron SYSMAC CJ1W-NC113 User manual

Omron CQM1-SRM21-V1 User manual

Omron

Omron CQM1-SRM21-V1 User manual

Omron C200H-MC221 - User manual

Omron

Omron C200H-MC221 - User manual

Popular Control Unit manuals by other brands

Puls MiniLine MLY-Series manual

Puls

Puls MiniLine MLY-Series manual

Epson R4CB56 user guide

Epson

Epson R4CB56 user guide

ProSoft Technology inRAx MVI46-PDPMV1 user manual

ProSoft Technology

ProSoft Technology inRAx MVI46-PDPMV1 user manual

Crane Dominator PRO Z4000 Series Installation, operating and maintenance instructions

Crane

Crane Dominator PRO Z4000 Series Installation, operating and maintenance instructions

Mosaic URC 9950 user guide

Mosaic

Mosaic URC 9950 user guide

Inta ZERO001 Installation and maintenance instructions

Inta

Inta ZERO001 Installation and maintenance instructions

B&R 8BVI0014HWD0.000-1 datasheet

B&R

B&R 8BVI0014HWD0.000-1 datasheet

aci DSIM-MV installation guide

aci

aci DSIM-MV installation guide

IBR IMB-im2 instruction manual

IBR

IBR IMB-im2 instruction manual

TLV COSPECT M-COS-3 instruction manual

TLV

TLV COSPECT M-COS-3 instruction manual

Moxa Technologies WAPN008 user manual

Moxa Technologies

Moxa Technologies WAPN008 user manual

Meccanica Fadini Elpro 980 manual

Meccanica Fadini

Meccanica Fadini Elpro 980 manual

ABB REF542plus Operator's manual

ABB

ABB REF542plus Operator's manual

Heinzmann PANDAROS II manual

Heinzmann

Heinzmann PANDAROS II manual

Miller-Leaman THOMPSON PDA owner's manual

Miller-Leaman

Miller-Leaman THOMPSON PDA owner's manual

BENDIX ATR-2 ANTILOCK TRACTION VALVE Service data sheet

BENDIX

BENDIX ATR-2 ANTILOCK TRACTION VALVE Service data sheet

Pro-Log M980 user manual

Pro-Log

Pro-Log M980 user manual

Raspberry Pi 52PI-RPI-RTC user manual

Raspberry Pi

Raspberry Pi 52PI-RPI-RTC user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.