E5KE5K
Specifications
RATINGS
Model number E5
K Standard E5
K 24V AC/DC
Supply voltage 100--240VAC, 50/60 Hz 24V AC/DC,
50/60Hz
Operating voltage range 85% to 110% of rated supply voltage 85% to 110% of rated supply voltage
Power consumption E5AK 16 VA 9VA, 6W
E5EK 15 VA 9VA, 6W
E5CK 10 VA (at 100 VAC)
14 VA (at 240 VAC) 6VA, 3.5W
Input Thermocouple K, J, T, E, L, U, N, R, S, B, W, PL
Platinum resistance
thermometer (RTD) JPt100, Pt100
Current input 4to20mA,0to20mA
Voltage input 1to5V,0to5V,0to10V
Mean Time Between Failure 15.4 years (135,000 hours
Control output (See Note 1.) Relay SPST, 250 VAC, 3 A (resistive load)
Mechanical life expectancy: 10,000,000 operations min.
Electrical life expectancy: 100,000 operations min.
Voltage
NPN 20 mA at 12/24 VDC (with short-circuit protection)
(Pulse) PNP 20 mA at 24 VDC (with short-circuit protection)
Linear voltage 0to10
VDC Permissible load impedance: 1 kΩmin.
Resolution: Approximately 2600 steps
Linear current 4to20
mA Permissible load impedance: 500 Ωmax.
Resolution: Approximately 2600 steps
0to20
mA Permissible load impedance: 500 Ωmax.
Resolution: Approximately 2600 steps
Auxiliary output SPST-NO E5AK 3 A at 250 VAC (resistive load)
E5EK 3 A at 250 VAC (resistive load)
E5CK 1A at 250 VAC (resistive load)
Control method (See Note 2.) ON/OFF, Advanced PID Control (with auto-tuning) or Self-tuning
Setting method Digital setting using front panel keys or communications features
Indication method -- 7-seg. digital display and LEDs E5AK: PV = 15 mm, SP = 10.5 mm
E5EK: PV = 14 mm, SP = 9.5 mm
E5CK: PV = 12 mm, SP = 8 mm
Potentiometer (Valve Positioning)
(for E5AK and E5EK only) 100 Ωto 2.5 kΩ
Event input Contact input ON 1k
Ωmax.
OFF 100 kΩmin.
No-contact
ON residual voltage: 1.5 V max.
input OFF leakage current: 0.1 mA max.
Transmission output 4 to 20 mA, permissible load impedance: 600 Ωmax.,
resolution: Approximately 2600 steps
Remote SP input (for E5AK and E5EK only) Current
input 4 to 20 mA (Input impedance: 150 Ω)
Current Transformer input (for E5AK and E5EK only) Connect only an Omron Current Transformer (E54-CT1 or E54-CT3)
Other functions Standard Manual output, heating/cooling control, SP limiter, loop burnout alarm, SP
ramp, MV limiter, MV change rate limiter, input digital filter, input shift,
run/stop, protect functions
Option Multiple SP, run/stop selection, transfer output functions, auto/manual
Communications (RS-232C, RS-422, or RS-485), Loop Break Alarm, and
Transfer Output.
Standards UL File No.: E68481
CSA File No.: LR59623
CE File No.: EN50081-2; EN50082-2; IEC 1010-1
Note: 1. All control outputs are insulated from the input circuit.
2. Fuzzy self-tuning is available only when using the Digital Controller in standard control operation with temperature input.