Omron H7CX-N - User manual

1
New Product
Multifunction Counter/Tachometer
H7CX-@-N
Ultra-compact Counter Provides More
Complete Functionality.
Basic Features
• Short body with depth of only 59 mm (for 12 to 24-VDC Models with Screw
Terminals).*1
• Better readability with character height of 12 mm on 4-digit models and 10 mm
on 6-digit models.
• The present value display characters can be switched between red, green, and
orange.*2
Safety and Reliability
• New set value limit and counter functions have been added.
Other Features
• Front Panel can be changed to white or light gray.*3
• Models with two independent tachometer inputs have been added to the series.
*1.For 100 to 240-VAC Models with Screw Terminals: 78 mm, Models with Sockets: 63.7 mm (case dimension).
*2.The H7CX-A11 and H7CX-R11 have only red characters.
*3.The Front Panel can be replaced with an optional Front Panel (except for Tachometer-only Models).
Features
Basic Features
Ultra Short Body
The body depth has been greatly reduced. Helps in making thinner
control panels.
Easier to Read
For better readability, the character height for the present value
display is 12 mm on models with 4 digits, the largest class in the
industry. The wide viewing angle and brightness provide excellent
visibility. The number of display segments has also been increased to
make settings easier to understand, and the present value display
can be switched between red, green, and orange so that output status
can be seen from a distance.
Note: The display color can be switched on all models except for the
H7CX-A11 and H7CX-R11.
The Easiest Operation
Operation is simplified by the
Up/Down Key for each digit
on 4-digit models and Up
Key for each digit on 6-digit
models.
Safety and Reliability
Isolated Power Supply and Input Circuits
Power supply circuit and input circuits are isolated inside the Counter/
Tachometer. Previous non-isolated counters had wiring restrictions
and could be damaged if wired incorrectly. The H7CX removes these
worries.
Note: Except 12 to 24-VDC models.
Set Value Limit
You can set an upper limit for the set value to prevent unexpected
operation of output devices caused by setting mistakes.
Output Counter
The output counter counts the number of times the output turns ON
(alarms can be displayed and the count can be monitored in
increments of 1,000 operations). This counter is useful in managing
the service life of the Counter/Tachometer or the load.
Refer to Safety Precautions on page 52.
12 to 24-VDC Models with Screw Terminals: 59 mm
100 to 240-VAC Models with Screw Terminals: 78 mm*
Models with Sockets: 63.7 mm (case dimension)
* Power supply circuit and input circuits are isolated for safety and reliability.
New models Previous
models
12 mm
(actual size)
Model with 4 Digits Model with 6 Digits
10 mm
(actual size)
(Display example)
New
models
Previous
models
Easy to read from the top, bottom,
and sides!
Model with 4 Digits Model with 6 Digits
For 1,000 pieces
No overflow
Setting the upper limit of the set
value enables worry-free operation.

2
H7CX-@-N
Other Features
The front color can be changed simply by
replacing the Front Panel.
The Front Panel can be replaced with an optional Front Panel (sold
separately) with a different color to match the installation site. Select
from black, white, and light gray (except for models with tachometer
function only).
Universal NPN/PNP Input
DC 2-wire sensors can be connected for a wide range of input
devices.
Waterproof, Dust-proof Structure (UL508 Type
4X and IP66)
Worry-free application is possible in locations subject to water.
Note: When the Y92S-29 Waterproof Packing is used.
Key Protection
Select from any of seven protection patterns. Use the best one for the
application.
New Functions
Many useful functions have been added, including a Twin Counter
Mode and many tachometer functions to handle even more
applications.
New Tachometer Functions
• Control with two independent inputs (independent measurements,
differential, absolute ratio, and error ratio)
• Peak/bottom hold function
• Output hysteresis setting
• Output OFF delay
• Switching the measurement method (pulse cycle/pulse width)
• Startup time
• Auto-zero time
• Averaging method/Number of averaging times
• AMD-compatible Mode
Model Number Structure
Model Configuration
*1. Set the tachometer input mode from the function setting mode to switch to the tachometer function.
White Light gray
Black
(Standard)
Only the Front
Panel can be
replaced.
H7CX Series
Model
H7CX-A-series Multifunction Preset Counter H7CX-R-series Digital Tachometer
Classification Preset counter Preset counter/tachometer Tachometer
Model H7CX-A@-N H7CX-A4W@-N H7CX-AW@-N/-AU@-N H7CX-R11@-N H7CX-R11W@-N
Function
1-stage preset
counter Yes Yes Yes No
2-stage preset
counter No Yes Yes No
Total and preset
counter Yes Yes Yes No
Batch counter No Yes Yes No
Dual counter No Yes Yes No
Twin counter No Yes Yes No
Tachometer No No Yes*1 Yes
Tachometer input No No
Yes
1 input or 2 inputs
(independent
measurements, differential,
absolute ratio value, and
error ratio value)
Yes
1 input
Yes
2 inputs (independent
measurement) only
Settings 1-stage 2-stage 1-stage
External connections 11-pin socket Screw terminals 11-pin socket
Display color of present value Red Red, green, or orange Red
Display digits 4 or 6 digits 4 digits 6 digits 6 digits

H7CX-@-N
3
Model Number Legend (Not all possible combinations of functions are available.)
H7CX-@@@@@@-N
123456
Ordering Information
List of Models
Note: 1. The functions that are provided depend on the model. Check detailed specifications before ordering.
2. Refer to page page 37 and later for information on H7CX-R Tachometers.
Type Classification Configuration External
connections Settings Display
digits Outputs Power supply
voltage Model
H7CX-A
Series
Preset counter
• 1-stage preset
counter
• Total and preset
counter
11-pin socket
1-stage
4 digits
Contact output (SPDT) 100 to 240 VAC H7CX-A114-N
Transistor output (SPST) H7CX-A114S-N
Contact output (SPDT) 12 to 24 VDC/24 VAC H7CX-A114D1-N
6 digits
Contact output (SPDT) 100 to 240 VAC H7CX-A11-N
Transistor output (SPST) H7CX-A11S-N
Contact output (SPDT) 12 to 24 VDC/24 VAC H7CX-A11D1-N
Transistor output (SPST) H7CX-A11SD1-N
Screw
terminals
4 digits
Contact output (SPDT) 100 to 240 VAC H7CX-A4-N
Transistor output (SPST) H7CX-A4S-N
Contact output (SPDT) 12 to 24 VDC H7CX-A4D-N
Transistor output (SPST) H7CX-A4SD-N
6 digits
Contact output (SPDT) 100 to 240 VAC H7CX-A-N
Transistor output (SPST) H7CX-AS-N
Contact output (SPDT) 12 to 24 VDC H7CX-AD-N
Transistor output (SPST) H7CX-ASD-N
• 1-stage preset
counter
• 2-stage preset
counter
• Total and preset
counter
• Batch counter
• Dual counter
• Twin counter
2-stage
4 digits
Contact output (SPST + SPDT) 100 to 240 VAC H7CX-A4W-N
Transistor output (DPST) 12 to 24 VDC H7CX-A4WSD-N
Preset counter/
Tachometer
• 1-stage preset
counter
• 2-stage preset
counter
• Total and preset
counter
• Batch counter
• Dual counter
• Twin counter
• Tachometer
6 digits
Contact output (SPST + SPDT) 100 to 240 VAC H7CX-AW-N
Transistor output (DPST) H7CX-AWS-N
Contact output (SPST + SPDT) 12 to 24 VDC/24 VAC H7CX-AWD1-N
Transistor output (DPST) H7CX-AWSD1-N
12 to 24 VDC H7CX-AWSD-N
Contact output (SPDT) +
Transistor output (SPST) 100 to 240 VAC H7CX-AU-N
Contact output (SPDT) +
Transistor output (SPST) 12 to 24 VDC/24 VAC
H7CX-AUD1-N
Transistor output (DPST) H7CX-AUSD1-N
H7CX-R
Series Tachometer • Tachometer 11-pin socket
1-stage
(1 input and
output) 6 digits
Contact output (SPDT)
100 to 240 VAC H7CX-R11-N
12 to 24 VDC/24 VAC H7CX-R11D1-N
1-stage
(2 inputs and
outputs)
Contact output (SPDT + SPST)
100 to 240 VAC H7CX-R11W-N
12 to 24 VDC/24 VAC H7CX-R11WD1-N
4. Settings
* The H7CX-R11W@is a 1-stage (2 inputs and outputs)
rather than a 2-stage Counter.
5. Output type 6. Supply voltage
Symbol Meaning
None 1-stage setting
U Factory-set to 1-stage setting
W Factory-set to 2-stage setting*
Symbol Meaning
None Contact output or contact output +
transistor output
S Transistor output
Symbol Meaning
None 100 to 240 VAC at 50/60 Hz
D 12 to 24 VDC
D1 12 to 24 VDC/24 VAC at 50/60 Hz
1. Type 2. External connections 3. Digits
Symbol Meaning
A Standard type
R Tachometer
Symbol Meaning
None Screw terminals
11 11-pin socket
Symbol Meaning
None 6 digits
4 4 digits

4
H7CX-@-N
Accessories (Order Separately)
Front Panels (Replacement Part)
Note: 1. You can change the color of the Front Panel when mounting the Counter. The Counter is shipped with a black (N1.5) Front Panel.
2. "COUNTER" is printed on the front of Replacement Front Panels.
Soft Cover
Hard Cover
Flush Mounting Adapter
Waterproof Packing
Connection Sockets
Terminal Covers for P3GA-11 Back-connecting Socket
Model Color Applicable Counters Page
Y92P-CXC4G Light gray (5Y7/1) 4-digit Counter
12
Y92P-CXC4S White (5Y9.2/0.5)
Y92P-CXC4B Black (N1.5)
Y92P-CXC6G Light gray (5Y7/1) 6-digit Counter
Y92P-CXC6S White (5Y9.2/0.5)
Y92P-CXC6B Black (N1.5)
Model Remarks Page
Y92A-48F1 --- 12
Model Remarks Page
Y92A-48 --- 12
Model Remarks Page
Y92F-30 Included with models with screw
terminals.
12
Y92F-45
Use this Adapter to install the Counter/
Tachometer in a cutout previously made
for a DIN 72 ×72 mm device (panel
cutout: 68 ×68 mm).
Model Remarks Page
Y92S-29 Included with models with screw
terminals. 12
Model Classification
Connectable
Counter/
Tachometers
Remarks Page
P2CF-11 Front-connecting Socket
H7CX-@11@-N
---
13
P2CF-11-E Front-connecting Socket (Finger-safe
Type)
Round crimp terminals cannot be used on
Finger-safe Sockets.
Use forked crimp terminals.
P3GA-11 Back-connecting Sockets
A Y92A-48G Terminal Cover can be used
with the Socket to create a finger-safe
construction.
Model Remarks Page
Y92A-48G --- 13

H7CX-A@-N
5
• Easy to check the output status from a long distance with changing
display colors*1 (red, green, and orange).
• Includes total and preset counter, batch counter, dual counter, twin
counter, and tachometer.*2
*1. Not supported by the H7CX-A11@-N.
*2. The functions that can be selected depend on the model.
Specifications
Ratings
*1. 1-stage preset counter and total counter functionality.
*2. Do not use the output from an inverter as the power supply.The ripple must be 20% maximum for DC power.
*3. A response of 10 kHz is possible if the response speed is 5 kHz and the 1-stage preset counter input mode is increment, decrement, or increment/
decrement (command input).
*4. The display is lit only when the power is ON. Nothing is displayed when power is OFF.
H7CX-A@-N Multifunction Preset Counter
Item Models H7CX-A114@-N H7CX-A11@-N H7CX-A4@-N H7CX-A@-N H7CX-A4W@-N H7CX-AW@-N/-AU@-N
Classification Preset counter Preset counter/
tachometer
Configuration 1-stage preset counter, 1-stage preset counter with total counter (selectable)*1
1-stage/2-stage preset
counter, total and preset
counter*1, batch
counter, dual counter,
and twin counter
(selectable)
1-stage/2-stage preset
counter, total and preset
counter*1, batch
counter, dual counter,
twin counter, and
tachometer (selectable)
Ratings
Power supply
voltage*2
• 100 to 240 VAC, 50/60 Hz
• 24 VAC, 50/60 Hz or 12 to 24 VDC
• 100 to 240 VAC, 50/60 Hz
•12to24VDC
• 100 to 240 VAC at 50/
60 Hz
• 24 VAC at 50/60 Hz or
12 to 24 VDC
• 12 to 24 VDC
Operating volt-
age fluctuation
range
85% to 110% of rated supply voltage (12 to 24 VDC: 90% to 110%)
Power con-
sumption Approx. 9.4 VA at 100 to 240 VAC, Approx. 7.2 VA/4.7 W at 24 VAC/12 to 24 VDC, Approx. 3.7 W at 12 to 24 VDC
Mounting method Flush mounting or surface mounting Flush mounting
External connections 11-pin socket Screw terminals
Degree of protection IEC IP66, UL508 Type 4X (indoors) for panel surface only and only when Y92S-29 Waterproof Packing is used.
Input signals CP1, CP2, reset, and total reset CP1, CP2, reset 1, and reset 2
Counter
Maximum
counting speed
30 Hz or 5 kHz (switchable) (ON/OFF ratio 1:1)*3
*Common setting for CP1 and CP2
Input mode Increment, decrement, increment/decrement (UP/DOWN A (command input), UP/DOWN B (individual inputs), or UP/DOWN C (quadrature inputs))
Output mode N, F, C, R, K-1, P, Q, A, K-2, D, and L. N, F, C, R, K-1, P, Q, A, K-2, D, L, and H.
One-shot out-
put time 0.01 to 99.99 s
Reset system External (minimum reset signal width: 1 ms or 20 ms, selectable), manual, and automatic reset (internal according to C, R, P, and Q mode operation)
Tachometer Refer to the separate table for tachometer function ratings.
Prescaling function Yes (0.001 to 9.999) Yes (0.001 to 99.999) Yes (0.001 to 9.999) Yes (0.001 to 99.999) Yes (0.001 to 9.999) Yes (0.001 to 99.999)
Decimal point adjustment Yes (rightmost 3 digits)
Sensor waiting time 290 ms max. (Control output is turned OFF and no input is accepted during sensor waiting time.)
Input method
No-voltage inputs:
ON impedance: 1 kΩmax. (Leakage current: 12 mA at 0 Ω)
ON residual voltage: 3 V max.
OFF impedance: 100 kΩmin.
Voltage input:
High (logic) level: 4.5 to 30 VDC
Low (logic) level: 0 to 2 VDC (Input resistance: approx. 4.7 kΩ)
No-voltage input/voltage input (switchable)
External power supply 12 VDC (±10%), 100 mA (except for H7CX-A@D models) Refer to Precautions for Correct Use on page page 53 for details.
Control output • Contact output: 3 A at 250 VAC/30 VDC, resistive load (cosφ=1), Minimum applied load: 10 mA at 5 VDC (failure level: P, reference value)
• Transistor output: NPN open collector, 100 mA at 30 VDC, Residual voltage: 1.5 VDC max. (approx. 1 V), Leakage current: 0.1 mA max.
Display*4
7-segment, negative
transmissive LCD
Character height
Count value: 12 mm
(red)
Set value: 6 mm (green)
7-segment, negative
transmissive LCD
Character height
Count value: 10 mm
(red)
Set value: 6 mm (green)
7-segment, negative
transmissive LCD
Character height
Count value: 12 mm
(red, green, or orange
selectable)
Set value: 6 mm (green)
7-segment, negative
transmissive LCD
Character height
Count value: 10 mm
(red, green, or orange
selectable)
Set value: 6 mm (green)
7-segment, negative
transmissive LCD
Character height
Count value: 12 mm
(red, green, or orange
selectable)
Set value: 6 mm (green)
7-segment, negative
transmissive LCD
Character height
Count value: 10 mm
(red, green, or orange
selectable)
Set value: 6 mm (green)
Digits
4 digits
−999 to 9999
(−3 digits to +4 digits)
6 digits
−99999 to 999999
(−5 digits to +6 digits)
4 digits
−999 to 9999
(−3 digits to +4 digits)
6 digits
−99999 to 999999
(−5 digits to +6 digits)
4 digits
−999 to 9999
(−3 digits to +4 digits)
6 digits
−99999 to 999999
(−5 digits to +6 digits),
tachometer: 0 to 999999
Memory backup EEPROM (overwrites: 100,000 times min.) that can store data for 10 years min.
Operating temperature
range −10 to 55°C (−10 to 50°C if Counter/Tachometers are mounted side by side) (with no icing or condensation)
Storage temperature range −25 to 70°C (with no icing or condensation)
Operating humidity range 25% to 85%
Case color Black (N1.5) (Optional Front Panels are available to change the Front Panel color to light gray or white.)
Attachments --- Flush mounting adapter, waterproof packing, terminal cover
Flush mounting adapter,
waterproof packing,
terminal cover, label for
DIP switch settings

6
H7CX-A@-N
Tachometer Function Ratings
* An input OFF time of at least 20 ms is required.
Characteristics
Model
Item
H7CX-A114@-N
H7CX-A11@-N
H7CX-A4@-N
H7CX-A@-N
H7CX-A4W@-N
H7CX-AW@-N/-AU@-N
Input mode
No tachometer
functionality
Selectable from independent measurements for 1 or 2 inputs, differential input for 2 inputs, absolute ratio for 2 inputs, and
error ratio for 2 inputs.
Pulse measurement method Periodic measurement Pulse width measurement
Maximum counting speed 30 Hz 1-input mode: 10 kHz
Other modes: 5 kHz 30 Hz 1-input mode: 10 kHz
Other modes: 5 kHz
Minimum input signal width --- --- 30 ms*1 1-input mode: 0.2 ms
Other modes: 0.4 ms*
Measuring ranges 0.01 to 30.00 Hz 1-input mode: 0.01 to 10 kHz,
Other modes: 0.01 to 5 kHz 0.030 to 999999 s 1-input mode: 0.0002 to 99999 s
Other modes: 0.0004 to 99999 s
Sampling period 200 ms min.
200 ms min. or continuous
selectable (minimum interval of 10
ms)
Continuous (minimum interval of 10 ms)
Measuring accuracy ±0.1% FS ±1 digit max. (at 23 ±5°C)
Output mode
Input mode:
Not 2-input independent measurement: HI-LO, AREA, HI-HI, LO-LO
2-input independent measurement: HI-HI, LO-LO
Auto-zero time 0.1 to 999.9s
Startup time 0.0 to 99.9s
Averaging Simple averaging/moving averaging selectable, Processing: OFF, 2, 4, 8, or 16 times
Hold input Minimum input signal width: 20 ms
* Refer to the Life-test Curve.
Applicable Standards
* The following safety standards apply to models with sockets (H7CX-A11@or H7CX-A114@).
cUL (Listing): Applicable when an OMRON P2CF(-E) Socket is used.
cUR (Recognition): Applicable when any other socket is used.
Insulation resistance 100 MΩmin. (at 500 VDC) between current-carrying terminals and exposed non-
current-carrying metal parts, and between non-continuous contacts
Dielectric strength
2,000 VAC, 50/60 Hz for 1 min between current-carrying metal parts and non-
current-carrying metal parts
2,000 VAC, 50/60 Hz for 1 min between power supply and input circuit for all models
except H7CX-@D@(1,000 VAC for 24 VAC/12 to 24 VDC)
1,000 VAC (for H7CX-@SD@), 50/60 Hz for 1 min between control output, power
supply, and input circuit (2,000 VAC for models other than H7CX-@SD@)
1,000 VAC, 50/60 Hz for 1 min between non-continuous contacts
Impulse withstand voltage
3.0 kV between power terminals (1.0 kV for models with 24 VAC/12 to 24 VDC or 12
to 24 VDC)
4.5 kV between current-carrying terminals and exposed non-current-carrying metal
parts (1.5 kV for models with 24 VAC/12 to 24 VDC or 12 to 24 VDC)
Noise immunity
±1.5 kV between power terminals (±480 V for models with 12 to 24 VDC)
±600 V between input terminals
Square-wave noise by noise simulator (pulse width: 100 ns/1 µs, 1-ns rise)
Static immunity Malfunction: 8 kV
Destruction: 15 kV
Vibration
resistance
Destruction 10 to 55 Hz with 0.75-mm single amplitude each in three directions for 2 h each
Malfunction 10 to 55 Hz with 0.35-mm single amplitude each in three directions for 10 min each
Shock re-
sistance
Destruction 300 m/s2each in three directions
Malfunction 100 m/s2each in three directions
Life expectancy
Mechanical: 10,000,000 operations min.
Electrical: 100,000 operations min. (3 A at 250 VAC, resistive load, ambient
temperature condition: 23°C)*
Weight Approx. 130 g (Counter only)
Approved
safety
standards
cULus (or cURus): UL508/CSA C22.2 No. 14*
EN 61010-1 (IEC 61010-1): Pollution degree 2/overvoltage category II
B300 PILOT DUTY
1/4 HP 120 VAC, 1/3 HP, 240 VAC, 3 A resistive load
VDE0106/P100 (finger protection)
EMC
(EMI) EN61326
Emission Enclosure: EN 55011 Group 1 class A
Emission AC mains: EN 55011 Group 1 class A
(EMS) EN61326
Immunity ESD: EN 61000-4-2: 4 kV contact discharge;
8 kV air discharge
Immunity RF-interference: EN 61000-4-3: 10 V/m (Amplitude-modulated, 80 MHz to 1
GHz);
10 V/m (Pulse-modulated, 900 MHz ±5 MHz)
Immunity Conducted Disturbance: EN 61000-4-6: 10 V (0.15 to 80 MHz)
Immunity Burst: EN 61000-4-4: 2 kV power-line;
1 kV I/O signal-line
Immunity Surge: EN 61000-4-5: 1 kV line to lines (power and output lines);
2 kV line to ground (power and output lines)
Immunity Voltage Dip/Interruption: EN 61000-4-11: 0.5 cycle, 100% (rated voltage)
L
if
e-test
C
urve
(
Re
f
erence
Values)
Resistive load
Inductive load
A current of 0.15 A max. can be switched at 125
VDC (cosφ=1) and current of 0.1 A max. can be
switched if L/R=7 ms. In both cases, a life of
100,000 operations can be expected.
1,000
700
500
300
100
70
50
Load current
(
A
)
01 2 34
30 VDC (cosφ=1)
250 VAC (cosφ=1)
No. of operations ( ×10
3
)
1,000
700
500
300
100
70
50
01 2 34
30 VDC (L/R=7 ms)
Load current (A)
250 VAC (cosφ=1)
No. of operations ( ×10
3
)

H7CX-A@-N
7
I/O Functions
Using as a Counter*1
*1. For information on operation of I/O functions, refer to pages page 22 to page 25.
*2. In increment mode or increment/decrement mode, the present value returns to 0; in decrement mode, the present value returns to the set value with 1-stage models,
and returns to set value 2 with 2-stage models.
*3. Reset operates as described in the following table. (The reset indicator will not be lit.)
• The following table shows the delay from when the reset signal is input until the output is turned OFF. (Reference values)
Operating Procedures (Tachometer Function)
Inputs
CP1, CP2
(1) In general (except for Dual Counter Mode)
• Reads counting signals.
• Increment, decrement, command, individual, and quadrature inputs accepted.
(2) When used as a dual counter or twin counter
• Reads CP1 count signals with CP1 input and CP2 count signals with CP2 input.
• Increment signals can be input.
Reset/reset 1
(1) In general (except for Dual Counter Mode)
• Resets present value and outputs (OUT2 when using the batch counter)*2.
• Counting cannot be performed during reset/reset 1 input.
• Reset indicator is lit while reset input is ON.
(2) When used as a dual counter or twin counter.
• Resets the CP1 present value (to 0).
• Counting for CP1 input cannot be performed while the reset 1 input is ON.
• The reset indicator is lit while the reset 1 input is ON.
Total reset or reset 2 The reset function depends on the selected configuration*3.
Outputs OUT1, OUT2 Outputs signals according to the specified output mode when a set value is reached.
Configuration Reset operation
1-stage/2-stage
preset counter Does not operate (not used).
Total and preset
counter
• Resets the total count value.
• The total count value is held at 0 while the total reset input is ON.
Batch counter • Resets the batch count value and batch output (OUT1).
• The batch count value is held at 0 while the reset 2 input is ON.
Dual counter • Resets the CP2 present value.
• Counting for CP2 input cannot be performed while the reset 2 input is ON.
Twin counter • Resets the CP2 present value.
Minimum reset signal width Output delay time
1 ms 0.8 to 1.2 ms
20 ms 15 to 25 ms
Inputs
CP1, CP2 Reads counting signals. (The CP2 input can be used when the input mode is not 1-input mode.)
Reset/reset 1
• Holds the measurement value and outputs. (The reset 2 input can be used when the input mode
is 2-input independent measurement.)
• The reset indicator is lit when the value is being held.
Outputs OUT1, OUT2 Outputs signals according to the specified output mode when a set value is reached.

H7CX-A@-N
8
Connections
Terminal Arrangement
Confirm that the power supply meets specifications before use.
Transistor Output
• The transistor output of the H7CX is isolated from the internal
circuitry by a photocoupler, so the transistor output can be used as
both NPN and PNP output.
• The diode connected to the collector of the output transistor is used
to absorb inverted voltage that is generated when an inductive load
is connected to the H7CX.
H7CX-A-N/-A4-N H7CX-AD-N/-A4D-N H7CX-AS-N/-A4S-N
1-stage Contact Output 1-stage Contact Output
Terminals 1 and 6 are connected internally.
1-stage Transistor Output
H7CX-ASD-N/-A4SD-N H7CX-AW-N/-A4W-N/-AWD1-N/-AU-N/-AUD1-N H7CX-AWS-N/-AWSD1-N/-AUSD1-N
1-stage Transistor Output
Terminals 1 and 6 are connected internally.
2-stage Contact Output 2-stage Transistor Output
H7CX-AWSD-N/-A4WSD-N H7CX-A11-N/-A114-N/-A11D1-N/-A114D1-N H7CX-A11S-N/-A114S-N/-A11SD1-N
2-stage Transistor Output
Terminals 1 and 6 are connected internally.
1-stage Contact Output 1-stage Transistor Output
678910
11
OUT
(−)
(+)
0 V
12345
Reset
Total reset
CP2
CP1
Sensor
12 VDC
External
power supply
678910
OUT
(+)
(−)
0 V
12345
Reset
Total reset
CP2
CP1
678910
11
12345
OUT
0 V
(−)
(+)
Reset
Total reset
CP2
CP1
Sensor
12 VDC
External
power supply
678910
0 V
12345
OUT
(+)(−)
Reset
CP2
CP1
Total reset
678910
11 12 13 OUT1
12345
OUT2
(+)(−)
0 V
(−)
(+)
Reset 1
CP2
CP1
12 VDC
External
power supply
Reset 2
Sensor
12 13
*1
1: “-AU@” Models
*
*
678910
11 12 13
12345
OUT1
OUT2
0 V
(+)(−)
(−)
(+)
Reset 1
CP2
CP1
Sensor
12 VDC
External
power supply
Reset 2
678910
12 13
0 V
12345
OUT1
OUT2
(+)(−)
Reset 1
CP2
CP1
Reset 2
67
8
9
10
11
1
2
3
4
5
(+)
(−)
OUT
0 V
(−)
(+)
Reset
Total reset
CP2
CP1
Sensor
12 VDC
External
power supply
Internal circui
t
67
8
9
10
11
1
2
3
4
5
0 V
OUT
(+)(−)
(−)
(+)
Reset
Total reset
CP2
CP1
Sensor
12 VDC
External
power supply
Internal circui
t
Power for load
+
Load
Power for load
+
Load
NPN Output PNP Output
Power for load
+
Counter
Inductive
load

H7CX-A@-N
9
Block Diagram
Note: All models except for H7CX-@D-N have basic insulation.
Input Circuits
CP1, CP2, Reset/Reset 1, and Total Reset/Reset 2
Input
Input Connections
The inputs of the H7CX-@-N are no-voltage (short-circuit or open) inputs or voltage inputs.
No-voltage Inputs (NPN Inputs)
No-voltage Input Signal Levels
Note: The DC voltage must be 30 VDC max.
Voltage Inputs (PNP Inputs)
Voltage Input Signal Levels
Note: 1. The DC voltage must be 30 VDC max.
2. Input resistance: Approx. 4.7 kΩ
Output circuit
(See note.)
Display circuit
Input circuits
(Basic insulation)
(Basic insulation)
Internal
control circuit
Power supply
circuit
Key switch
circuit
No-voltage Inputs
(NPN Inputs)
Voltage Inputs (PNP Inputs)
Internal
circuit
IN
+14V
1 kΩIN
Approx. 4.7 kΩInternal
circuit
Open Collector Voltage Output Contact Input DC Two-wire Sensor
H7CX-A@
H7CX-A11@
Note: Operates with transistor ON.
PLC or
sensor
678910
37564
0 V for inputs
Reset/reset 1 input
CP2 input
CP1 input
Total reset/reset 2 input
H7CX-A@
H7CX-A11@
Note: Operates with transistor ON.
Sensor
678910
37564
0 V for inputs
Reset/reset 1 input
CP2 input
CP1 input
Total reset/reset 2 input
Note: Operates with relay ON.
H7CX-A@
H7CX-A11@
678910
37564
0 V for inputs
Reset/reset 1 input
CP2 input
CP1 input
Total reset/reset 2 input
Note: Operates with transistor ON.
H7CX-A@
H7CX-A11@
678910
37564
0 V for inputs
Reset/reset 1 input
CP2 input
CP1 input
Total reset/reset 2 input
No-contact input
Short-circuit level (transistor ON)
• Residual voltage: 3 V max.
• Impedance when ON: 1 kΩmax.
(The leakage current is approx. 12 mA when the impedance is 0 Ω.)
Open level (transistor OFF)
• Impedance when OFF: 100 kΩmin.
Contact input Use contacts which can adequately switch 5 mA at 10 V.
Applicable Two-wire Sensor
• Leakage current: 1.5 mA max.
• Switching capacity: 5 mA min.
• Residual voltage: 3 VDC max.
• Operating voltage: 10 VDC
No-contact Input (NPN Transistor) No-contact Input (PNP Transistor) Contact Input
Note: Operates with transistor OFF.
H7CX-A@
H7CX-A11@
Sensor
678910
37564
0 V for inputs
Reset/reset 1 input
CP2 input
CP1 input
Total reset/reset 2 input
Note: Operates with transistor ON.
H7CX-A@
H7CX-A11@
Sensor
678910
37564
0 V for inputs
Reset/reset 1 input
CP2 input
CP1 input
Total reset/reset 2 input
Note: Operates with relay ON.
H7CX-A@
H7CX-A11@
678910
37564
0 V for inputs
Reset/reset 1 input
CP2 input
CP1 input
Total reset/reset 2 input
High level (input ON): 4.5 to 30 VDC
Low level (input OFF): 0 to 2 VDC

10
H7CX-A@-N
Nomenclature
Dimensions (Unit: mm)
Counters
ON
(Enable)
(Default setting) OFF
(Disable)
RST
11
10
9
10
11
8
6
7
4
12
13
8
6
7
12
5
4
1st digit4th digit
1st digit6th digit
1
1
2
2
3
3
5
1 4
1
1 2
4
Display Section
3. Reset Indicator (orange)
1. Key Protect Indicator (orange)
2. Control Output Indicator (orange)
4. Total Count Indicator
6. Set Value 1, 2 Stage Indicator
8. Set value (Sub-display)
(Character height: 6 mm, green)
9. Hold Display (orange)
OUT: (One-stage)
OUT: (Two-stage)
(Lit when the total count value is displayed.)
(Lit when the reset input (1) or Reset Key is ON.)
Displayed only when the configuration selection
mode is not tachometer mode.
5. Batch Indicator
(Lit when the batch count value is displayed.)
Operation Keys
10. Mode Key
(Changes modes and setting items.)
11. Reset Key (See note.)
12. Up Keys to
1 6
(6-digit models: to )
13. Down Keys to
Switches
14. Key-protect Switch
15. DIP Switch
7. Present Value (Main Display)
(Character height: 12 mm (6-digit: 10 mm), red*)
(Front view of 4-digit model)
(Front view of 6-digit model)
* Characters on models with screw terminals (H7CX-A11@)
can be switched between red, green, and orange.
Displayed only when the configuration selection
mode is not tachometer mode.
OFF
ON
12345678
Note: The reset functions depends on the selected configuration.
Configuration Reset operation
1-stage/2-stage
preset counter Resets the present value and outputs.
Total and preset
counter
• Resets the present value and outputs.
• When the total count value is displayed, resets the
present value, the total count value, and outputs.
Batch counter
• Resets the present value and OUT2.
• When the batch count value is displayed, resets the
present value, the batch count value, and outputs.
Dual counter Resets the CP1 present value, CP2 present value, dual
count value, and outputs.
Twin counter
Resets the CP1 present value and output 1 when the
CP1 present value is displayed.
Resets the CP2 present value and output 2 when the
CP2 present value is displayed.
Tachometer
Holds the measurement value and outputs (hold
function).
(When the input mode is 2-input independent
measurement, the CP1 measurement value display will
hold the CP1 measurement value and output 1 and the
CP2 measurement value display will hold the CP2
measurement value and output 2.)
14 1
5
Model with 4 Digits
6 mm
12 mm
Character Size
for Sub-display
Character Size
for Main Display
Model with 6 Digits
10 mm 6 mm
Character Size
for Sub-display
Character Size
for Main Display
44.8 ×44.8
78
48 ×48 6
H7CX-A-N/-AS-N/-AW-N/-AWS-N/-AWD1-N/-AWSD1-N/-A4-N/-A4S-N/-A4W-N/-AU-N/-AUD1-N/-AUSD1-N
(Flush Mounting Models)
Note: M3.5 terminal screw (effective length: 6 mm)

H7CX-A@-N
11
Dimensions with Flush Mounting Adapter
48 ×48
44.8 ×44.8
59
6
H7CX-AD-N/-ASD-N/-AWSD-N/-A4D-N/-A4SD-N/-A4WSD-N (Flush Mounting Models)
Note: M3.5 terminal screw (effective length: 6 mm)
48 ×48
44.8 ×44.8
63.7 14.4
6
H7CX-A11-N/-A11S-N/-A11D1-N/-A11SD1-N/-A114-N/-A114S-N/-A114D1-N (Flush Mounting/Surface Mounting Models)
58
48 76.57.5
Panel Y92F-30 (provided)
Flush Mounting Adapter
Y92S-29 (provided)
Waterproof Packing
(51)
H7CX-A-N/-AS-N/-AW-N/-AWS-N/-AWD1-N/-AWSD1-N/-A4-N/-A4S-N/-A4W-N
(Provided with Adapter and Waterproof Packing)
Panel Cutouts
Panel cutouts are as shown below. (according
to DIN43700).
Note: 1. The mounting panel thickness
should be 1 to 5 mm.
2. To allow easier operation, it is
recommended that Adapters be
mounted so that the gap between
sides with hooks is at least 15 mm
(i.e., with the panel cutouts
separated by at least 60 mm).
3. It is possible to mount counters
side by side, but only in the
direction without the hooks. If they
are mounted side-by-side, water-
resistance will be lost.
Dimensions with Front
Connecting Socket
* These dimensions depend on the kind of DIN Track.
(Reference value)
60 min.
60 min.
15 min.
45+0.6
0
45+0.6
0
A
With Y92A-48F1 attached.
With Y92A-48 attached.
A=(48n−2.5) +1
−0
A=(51n−5.5) +1
−0
A={48n−2.5+(n−1)×4} +1
−0
n Units mounted
side by side
103.2* 100.9
H7CX
-A11@
P2CF-11(-E) Front Connecting Socket
(order separately)
58
48
(51)
7.5 57.5
Panel Y92F-30 (provided)
Flush Mounting Adapter
Y92S-29 (provided)
Waterproof Packing
H7CX-AD-N/-ASD-N/-AWSD-N/-A4D-N/-A4SD-N/-A4WSD-N
(Provided with Adapter and Waterproof Packing)
58
48
(51)
7.5 89.9
Panel Y92F-30 (order separately)
Flush Mounting Adapter
Y92S-29 (order separately)
Waterproof Packing
H7CX-A11-N/-A11S-N/-A11D1-N/-A11SD1-N/-A114-N/-A114S-N/-A114D1-N
(Adapter and Waterproof Packing Ordered Separately)

12
H7CX-A@-N
Accessories (Order Separately)
Front Panel (Replacement Part)
You can change the color of the Front Panel when mounting the
Counter/Tachometer. The Counter/Tachometer is shipped with a
black (N1.5) Front Panel. "COUNTER" is printed on the front of
Replacement Front Panels.
Protecting the Counter/Tachometer in Environments
Subject to Oil
The Waterproof Packing will deteriorate, harden, and shrink
depending on the application environment. To ensure maintaining the
IP@6, UL Type 4X waterproof level, periodically replace the
Waterproof Packing. The periodic replacement period will depend on
the application environment. You must confirm the proper
replacement period. Use 1 year or less as a guideline. If the
Waterproof Packing is not replaced periodically, the waterproof level
will not be maintained. It is not necessary to mount the Waterproof
Packing if waterproof construction is not required.
Note: Depending on the operating environment, the condition
of resin products may deteriorate, and may shrink or
become harder. Therefore, it is recommended that resin
products are replaced regularly.
Y92P-
C
X
C
4
G
4-digit Counter
Light gray (5Y7/1)
Y92P-CXC4S
4-digit Counter
White (5Y9.2/0.5)
Y92P-CXT4B
4-digit Counter
Black (N1.5)
Replacement Method
The Front Panel is attached to the
Counter/Tachometer with tabs in
four locations. To remove the
Front Panel, open the tabs and
pull the Front Panel forward. To
attach the Front Panel, press it
onto the Counter/Tachometer so
that all four tabs lodge into the
grooves on the body of the
Counter/Tachometer.
Ta b s
Grooves
Y92P-CXT6G
6-digit Counter
Light gray (5Y7/1)
Y92P-CXT6S
6-digit Counter
White (5Y9.2/0.5)
Y92P-CXT6B
6-digit Counter
Black (N1.5)
The H7CX's panel surface is water-resistive (conforming to IP@6,
UL Type 4X) and so even if drops of water penetrate the gaps
between the keys, there will be no adverse effect on internal circuits.
If, however, there is a possibility of oil being present on the
operator's hands, use the Soft Cover. The Soft Cover ensures
protection equivalent to IP54F against oil. Do not, however, use the
H7CX in locations where it would come in direct contact with oil.
Soft Cover
Y92A-48F1
Hard Cover
Y92A-48
Y92F-45
Use this Adapter to
install the Counter/
Tachometer in a
cutout previously
made for a DIN 72
×72 mm device
(panel cutout: 68 ×
68 mm).
Flush Mounting Adapter
Y92F-30
Order the Flush
Mounting Adapter with
the following model
number separately if it
is lost or damaged.
Note: The
Waterproof
Packing is
included with
models with
screw
terminals.
Waterproo
f
Pack
i
ng
Y92S-29
Note: The
Waterproof
Packing is
included with
models with
screw
terminals.
Order the Waterproof Packing
separately if it is lost or damaged. The
Waterproof Packing can be used to
achieve IP66 protection.

H7CX-A@-N
13
Connection Sockets
Front Connecting Socket
Note: Round crimp terminals cannot be used on Finger-safe Sockets. Use forked crimp terminals.
Back-connecting Sockets
Note: A Y92A-48G Terminal Cover can be used with the Socket to create a finger-safe construction.
Terminal Covers for P3GA-11 Back-connecting Socket
Note: The Terminal Cover can be used with a Back-mounting Socket (P3GA-11) to create a finger-safe construction.
Model Dimensions Terminal arrangement
and internal connections
Mounting hole
dimensions
P2CF-11
(Top View)
Note: The Socket can
also be mounted
to DIN track.
P2CF-11-E
(Finger-safe Type)
Model Dimensions Terminal arrangement
and internal connections
P3GA-11
(Bottom View)
Model Dimensions
Y92A-48G
4
70 max.
50 max.
Two, 4.5-dia. holes
Eleven, M3.5 ×7.5 sems screws 7.8
31.2 max.
4
3
8 7 6 5
10 11 1 2
9 3
4
40±0.2
Two, M4 or 4.5-dia. holes
10 11
12
7865
3
4
9
P2CF-11-E
10A250VAC
RESISTIVE
4
40±0.2
7.8
30
4.5
35.
4
1.2
3
5
70 max.
50 max.
Two, 4.5-dia. holes
Eleven, M3.5 ×7.5 set screws
31.2 max.
27 dia.
4.5 16.3 6.2
25.6
45
45
876
4
39
5
101112
Y92A-48G UP
P C
34
Twelve, 6.4-dia. holes
47.7 ×47.7
48 ×48
27.6
24.6
16.5
47.4

14
H7CX-A@-N
Optional Products for Track Mounting
Note: Order Spacers in increments of 10.
1
35±0.3
7.3±0.15
27±0.15
4.5
15 25 2510 15 (5)*
1025 25
1,000 (500)* * The values shown in parentheses
are for the PFP-50N.
Mounting Track
PFP-100N
PFP-50N
15 25 25 1,000
4.5
25 25 1510 1
242735±0.3
16
1.5
29.2
10
Mounting Track
PFP-100N2
4.8
1.3
35.5 35.3
1.8
1
1.8
10
6.2
M4 spring washer
50
11.5
10
M4 ×8
pan head
screw
End Plate
PFP-M
5
16
12
44.3 34.8
16.5
Spacer
PFP-S

H7CX-A@-N
15
Counter
Operating Procedures
Setting Procedure Guide
Setting for Counter Operation *
Use the following settings.
Setting for Tachometer Operation *
Refer to page page 27.
* At the time of delivery, the H7CX is set to the 1-stage preset counter configuration. (2-stage models are set to the 2-stage preset counter configuration.) Refer to page page 35 for information
on switching models.
I/O Functions for Counter Operation
After making DIP switch settings for basic operations, advanced functions can be added using the operation keys.
For details, refer to page page 16.
Key-protect switch
Disabled Enabled
OFF
ON
OFF
ON
OFF
OFF
ON
ON
N
F
C
K-1
UP DOWN
Refer to the table on the right.
30 Hz 5 kHz
20 ms 1 ms
DIP switch settings
Counting speed
Input mode
Output mode
Minimum reset signal
Input selection
Output time 0.5 s 0.05 s
NPN PNP
Note: All pins are factory-set to OFF.
•When setting functions using the DIP switch, be sure to set pin 1 of the DIP switch to ON.
•DIP switch settings are effective when the power is turned ON again. (Perform DIP switch settings while the power is OFF.)
Step1
Step3
Set the basic parameters.
(If the desired I/O mode is not listed below or to set all parameters using the front panel keys, perform ,
below.)
Note: can be performed first, followed by .
Note: The configuration that can be selected depends on the model.
* The default mode is 1-stage preset counter configuration (2-stage preset counter configuration for 2-stage models).
Item OFF ON
Output modePin 5Pin 4
1
2
3
4
5
6
7
8
Step2
Step2 Step1
Hold down for 1 s min.
Select the function from Table 1 using the U(D) Key.
Run mode
Power ON
1
+
Hold down for 1 s min.
1
+twn
The H7CX-A@-N is a Counter that contains more than one functional counter.
When using the Counter in any mode other than the default mode*, use the following chart to enter
Configuration Selection Mode and set the functions that are suitable to the application.
(1-stage
preset
counter)
(2-stage
preset
counter)
(Total and
preset counter)
(Batch
counter)
(Dual
counter)
(Twin
counter)
(Tachometer)
Configuration
selection mode
Be sure to set pin 1 to ON.
OFF
ON
12345678

16
H7CX-A@-N
Counter
Run mode
Power ON
Function
setting mode
*3
*7
*5 Displayed for output modes other than K-2, D, L, and H only.
*5
*5
*6 Displayed only when the input mode is ud-a, ud-b, or ud-c.
(Not displayed when the function is set to twn.)
Note: Displayed only when the output mode is C, R, K-1, P, Q, A,
or K-2.
Note: Displayed for terminal-block models (except H7CX-A11@) only.
*3 When Using Dual Counter
Operation
*7 Set each digit using the individual U(D) Keys.
Note: Displayed only when the
output mode is C, R, K-1, P, Q,
A, or K-2.
Note: Displayed for output modes
other than D, L, and H.
HOLD cannot be set when
the output mode is K-2.
*7 Set each digit using the individual U(D) Keys.
Note: Displayed only when Twin Counter Mode is not selected.
(Red) (Green) (Orange)
(Red-green) (Green-red) (Red-orange) (Orange-red)
(Green-orange) (Orange-green)
3 s min.*2
3 s min.*1
Step3
Parameters that cannot be set with the DIP switch are set with the operation keys on the front panel.
Change to Function Setting Mode.
Input mode
(CNTM)
Output
time
(OTIM)
Output mode
(OUTM)
NPN/PNP
input mode
(IMOD)
Display color
(COLR)
(1 ms)(20 ms)
(No decimal point)
Prescale
value
(PSCL)
Counting
speed
(CNTS)
(30 Hz) (5 kHz)
(PNP input)(NPN input)
The characters displayed in reverse video are the default settings.
When performing settings with operation keys only, set pin1 of the DIP switch to OFF (factory setting).
If pin 1 of the DIP switch is set to ON, the setting items indicated by will not be displayed.
For 6-digit models, only UKeys are provided.
Displays for 6-digit models are given in parentheses.
(N)
(0.50 s) (99.99 s)(0.01 s)
(0.01 s) (99.99 s)
(Outputs held)
(F) (C) (R) (K-1) (P) (Q) (A) (K-2) (D) (L) (H)
*6 *6 *6 *6
(DOWN) (
UP/DOWN A
)(
UP/DOWN B
)(
UP/DOWN C
)(UP)
(99.999)(1.000)(0.001)
(0.50 s) (99.99 s)(0.01 s)
To next pageFrom next page
(Addition) (Subtraction)
*4
Reset input
signal width
(IFLT)
Decimal
point position
(DP)
• Set the input mode using the U(D) Keys.
• Set the output mode using the U(D) Keys.
• Set each digit using the individual U(D) Keys.
• Set the counting speed using the U(D) Keys.
• Set the Reset input signal width using the U(D) Keys.
• Set the decimal point position using the U(D) Keys.
(One digit after
decimal point)
(Two digits after
decimal point)
(Three digits after
decimal point)
• Set each digit using the individual U(D) Keys.
(9.999)
• Set the NPN/PNP input mode using the U(D) Keys.
• Set the display color using the U(D) Keys.
Dual count
calculating
mode
(ADD)
• Set the dual count calculating
mode using the UD Keys.
*4 Displayed only when the output mode is K-2,
D, L, or H.
When using as a 2-stage preset counter
One-shot
output 2
time
(OTM2)
One-shot
output 1
time
(OTM1)
Note: Displayed only when the
output mode is C, R, K-1, P, Q,
A, or K-2.
(0.50 s) (99.99 s)(0.01 s)
When using as a batch counter
One-shot
output 2
time
(OTM2)
Function Setting Mode
grnred org r-g g-r r-o o-r g-o o-g
up down
nf
0.01 99.990.50
30hz
1ms
0.001 99.9999.999
1.000
pnpnpn
20ms
crk-1 k-2pqa dlh
subadd
0.50
hold 0.01 99.99
0.01 0.50 99.99
0.01 99.99
ud-a ud-b ud-c
*1 If the mode is switched to the function setting mode during operation, operation will continue.
*2 Changes made to settings in function setting mode are enabled for the first time when the mode is changed to run mode. Also,
when settings are changed, the counter is reset (present value initialized and output turned OFF) on returning to run mode.
If the output time is 0.00, hold is displayed.
Note: Displayed only when the
output mode is C, R, K-1, P,
Q, or A.
Note: Displayed only when the
output mode is C, R, K-1, P,
Q, or A.
(0.50 s) (99.99 s)(0.01 s)
Twin Counter
Output 2
output
time
(OTM2)
Output 1
output
time
(OTM1)
0.500.01 99.99
(0.50 s) (99.99 s)(0.01 s)
0.500.01 99.99
For details on operations and display in run mode, refer to page page 20.
The display depends on the selected configuration.

H7CX-A@-N
17
Counter
(9999 ×1000 times)(0 ×1000 times)
(OFST)(ABS)
(KP-1) (KP-2) (KP-3) (KP-4) (KP-5) (KP-6) (KP-7)
(9999 ×1000 times)(0 ×1000 times)
(9999 ×1000 times)(0 ×1000 times)
99990
99990
99990
(9999)(1)
99991
(9999)(1)
99991
(9999)(1)
99991
ofstabs
kp-1 kp-2 kp-3 kp-4 kp-5 kp-6 kp-7
(ON)(OFF)
onoff
*8
Note: 1 to 999999 for 6-digit models
*8 Set each digit using the individual U(D) Keys.
Note: The monitor value is only displayed. It cannot be set.
Forecast
setting
upper limit
(PL-H)
Key protect
level
(KYPT)
From previous
page
To previous
page
Output ON
count alarm set
value/monitor
value
• Make the absolute value setting and forecast setting using the U(D) Keys.
• Set each digit using the individual U(D) Keys.
• Set each digit using the individual U(D) Keys.
• Set the key protect level using the U(D) Keys.
Procedure for Models Other than “-@W@” Models
Output
ON count
alarm set
value
Output
ON count
monitor
value
Output 1
(OUT1) ON
count alarm
set value
Function Setting Mode
Absolute value
setting/forecast
value setting
(SETM)
Set value
upper limit
(SL-H)
Note: 1 to 999999 for 6-digit models.
Note: 1 to 999999 for 6-digit models.
Note: Displayed only when the output mode is set to bcnt.
• Set each digit using the individual U(D) Keys.
Procedure for “-@W@” Models
Note: The monitor value is only displayed. It cannot be set.
Note: The monitor value is only displayed. It cannot be set.
Output 2
(OUT2) ON
count alarm
set value
Output 1
(OUT1) ON
count monitor
value
Output 2
(OUT2) ON
count monitor
value
Batch count
upper limit
(BL-H)
Note: Displayed only when the configuration selection mode is set to the 2-stage function 2cnt.
Note: Displayed only when the configuration selection mode is set to the 2-stage function 2cnt and a forecast value is set.
Output
allocation
change
Note: Displayed only for "-AU@" models.
off: Output 1 = 12, 13, Output 2 = 3, 4, 5 on: Output 1 = 3, 4, 5, Output 2 = 12, 13
The numbers are the terminals numbers.

18
H7CX-A@-N
Counter
Explanation of Functions
Items marked with stars ★can be set using the DIP switch.
Input Mode (cntm)★
Set increment mode (UP), decrement mode (DOWN), or one of the
increment/decrement modes (UP/DOWN A, UP/DOWN B, or UP/
DOWN C) as the input mode.
Input modes other than UP or DOWN modes cannot be set using the
DIP switch and so use the operation keys if other modes are required.
(For details on the operation of the input modes, refer to Input Modes
and Present Value on page page 21.)
Dual Count Calculating Mode ( calm)
When using as a dual counter, select either ADD (addition) or SUB
(subtraction) as the calculation method for the dual count value.
ADD: Dual count value = CP1 PV + CP2 PV
SUB: Dual count value = CP1 PV −CP2 PV
Output Mode (outm)★
Set the way that control output for the present value is output. The
possible settings are N, F, C, R, K-1, P, Q, A, K-2, D, L, and H.
Output modes other than N, F, C, or K-1 cannot be set using the DIP
switch and so use the operation keys if other modes are required. The
output modes that can be set vary with the model.
(For details on the operation of the output modes, refer to Input/
Output Mode Settings on page page 22.)
One-shot Output Time (otim)★
Set the one-shot output time (0.01 to 99.99 s) for control output.
One-shot output can be used only when C, R, K-1, P, Q, A, or K-2 is
selected as the output mode. Output times other than 0.5 s or 0.05 s
cannot be set with the DIP switch and so use the operation keys if
other settings are required.
One-shot Output 2 Time (otm2)★
Set the one-shot output time (0.01 to 99.99 s) for control output
(OUT2).
One-shot output can be used only when C, R, K-1, P, Q, A, or K-2 is
selected as the output mode. Output times other than 0.5 s or 0.05 s
cannot be set with the DIP switch and so use the operation keys if
other settings are required.
One-shot Output 1 Time (otm1)
Set the one-shot output time (0.01 to 99.99 s) for control output
(OUT1).
One-shot output can be used only when D, L, or H is selected as the
output mode.
If the output time is set to 0.00, hold is displayed, and outputs are
held.
Counting Speed (cnts)★
Set the maximum counting speed (30 Hz/5 kHz) for CP1 and CP2
inputs together.
If contacts are used for input signals, set the counting speed to 30 Hz.
Processing to eliminate chattering is performed for this setting.
Reset Input Signal Width (iflt)★
Set the reset input signal width (20 ms/1 ms) for reset/reset 1 and total
reset/reset 2 inputs together.
If contacts are used for the input signal, set the input signal width to
20 ms. Processing to eliminate chattering is performed for this setting.
Decimal Point Position (dp)
Decide the decimal point position for the present value, CP1/CP2
present values, set value (SV1, SV2), total count value, and dual
count set value.
Prescale Value (pscl)
Pulses input to the counter are converted according to the specified
prescale value.
(Setting range: 0.001 to 99.999 for 6-digit models and 0.001 to 9.999
for 4-digit models.)
Example: To display the feed distance for systems that output 25
pulses for a feed length of 0.5 m in the form @@.@@ m:
1. Set the decimal point position to 2 decimal places.
2. Set the prescale value to 0.02 (0.5 ÷25).
• Observe the following points when setting a prescale value.
Set the set value to a value less than {Maximum countable value
−Prescale value}.
Example: If the prescale value is 1.25 and the counting range is
0.000 to 999.999, set the set value to a value less than 998.749
(= 999.999 −1.25).
If the set value is set to a value greater than this, output will not turn
ON.
• Output will turn ON, however, if a present value overflow occurs
(FFFFFF or FFFF).
NPN/PNP Input Mode (imod)
Select either NPN input (no-voltage input) or PNP input (voltage
input) as the input format. When using a two-wire sensor, select NPN
input.
The same setting is used for all external inputs.
For details on input connections, refer to Input Connections on page
page 9.
Display Color (colr) (Displayed for terminal block models
(except H7CX-A11@) only.)
Set the color used for the present value.
* Output 2 for 2-stage models.
With the twin counter, output 1 and output 2 will both turn OFF when
the output status is OFF. Either output 1 or output 2 will turn ON when
the output status is ON.
Output OFF* Output ON*
red Red (fixed)
grn Green (fixed)
org Orange (fixed)
r-g Red Green
g-r Green Red
r-o Red Orange
o-r Orange Red
g-o Green Orange
o-g Orange Green
25 pulses
Encoder
0.5 m
Note: If the prescale value setting is incorrect, a counting error will
occur. Check that the settings are correct before using this
function.

H7CX-A@-N
19
Counter
Absolute Value Setting/Forecast Value Setting (setm)
For the 2 count output mode, an absolute value setting (abs) or
forecast value setting (ofst) can be set for set value 1.
When a forecast value is set, specify the forecast value set value (i.e.,
the deviation for the set value).
The forecast output (output 1) turns ON when the present value
reaches the forecast value.
If the forecast set value is greater than or equal to the set value, the
forecast output (output 1) will turn ON as soon as counting starts.
If the forecast value setting is used, specify the set value 2 minus the
forecast value setting for set value 1.
Set Value Upper Limit (sl-h)
Set the upper limit for the set value when it is set in run mode.
The setting can be made from 1 to 9999 for 4-digit models and from
1 to 999999 for 6-digit models.
Forecast Set Upper Limit (pl-h)
Set the upper limit for the forecast set value.
The setting can be made from 1 to 9999 for 4-digit models and from
1 to 999999 for 6-digit models.
Batch Count Upper Limit (bl-h)
Set the upper limit for the batch count value. The setting can be made
from 1 to 9999 for 4-digit models and from 1 to 999999 for 6-digit
models.
Output Allocation (otst)
When using an H7CX-AU@-N model as a 2-stage counter, the output
can be flexibly allocated to either stage 1 or 2.
The transistor output can be allocated to SV1 and the contact output
to SV2 or vice verse, as in the following tables.
H7CX-AU-N/-AUD1-N
H7CX-AUSD1-N
Key Protect Level (kypt)
Set the key protect level.
Refer to Key Protect Level on page page 36.
Output ON Count Alarm Set Value (on-a)
Set the alarm value for the output ON count.
The limit can be set to between 0 ×1000 (0 times) and 9999 ×1000
(9,999,000 times). Only the underlined values are set. The alarm will
be disabled if 0 is set.
If the total ON count of the output exceeds the alarm set value, e3
will be displayed on the Timer to indicate that the output ON count
alarm value was exceeded. Refer to Self-diagnostic Function on page
page 36 for information on the e3 display.
ON Count Alarm Set Values for Outputs 1 and 2 (OUT1
and OUT2) (on1a and on2a)
Set the ON count alarm values for the outputs 1 and 2.
The limit can be set to between 0 ×1000 (0 times) and 9999 ×1000
(9,999,000 times). Only the underlined values are set. The alarm will
be disabled if 0 is set.
If the total ON count of instantaneous output 1 or 2 exceeds the alarm
set value, e3 will be displayed on the Timer to indicate that the output
ON count alarm value was exceeded. Refer to Self-diagnostic
Function on page page 36 for information on the e3 display.
Output ON Count Monitor Value (on-c)
The monitor value is only displayed. It cannot be set.
The output ON count will be 1,000 times the displayed value.
ON Count Monitor Values for Outputs 1 and 2 (OUT1 and
OUT2) (on1c and on2c)
The monitor value for output 1 or 2 is only displayed. It cannot be set.
The output ON count will be 1,000 times the displayed value.
Output 1 Output 2
off Transistor (12-13) Contact (3, 4, 5)
on Contact (3, 4, 5) Transistor (12-13)
Output 1 Output 2
off Transistor (12-13) Transistor with diode (3, 4, 5)
on Transistor with diode (3, 4, 5) Transistor (12-13)
Set value 2
Set value 1
0
Control output 1 (OUT1)
Control output 2 (OUT2)
Count value
Example: F Mode
Set value
Forecast
value
Forecast set value
0
Forecast output (OUT1)
Control output (OUT 2)
Count value
Example: F Mode

20
H7CX-A@-N
Counter
Operation in Run Mode
I/O Functions for Counter Operation
Present value
Set value 1
Present value
Set value
Present value
Set value 2
Present value
Set value
Batch count value
Batch count set value
Present value 1
Set value 1
Present value 2
Set value 2
Present value
Set value
Total count value
Dual count value
Dual count
set value
CP1 present value
CP2 present value
Present value
Set value
Present value
Forecast Set Value
Total and Preset Counter
Batch Counter
Dual Counter
Twin Counter
• Set values for each digit as required using the U(D) Keys. (UKey only for 6-digit models.)
1-stage Preset Counter
2-stage Preset Counter with
Absolute Value Setting
• Present Value
Shows the present count value.
• Set Values (Set Value 1 and Set Value 2)
Set the set values.
When the present value reaches the set value (set
value 1 or set value 2), a signal is output according
to the specified output mode.
• Present Value/Set Value
Same as 1-stage preset counter.
• Total Count Value
Shows the present total count value.
• Present Value/Set Value
Same as 1-stage preset counter.
• Batch Count Value
Shows the number of times the count has been
completed for the present value.
• Batch Count Set Value
Set the batch count set value.
When the batch count value reaches the batch
count set value, batch output (OUT1) turns ON.
• Dual Count Value
Shows the sum of the CP1 present value and
CP2 present value when the dual count
calculating mode is ADD and shows the value
obtained by subtracting the CP2 present
value from the CP1 present value when the
dual count calculating mode is SUB.
• Dual Count Set Value
Set the dual count set value.
When the dual count value reaches the dual
count set value, signals are output according
to the specified output mode.
• CP1/CP2 Present Value
Show the present count values for CP1 and
CP2 present values respectively.
• Present Values 1 and 2
Shows the present count value 1 or 2.
• Set Values 1 and 2
Setting for present value 1 or 2.
• Present Value
Shows the present count value.
• Set Values
Set the set values.
• Forecast Set Value
Set the deviation for the set value.
2-stage Preset Counter with
Forecast Value Setting
This manual suits for next models
43
Table of contents
Other Omron Measuring Instrument manuals

Omron
Omron V700-HMD11 User manual

Omron
Omron E3NC-SH Series User manual

Omron
Omron K3MA-L User manual

Omron
Omron KE1 User manual

Omron
Omron K7DD User manual

Omron
Omron K3TJ User manual

Omron
Omron H7CX - User manual

Omron
Omron K3HB-P User manual

Omron
Omron ZN-KMX21 Series User manual

Omron
Omron K3MA-J Series User manual

Omron
Omron K3HB-S User manual

Omron
Omron K3NR User manual

Omron
Omron K6CM series User manual

Omron
Omron Peak-Air PF9940 User manual

Omron
Omron K6PM-TH User guide

Omron
Omron K3NX User manual

Omron
Omron H7CX-R11-N User manual

Omron
Omron H7E User manual

Omron
Omron K6CM series User guide

Omron
Omron M16 - User manual