Omron E5AZ User manual

Digital Temperature Controller
User's ManualUser's Manual
E5AZ
E5EZ
E5AZ
E5EZ
E5AZ
E5EZ
Cat. No. H205-E1-01

E5AZ/E5EZ Digital Temperature
Controller
User’s Manual
Produced September 2007

iv

v
Preface The compact E5AZ/E5EZ Temperature Controller allows the user to carry out
the following:
• Depth of only 78 mm.
• Select from many types of temperature, infrared temperature sensor and
analog input
• Select heating/cooling control in addition to standard control
• Select AT (auto-tuning) and ST (self-tuning) as tuning functions
• Use multi-SP and the run/stop function according to event input
• Use optional functions when option board E53-AZM is mounted along
with option units.
• Use the HBA (heater burnout alarm) function (when option unit E53-AZH
is fitted)
• Use the communications function (when option communications unit E53-
AZ01 or E53-AZ03 is fitted)
• The E5AZ/E5EZ conforms to UL/CSA/IEC safety standards and EMC
standards.
This User’s Manual describes how to use the E5AZ/E5EZ.
Before using your E5AZ/E5EZ, thoroughly read and understand this manual
in order to ensure correct use.
Also, store this manual in a safe place so that it can be retrieved whenever
necessary.
Note For an additional description of the communications function, also refer to the
E5AZ/E5EZ/E5EZ-PRR/E5CZ Digital Temperature Controllers Communica-
tions User’s Manual (Cat. No. H204).
Visual Aids
The following headings appear in the left column of the manual to help you locate different types of
information.
Note Indicates information of particular interest for efficient and convenient opera-
tion of the product.
1,2,3... 1. Indicates lists of one sort or another, such as procedures, checklists, etc.
OMRON, 2007
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, o
r
by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission o
f
OMRON.
No patent liability is assumed with respect to the use of the information contained herein. Moreover, because OMRON is con-
stantly striving to improve its high-quality products, the information contained in this manual is subject to change without
notice. Every precaution has been taken in the preparation of this manual. Nevertheless, OMRON assumes no responsibility
for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in
this publication.

vi
Read and Understand this Manual
Please read and understand this manual before using the product. Please consult your OMRON
representative if you have any questions or comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a
period of one year (or other period if specified) from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-
INFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE
PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR
INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES,
LOSS OF PROFITS OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS,
WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT
LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which
liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS
REGARDING THE PRODUCTS UNLESS OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS
WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT SUBJECT TO
CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the
combination of products in the customer's application or use of the products.
At the customer's request, OMRON will provide applicable third party certification documents identifying
ratings and limitations of use that apply to the products. This information by itself is not sufficient for a
complete determination of the suitability of the products in combination with the end product, machine,
system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not
intended to be an exhaustive list of all possible uses of the products, nor is it intended to imply that the uses
listed may be suitable for the products:
•Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or
uses not described in this manual.
•Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical
equipment, amusement machines, vehicles, safety equipment, and installations subject to separate
industry or government regulations.
•Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR
PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO
ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND INSTALLED
FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any
consequence thereof.

vii
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other
reasons.
It is our practice to change model numbers when published ratings or features are changed, or when
significant construction changes are made. However, some specifications of the products may be changed
without any notice. When in doubt, special model numbers may be assigned to fix or establish key
specifications for your application on your request. Please consult with your OMRON representative at any
time to confirm actual specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when
tolerances are shown.
PERFORMANCE DATA
Performance data given in this manual is provided as a guide for the user in determining suitability and does
not constitute a warranty. It may represent the result of OMRON's test conditions, and the users must
correlate it to actual application requirements. Actual performance is subject to the OMRON Warranty and
Limitations of Liability.
ERRORS AND OMISSIONS
The information in this document has been carefully checked and is believed to be accurate; however, no
responsibility is assumed for clerical, typographical, or proofreading errors, or omissions.

viii
■Definition of Precautionary Information
The following notation is used in this manual to provide precautions required
to ensure safe usage of the product.
The safety precautions that are provided are extremely important to safety.
Always read and heed the information provided in all safety precautions.
The following notation is used.
■Symbols
Safety Precautions
CAUTION Indicates a potentially hazardous situation which, if not
avoided, is likely to result in minor or moderate injury or in
property damage.
Symbol Meaning
Caution
General Caution
Indicates non-specific general cautions, warnings, and
dangers.
Electrical Shock Caution
Indicates possibility of electric shock under specific
conditions.
Prohibition General Prohibition
Indicates non-specific general prohibitions.
Mandatory
Caution
General Caution
Indicates non-specific general cautions, warnings, and
dangers.

ix
■Safety Precautions
Note
1. A SELV circuit is one separated from the power supply with double insulation
or reinforced insulation, that does not exceed 30 V r.m.s. and 42.4 V peak or
60 VDC.
2. A class 2 power supply is one tested and certified by UL as having the current
and voltage of the secondary output restricted to specific levels.
CAUTION
If the output relays are used past their life expectancy, contact
fusing or burning may occasionally occur. Always consider the
application conditions and use the output relays within their rated
load and electrical life expectancy. The life expectancy of output
relays varies considerably with the output load and switching
conditions.
CAUTION - Risk of Fire and Electric Shock
a) This product is UL listed as Open Type Process Control
Equipment. It must be mounted in an enclosure that does not
allow fire to escape externally.
b) More than one disconnect switch may be required to de-
energize the equipment before servicing the product.
c) Signal inputs are SELV, limited energy. (See note 1.)
d) Caution: To reduce the risk of fire or electric shock, do not
interconnect the outputs of different Class 2 circuits. (See note
2.)
Do not touch the terminals while power is being supplied. Doing
so may occasionally result in minor injury due to electric shock.
Be sure to turn OFF the power supply before mounting the option
unit. Not doing so may occasionally result in minor or moderate
injury due to electric shock.
Do not allow pieces of metal, wire clippings, or fine metallic
shavings or filings from installation to enter the product. Doing so
may occasionally result in electric shock, fire, or malfunction.
Do not use the product where subject to flammable or explosive
gas. Otherwise, minor injury from explosion may occasionally
occur.
Never disassemble, modify, or repair the product or touch any of
the internal parts. Minor electric shock, fire, or malfunction may
occasionally occur.

x
CAUTION
Loose screws may occasionally result in fire.
Tighten terminal screws to the specified torque of 0.74 to
0.90 N⋅m.
Unexpected operation may result in equipment damage or
accidents if the settings are not appropriate for the controlled
system. Set the Temperature Controller as follows:
A malfunction in the Temperature Controller may occasionally
make control operations impossible or prevent alarm outputs,
resulting in property damage.
To maintain safety in the event of malfunction of the Temperature
Controller, take appropriate safety measures, such as installing a
monitoring device on a separate line.
Be sure that the platinum resistance thermometer type and the
input type set on the Temperature Controller are the same.

xi
Be sure to observe the following precautions to ensure the safe use of the product.
1. Do not use the product in any of the following environments.
• Places subject to splashing liquid or oil atmosphere
• Places subject to direct sunlight
• Places subject to dust or corrosive gas (in particular, sulfide gas and
ammonia gas)
• Places subject to intense temperature change
• Places subject to icing and condensation
• Places subject to vibration and large shocks
• Places directly subject to heat radiated from heating equipment.
2. To reduce the risk of fire or electric shock, install the Temperature Control-
ler in a controlled environment relatively free of contaminants.
3. Use and store the product within the rated temperature and humidity rang-
es. Group-mounting two or more Temperature Controllers, or mounting
Temperature Controllers above each other may cause heat to build up in-
side the Temperature Controllers, which will shorten their service life. In
such a case, use forced cooling by fans or other means of air ventilation to
cool down the Temperature Controllers.
4. To allow heat to escape, do not block the area around the product. Do not
block the ventilation holes on the product.
5. Use the specified size (M3.5, width of 7.2 mm or less) crimped terminals
for wiring.
6. To connect bare wires to the terminal block, use copper braided or solid
wires with a gage of AWG24 to AWG14 (equal to a cross-sectional area of
0.205 to 2.081 mm2). (The stripping length is 5 to 6 mm.) Up to two wires
of the same size and type, or two crimp terminals can be inserted into a
single terminal.
7. Be sure to wire properly with correct polarity of terminals. Do not wire any
of the I/O terminals incorrectly.
8. Do not wire the terminals that are not used.
9. The voltage output (control output) is not electrically isolated from the in-
ternal circuits. When using a grounded temperature sensor, do not connect
any of the control output terminals to ground.Otherwise unwanted current
paths will cause measurement errors.
10. To avoid inductive noise, keep the wiring for the Temperature Controller's
terminal block away from power cables carrying high voltages or large cur-
rents. Also, do not wire power lines together with or parallel to Temperature
Controller wiring. Using shielded cables and using separate conduits or
ducts is recommended. Attach a surge suppressor or noise filter to periph-
eral devices that generate noise (in particular, motors, transformers, sole-
noids, magnetic coils or other equipment that have an inductance
component). When a noise filter is used at the power supply, first check the
voltage or current, and attach the noise filter as close as possible to the
temperature controller.Allow as much space as possible between the Tem-
perature Controller and devices that generate powerful high frequencies
(high-frequency welders, high-frequency sewing machines, etc.) or surge.
11. Use the product within the rated load and power supply.
Precautions for Safe Use

xii
12. Use a switch, relay, or other contact so that the power supply voltage
reaches the rated voltage within 2 seconds. If the applied voltage is in-
creased gradually, the power supply may not be reset or malfunctions may
occur.
13. When using PID operation (self-tuning), turn ON the power supply to the
load (e.g., heater) at the same time or before turning the power supply to
the Temperature Controller ON. If power is turned ON for the Temperature
Controller before turning ON power supply to the load, self-tuning will not
be performed properly and optimum control will not be achieved.
14. Design the system (e.g., control panel) to allow for the 2 seconds of delay
required for the Temperature Controller's output to stabilize after the power
is turned ON.
15. A switch or circuit breaker should be provided close to this unit. The switch
or circuit breaker should be within easy reach of the operator, and must be
marked as a disconnecting means for this unit.
16. Approximately 30 minutes is required for the correct temperature to be dis-
played after turning the power supply to the Temperature Controller ON.
Turn the power supply ON at least 30 minutes prior to starting control op-
erations.
17. The output may turn OFF when shifting to certain levels. Take this into con-
sideration when performing control.
18. When turning OFF the power, use a switch or relay to ensure the voltage
decreases immediately. Incorrect operation and data storage errors may
occur if the voltage decreases slowly.
19. When extending the thermocouple lead wires, always use compensating
conductors suitable for the type of thermocouple. Do not extend the lead
wires on a platinum resistance thermometer. Use only low-resistance wire
(5 Ωmax. per line) for lead wires and make sure that the resistance is the
same for all three wires.
20. Make sure that any option units are installed correctly. Do not remove the
internal PCB when installing an option unit.
21. When drawing out the Temperature Controller from the case, do not apply
force that would deform or alter the Temperature Controller.
22. When drawing out the Temperature Controller from the case to replace the
Temperature Controller, check the status of the terminals. If corroded ter-
minals are used, contact faults with the terminals may cause the tempera-
ture inside the Temperature Controller to increase, possibly resulting in fire.
If the terminals are corroded, replace the rear case as well.
23. When inserting the Temperature Controller into the case, do not force it
into the case. Doing so will damage internal parts.
24. When drawing out the Temperature Controller from the case, turn the pow-
er supply OFF first, and absolutely do not touch the terminals or electronic
components or apply shock to them. When inserting the Temperature Con-
troller, do not allow the electronic components to come into contact with the
case.
25. Static electricity may damage internal components. Always touch ground-
ed metal to discharge any static electricity before handling the Tempera-
ture Controller. When drawing out the Temperature Controller from the
case, do not touch the electronic components or patterns on the board with

xiii
your hand. Hold the Temperature Controller by the edge of the front panel
when handling it.
26. The EEPROM has a limited write life. When overwriting data frequently,
e.g., via communications, use RAM Mode.
27. Do not use paint thinner or similar chemical to clean with. Use standard
grade alcohol.
28. Use tools when separating parts for disposal. Contact with the sharp inter-
nal parts may cause injury.

xiv
Service Life
1. Use the product within the following temperature and humidity ranges:
Temperature: −10 to 55°C (with no icing or condensation)
Humidity: 25% to 85%
If the product is installed inside a control board, the ambient temperature
must be kept to under 55°C, including the temperature around the product.
2. The service life of electronic devices like Temperature Controllers is deter-
mined not only by the number of times the relay is switched but also by the
service life of internal electronic components. Component service life is af-
fected by the ambient temperature: the higher the temperature, the shorter
the service life, and the lower the temperature, the longer the service life.
Therefore, the service life can be extended by lowering the temperature of
the Temperature Controller.
3. When two or more Temperature Controllers are mounted horizontally close
to each other or vertically next to one another, the internal temperature will
increase due to heat radiated by the Temperature Controllers and the ser-
vice life will decrease. In such a case, use forced cooling by fans or other
means of air ventilation to cool down the Temperature Controllers. When
providing forced cooling, however, be careful not to cool down the termi-
nals sections alone to avoid measurement errors.
Measurement Accuracy
1. When extending or connecting the thermocouple lead wire, be sure to use
compensating wires that match the thermocouple types.
2. When extending or connecting the lead wire of the platinum resistance
thermometer, be sure to use wires that have low resistance and keep the
resistance of the three lead wires the same.
3. Mount the product so that it is horizontally level.
4. If the measurement accuracy is low, check to see if input shift has been set
correctly.
Operating Precautions
1. It takes approximately two seconds for the outputs to turn ON from after
the power supply is turned ON. Due consideration must be given to this
time when incorporating Temperature Controllers in a sequence circuit.
2. When using self-tuning, turn ON power for the load (e.g., heater) at the
same time as or before supplying power to the Temperature Controller. If
power is turned ON for the Temperature Controller before turning ON pow-
er for the load, self-tuning will not be performed properly and optimum con-
trol will not be achieved.
3. When starting operation after the Temperature Controller has warmed up,
turn OFF the power and then turn it ON again at the same time as turning
ON power for the load. (Instead of turning the Temperature Controller OFF
and ON again, switching from STOP mode to RUN mode can also be
used.)
4. Avoid using the Controller in places near a radio, television set, or wireless
installation. These devices can cause radio disturbances which adversely
affect the performance of the Controller.
Precautions for Correct Use

xv
The manuals related to the E5AZ/E5EZ are configured as shown in the following tables. Refer to these
manuals as required.
Related Manuals
Name Cat. No. Contents
E5AZ/E5EZ Digital Temperature Controller User’s
Manual H205
(This
manual)
Describes the following information on the E5AZ/E5EZ.
•Overview and features
•Basic specifications
•System design
•System configuration
•Mounting and wiring
•Maintenance
E5AZ/E5EZ/E5EZ-PRR/E5CZ Digital Temperature
Controllers Communications User’s Manual H204 Describes the CompoWay/F and SYSWAY communica-
tions commands used with E5@Z Digital Temperature
Controllers.

xvi
Conventions Used in This Manual
Model Notations
“E5AZ/E5EZ” is used when the information being provided applies to all E5@Z-@3@@ Digital Temper-
ature Controllers. The notation used in the manual for information that is restricted by the model is
given in the following table.
Note The E5AZ/E5EZ provides optional functions when an E53-AZM option board
is mounted along with one or two (E53-AZH and another) option units.
Meanings of Abbreviations
The following abbreviations are used in parameter names, figures and in text explanations. These
abbreviations mean the following:
Note “EU” stands for Engineering Unit. EU is used as the minimum unit for engi-
neering units such as °C, m, and g.
The size of EU varies according to the input type. For example, when the input
temperature setting range is –200 to +1300°C, 1 EU is 1°C, and when the
input temperature setting range is –20.0 to +500.0°C, 1 EU is 0.1°C.
In the case of analog input, the size of EU varies according to the decimal
point position of the scaling setting, and 1 EU becomes the minimum scaling
unit.
How to Read Display Symbols
The following tables show the correspondence between the symbols displayed on the displays and
alphabet characters.
Notation Optional function
E53-AZM Option board is mounted along with one or two of the following option units.
E53-AZH Heater burnout alarm option unit
E53-AZ01 RS-232C communications option unit
E53-AZ03 RS-485 communications option unit
E53-AZB Event input option unit
Symbol Term
PV Process value
SP Set point
SV Set value
AT Auto-tuning
ST Self-tuning
EU Engineering unit (See note.)
ABCDEFGHI JKLM
NOPQRSTUVWXYZ

xvii
SECTION 1
Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1-1 Names of Parts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1-2 I/O Configuration and Main Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1-3 Setting Level Configuration and Key Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1-4 Communications Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
SECTION 2
Preparations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2-1 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2-2 Wiring Terminals. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
2-3 Requests at Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
SECTION 3
Basic Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
3-1 Initial Setting Examples. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
3-2 Setting the Input Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
3-3 Selecting the Temperature Unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
3-4 Selecting PID Control or ON/OFF Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
3-5 Setting Output Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
3-6 Setting the Set Point (SP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
3-7 Using ON/OFF Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
3-8 Determining PID Constants (AT, ST, Manual Setup) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
3-9 Alarm Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
3-10 Using Heater Burnout Alarm (HBA). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
3-11 Requests during Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
SECTION 4
Applications Operations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
4-1 Shifting Input Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
4-2 Alarm Hysteresis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
4-3 Setting Scaling Upper and Lower Limits (for Analog Inputs) . . . . . . . . . . . . . . . . . . . . . . . 59
4-4 Executing Heating/Cooling Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
4-5 Using Event Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
4-6 Setting the SP Upper- and Lower-Limit Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
4-7 Using the SP Ramp Function (to Limit the SP Change Rate). . . . . . . . . . . . . . . . . . . . . . . . 69
4-8 Moving to the Advanced Function Setting Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
4-9 Using the Key Protect Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .72
TABLE OF CONTENTS

xviii
TABLE OF CONTENTS
SECTION 5
Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
5-1 Conventions Used in This Section. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
5-2 Protect Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
5-3 Operation Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
5-4 Adjustment Level. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
5-5 Initial Setting Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
5-6 Advanced Function Setting Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
5-7 Communications Setting Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Index. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
Revision History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141

xix
About this Manual:
Please read this manual carefully and be sure you understand the information provided before
attempting to install or operate the E5AZ/E5EZ Temperature Controller. Be sure to read the precau-
tions provided in the following section.
Section 1 describes the features, names of parts and typical functions.
Section 2 describes installation and wiring.
Section 3 describes basic control examples.
Section 4 describes advanced functions to fully use E5AZ/E5EZ.
Section 5 describes the parameters of the E5AZ/E5EZ.

xx

1
SECTION 1
Introduction
This section introduces the features, components, and main specifications of the E5AZ/E5EZ Digital Temperature
Controllers.
1-1 Names of Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1-1-1 Front Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1-1-2 Meaning of Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1-1-3 Using the Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1-2 I/O Configuration and Main Functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1-2-1 I/O Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1-2-2 Basic Model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1-2-3 Main Functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1-3 Setting Level Configuration and Key Operations. . . . . . . . . . . . . . . . . . . . . . 6
1-3-1 Selecting Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1-3-2 Fixing Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1-4 Communications Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
This manual suits for next models
1
Table of contents
Other Omron Temperature Controllers manuals

Omron
Omron E5ZE-8 D1 B-V2 User manual

Omron
Omron E5AJ-A2HB User manual

Omron
Omron E5 J Series User manual

Omron
Omron E5CSL User manual

Omron
Omron E5CN User manual

Omron
Omron E5*C-B Series User manual

Omron
Omron E5 D Series Use and care manual

Omron
Omron E5AN Use and care manual

Omron
Omron E5CD-800 User manual

Omron
Omron E5CD-B User manual

Omron
Omron E5C-T Series Use and care manual

Omron
Omron CJ Series User manual

Omron
Omron E5AX-P Series User manual

Omron
Omron E5CN User manual

Omron
Omron E5C2 User manual

Omron
Omron E5AN-H User manual

Omron
Omron EJ1N-TC4 User manual

Omron
Omron E5ZN Series User manual

Omron
Omron EJ1G User manual

Omron
Omron E5AC-T User manual