Omron E5 J Series User manual

1
Temperature Controller E5jJ
Fuzzy Self-tuning Temperature
Controller with Advanced PID (2-PID)
Control
DIN-size:
96 x 96 mm (E5AJ), 72 x 72 mm (E5BJ),
48 x 48 mm (E5CJ), 48 x 96 mm (E5EJ)
Fuzzy
self-tuning and
Auto-tuning optimize temper
-
ature control.
Minimal user setup.
Dual set point, selectable by external input.
RUN/STOP operation (E5AJ/E5EJ) by external
input.
Front panel protection conforming to IP54 on
E5AJ/E5EJ/E5BJ (IP66/NEMA4 with optional
cover). E5CJ conforms to IP50 (IP66/NEMA4
with
optional cover).
Serial communications models (E5AJ/E5EJ).
Relay, voltage or linear outputs.
Conforms to international EMC and safety
standards.
RC
Ordering Information
Temperature Controllers
E5AJ/EJ/BJ
Item Standard
type
T
wo alarm
ttt t
Communications type
Communications
Board add-on type
outputs; two event
inputs (with heater
burnout alarm)
RS-232C RS-422 RS-485
Model E5AJ-A2HB
E5EJ-A2HB
E5BJ-A2HB
E5AJ-A2H01
E5EJ-A2H01 E5AJ-A2H02
E5EJ-A2H02 E5AJ-A2H03
E5EJ-A2H03 E5AJ-A2HM
E5EJ-A2HM
Note: 1.
Be sure to specify Control Output Unit and Current T
ransformer as necessary when ordering.
Example: E5AJ-A2HB, Relay Output Unit E53-R, Current T
ransformer E54-CT1
2.
The heater burnout alarm is not available when the E5
j
J is used with Linear Output Units.
3. Ask
your OMRON representative for the
E5AJ/E5EJ Communications
Manual (Z102)
when using a model incorporating a commu
-
nications
function.
4. Be
sure to specify Communications Boards as necessary when ordering E5AJ/EJ-A2HM Communications Board add-on types.
Control
Output Unit (Required for E5AJ, E5BJ, and E5EJ)
Type
Relay Output Unit
V
oltage Output Unit
(for SSR drive)
Current Output Unit
Model E53-R E53-Q E53-C3
Communications Boards
When communications capability is required, mount one of the following Boards on the E5AJ-A2HM or E5EJ-A2HM.
Communications RS-232C RS-422 RS-485
Model E53-J01 E53-J02 E53-J03
Note:
For details, refer to the
E5AJ/E5EJ Communications Manual (Z102)
.

E5jJE5jJ
2
E5CJ
Item
Standard type Single-function type
T
wo alarm points; one event input
T
wo alarm points; without event
input W
ithout alarm and event input
Relay
output Voltage
output Current
output Relay
output Voltage
output Current
output Relay
output Voltage
output Current
output
Model E5CJ-R2HB E5CJ-Q2HB E5CJ-C2B E5CJ-R2 E5CJ-Q2 E5CJ-C2 E5CJ-R E5CJ-Q E5CJ-C
Note:
Be sure to specify Current T
ransformer as necessary when ordering E5CJ-R2HB and E5CJ-Q2HB.
The heater burnout alarm is not available for models other than E5CJ-R2HB and E5CJ-Q2HB.
Current Transformers (CT) (Order Separately)
Hole
diameter
5.8 mm 12.0 mm
Model E54-CT1 E54-CT3
Note:
No CT is required unless the heater burnout alarm function is used.
Terminal Covers (Order Separately)
Model E5AJ E5EJ E5CJ
Connectable
models
E53-COV02 E53-COV03 E53-COV04
Temperature Ranges
Input
(switch selectable)
Temperature-resistance
thermometer Thermocouple
()
JPt100
Platinum
resistance
thermometer
Pt100
Platinum
resistance
thermometer
K
(CA)
Chromel vs.
alumel
J (IC)
Iron vs.
constantan
T (CC)
Copper vs.
constantan
L
Iron vs.
constantan
U
Copper vs.
constantan
N
Nichrosil
vs. nisil
Built-in
switch
Default set-
ting; 2(K)
T
emperature range
1,300
900
800
600
400
300
200
100
0
–100
–200
°C
–199.9
650.0
–199.9
650.0
–200
1,300
–100
850
–199.9
400.0
–100
850
–199.9
400.0
–200
1,300
Setting
No. 0 1 2 3 4 5 6 7
Minimum
setting unit
Target
value 0.1°C 1°C 1°C 0.1°C 1°C 0.1°C 1°C
g
Alarm 0.1°C 1°C 1°C 0.1°C 1°C 0.1°C 1°C
Note:
Default setting: 2 (K).

E5jJE5jJ
3
Specifications
Ratings
Supply
voltage
100 to 240 V
AC, 50 or 60 Hz 24 V AC/DC, 50 or 60 Hz
Operating voltage range
85% to 1
10% of rated supply voltage
Power consumption
E5AJ/E5EJ:
10 V
A (at 100 V
AC) to 14 V
A (at 240 V
AC)
E5BJ/E5CJ:
10 V
A (at 100 V
AC) to 12 V
A (at 240 V
AC)
10 V
A (at 24 V
AC)
6 W (at 24 VDC)
Input
Thermocouple (K/J/T/L/U/N) or platinum resistance thermometer (JPt100/Pt100), selectable
Current T
ransformer input Connect an exclusive Current T
ransformer unit (E54-CT1 or E54-CT3)
Control
tt
E5AJ/E5BJ/E5EJ
Replaceable Output Unit (sold separately)
Co o
output E5CJ
Relay output
SPST
-NO, 3 A at 250 V
AC (resistive load)
5CJ
V
oltage output
20 mA at 12 VDC (with short-circuit protection)
Current output
4 to 20 mA DC with a load of 600
Ω
max. and a resolution of approx. 2600
Control mode
ON/OFF or PID control (2-PID) with fuzzy self-tuning and auto-tuning
Alarm output E5AJ/E5EJ:
Relay output, 2 independent SPST
-NO contacts; 3 A, 250 VAC
E5BJ/E5CJ:
Common 2 outputs, 2 independent SPST
-NO contacts;
E5CJ: 1 A, 250 VAC; E5BJ: 3 A, 250 V
AC
Setting method
Digital setting via Up and Down Keys
Indication method
Digital indications
Character heights:
E5AJ: PV
: 15 mm, SV
: 10.5mm
E5EJ/E5BJ: PV
: 14 mm, SV
: 9.5 mm
E5CJ: PV
: 12 mm, SV
: 8 mm
Event input
Contact input:
ON: 1 kΩ
max., OFF: 100 k
Ω
min.
No-contact input: ON: residual voltage: 3 V max., OFF: leakage current: 1 mA max.
Other functions
Key protection
Direct and reverse output selection
Multiple SP (four set points; up to four set points available on E5AJ/E5EJ by engineering level)
RUN/ST
OP (selected via external terminals) (E5AJ, E5EJ)
Heater burnout detection
Note: It
is possible to add other functions from
the engineering level. Refer to the
E5
j
J Operation Manual
, obtainable from your OMRON
representative,
for details.

E5jJE5jJ
4
Characteristics
Indication
accuracy (see note 1)
(±
0.5% of indication value or
±1°
C, whichever greater)
±
1 digit max.
Hysteresis 0.1°
to 999.9
°C/°
F (in units of 0.1
°C/°
F) (during ON/OFF control action)
Proportional band
0.1°
to 999.9
°C/°
F (in units of 0.1
°C/°F)
Integral (reset) time
0 to 3,999 s (in units of 1 s)
Derivative (rate) time
0 to 3,999 s (in units of 1 s)
Alarm output setting range
Thermocouple (K/J/L/N): –1,999
°
to 9,999
°C/°
F (in units of 1
°C/°F)
Platinum resistance thermometer
, thermocouple (T/U): –199.9
°
to 999.9
°C/°F
(in units of 0.1
°C/°F)
Control period
Pulse output: 1 to 99 s (in units of 1 s)
Sampling period
500 ms
Output refresh time
500 ms
Display refresh time 500 ms
Insulation resistance (see note 2)
20 M
Ω
min. (at 500 VDC)
Dielectric strength
2,000 V
AC, 50/60 Hz for 1 min between terminals of dif
ferent polarities
V
ibration resistance
Malfunction:
10 to 55 Hz, 9.8 m/s
2
(1G) for 10 min each in X, Y, and Z directions
Destruction:
10 to 55 Hz, 19.6 m/s
2
(2G) for 2 hrs each in X, Y
, and Z directions
Shock resistance
Malfunction:
196 m/s
2
(20G), 3 times each in 6 directions
(98 m/s
2
(10G) applied to the relay)
Destruction:
294 m/s
2
(30G), 3 times each in 6 directions
Life expectancy
Mechanical:
10,000,000 operations (relay alarm output)
Electrical:
100,000 operations (relay alarm output)
Ambient temperature
Operating: –10°
C to 55
°
C (with no icing)
Storage: –25°
C to 65
°
C (with no icing)
Ambient humidity
Operating: 35% to 85%
Memory protection
Non-volatile memory (number of write operations: 100,000)
Enclosure ratings
Front panel:
E5AJ/E5EJ/E5BJ: IEC standard IP54
E5CJ: IEC standard IP50 (see note 3)
Rear case:
IEC standard IP20
Terminals:
IEC standard IP00
Weight
E5AJ: Approx. 360 g, E5EJ: Approx. 280 g, E5BJ: Approx. 240 g, E5CJ: Approx. 170 g;
Mounting adapter for E5CJ: approx. 10 g;
Mounting bracket for E5AJ, E5BJ, and E5EJ: Approx. 65 g
EMC Emission Enclosure: EN55011 Group 1 class A
Emission AC Mains:
EN55011 Group 1 class A
Immunity ESD:
EN61000-4-2:
4-kV contact discharge (level 2)
8-kV air discharge (level 3)
Immunity RF-interference:
ENV50140:
10 V/m (amplitude modulated,
80 MHz to 1 GHz) (level 3)
10 V/m (pulse modulated, 900 MHz)
Immunity Conducted Disturbance:
ENV50141:
10 V (0.15 to 80 MHz) (level 3)
Immunity Burst:
EN61000-4-4:
2-kV power-line (level 3)
2-kV I/O signal-line (level 4)
Approved standards
UL1092, CSA C22.2 No. 142
Conforms to EN50081-2, EN50082-2, EN61010-1 (IEC1010-1) (see note 4)
Conforms to VDE0106/part 100 (Finger Protection), when the separately-ordered terminal
cover is mounted.
Note: 1. The
indication accuracy of the K, T
, and N thermocouples at a temperature of –100
°
C or less is
±2°C±
1 digit maximum. The indica
-
tion
accuracy of the U thermocouple at any temperature is
±2°C±
1 digit maximum.
2.
The insulation resistance was measured with a Control Output Unit attached.
3.
The model numbers of the exclusive watertight covers conforming to IP66, NEMA4 are as follows:
For E5AJ: Y92A-96N; For E5BJ: Y92A-72N; For E5CJ: Y92A-48N; For E5EJ: Y92A-49N
4.
Basic insulation is between the input and output.

E5jJE5jJ
5
Output Unit Ratings
No
event input is photoelectrically insulated from the voltage or current output.
Relay Output Unit (see note 2)
E53-R SPDT
, 5 A at 250 V
AC (resistive load)
Voltage Output Unit (for driving SSR) E53-Q
NPN, 40 mA at 12 VDC (with short-circuit protection)
E53-Q3
NPN, 20 mA at 24 VDC (with short-circuit protection)
E53-Q4 PNP
, 20 mA at 24 VDC (with short-circuit protection)
Linear Output Unit (see note 1 and 3)
E53-C3
4 to 20 mA; DC: 600
Ω
max.; resolution: approx. 2,600
E53-C3D
0 to 20 mA; DC: 600
Ω
max.; resolution: approx. 2,600
E53-V34
0 to 10 V
; DC: 1 kΩ
min.; resolution: approx. 2,600
E53-V35
0 to 5 V
; DC: 1 kΩ
min.; resolution: approx. 2,600
Note: 1.
The current output is not a transmission output.
The heater burnout alarm cannot be used with the E53-C Current Output Units.
2.
The contact configuration will be SPST
-NO when used with the E5
jJ.
3.
No heater burnout alarm is available if the Linear Output Unit is used with the E5
jJ.
Heater Burnout Alarm
Max.
heater current
Single-phase 50 A V
AC (see note 1)
Heater current value display accuracy
±
5% FS
±
1 digit max.
Heater burnout alarm setting range
0.1 to 49.9 A (in units of 0.1 A) (see note 2)
Min. detection ON time
190 ms (see note 3)
Note: 1. Use the K2CU-FjjA-j
GS (with gate input terminals) for the detection of three-phase heater burnout.
2.
The heater burnout alarm is always OFF if the alarm is set to 0.0 A and always ON if the alarm is set to 50.0 A.
3.
No heater burnout detection or heater current value measurement is possible if the control output is ON for less than 190 ms.
Current Transformer Ratings
Max.
continuous heater current
50 A
Dielectric strength
1,000 V
AC
V
ibration resistance
50 Hz, 98 m/s
2(10G)
Weight
E54-CT1: Approx. 1
1.5 g; E54-CT3: Approx. 50 g
Accessories (E54-CT3 only)
Contact: 2; Plug: 2
Output Unit Characteristics
Relay
unit life expectancy
Mechanical:
10,000,000 operations min.
Electrical:
100,000 operations min.
Communications (E5AJ/E5EJ)
Protocol RS-232C,
RS-422, RS-485
T
ransmission method
Half-duplex
Synchronization method Start-stop synchronization (asynchronous method)
Baud rate
1,200/2,400/4,800/9,600/19,200 bps
T
ransmission code
ASCII
Communications W
rite to T
emperature Controller
Set point, alarm value, remote/local selection etc. (proportional band,
integral time, derivative time)
Read from Temperature Controller
Process value, output value, set point, alarm value, heater current
value, initial status, etc. (proportional band, integral time, derivative
time)
Note: 1.
The maximum total cable length must not exceed the following limits.
RS-422: 500 m, RS-232C: 15 m, RS-485: 500 m
2. The
number of connecting Units including the host computer via RS-485 is 32. The number of connecting Units via RS-422 is 32.

E5jJE5jJ
6
Nomenclature
E5CJ
Lights
when the control out
-
put is ON. In current output
mode, however
, the output
indicator will not be lit.
Set V
alue (SV) Display
Displays the set temperature
and set value of each setting
item.
Output Indicator
Level Key
Press for 1 second minimum to
change levels to set dif
ferent
groups of parameters.
Display Key
Press to shift the display
to the next parameter
.
Process V
alue (PV) display
Displays the process value, the charac-
ter for the parameter being displayed
on the SV display
, and error messages.
Heater Burnout Indicator
Lights when a heater burnout is
detected and stays lit until reset.
Alarm 1 Indicator
Lights when alarm
output 1 is ON.
Alarm 2 Indicator
Lights when alarm
output 2 is ON.
Down and Up Keys
Press to increase or decrease the value on the SV display
. Successively
increases or decreases the value when held down for 1 s or more. The
value set will be ef
fective automatically in 2 s or immediately after pressing
the Display Key or Level Key
.
Note:
There are models that do not incorporate
HB, ALM1, and ALM2 indicators.
E5AJ/E5BJ/E5EJ
Lights when the control out
-
put is ON. In current output
mode, however
, the output
indicator will not be lit.
Lights when the T
emperature
Controller is not in operation.
The E5BJ or any other E5
jJ
model with a communications
function does not incorporate a
stop indicator
.
Heater Burnout Indicator
Output Indicator
Level Key
Press for 1 second mini
-
mum to change levels to
set dif
ferent groups of
parameters.
Display Key
Press to shift the display
to the next parameter
.
Stop Indicator
Process V
alue (PV) display
Displays the process value, the
character for the parameter being
displayed on the SV display
, and
error messages.
Set V
alue (SV) Display
Displays the set temperature
and set value of each setting
item.
Alarm 1 Indicator
Lights when alarm
output 1 is ON.
Alarm 2 Indicator
Lights when alarm output
2 is ON.
Lights when a heater burnout is
detected and stays lit until reset.
Down and Up Keys
Press to increase or decrease the value on the SV display
.
Successively increases or decreases the value when held down
for 1 s or more. The value set will be ef
fective automatically in 2 s
or immediately after pressing the Display Key or Level Key
.

E5jJE5jJ
7
Operation
NOTICE: Always turn of
f the power supply to the T
emperature Controller before changing any switch settings.
Settings
E5CJ
Remove
the internal mechanism from the
housing. Pull out the inter
-
nal mechanism while pressing the hook at the bottom of the front
panel.
Internal Switches
E5CJ
Top
V
iew
Bottom View
Note: A
model with no alarm does not
incorporate
an
alarm mode selector
.
Alarm mode selector 2
(ALM2) (see note)
Alarm mode selector 1
(ALM1) (see note)
Input type selector
(INPUT)
Key protection switch
(PROTECT)
Function selector
(FUNCTION)
E5AJ/E5BJ/E5EJ
1. Remove the internal mechanism from the housing. Pull out
the
internal mechanism while pressing the hook at the bottom
of
the front panel.
Hook Pull out the internal mechanism
while holding down the hook with
your finger.
When inserting the internal
mechanism back into the case,
push the internal mechanism into
the case until it clicks into place.
2. Connect a Control Output Unit to the vacant socket on the
printed
circuit board as shown below
.
Mount the Control Output Unit
with the mark facing the direc-
tion indicated by the arrow.
Be sure to secure the output
unit with the provided fixture.
To
remove a Control Output Unit, push it up with the tip of a
flat-blade
screwdriver
as shown below
.
Flat-blade
screwdriver
Internal Switches
E5AJ
T
op V
iew Alarm mode selector 2
(ALM2)
Alarm mode selector 1
(ALM1)
Key protection switch
(PROTECT)
Input type selector
(INPUT)
Function selector
(FUNCTION)
Bottom
V
iew

E5jJE5jJ
8
Input type selector
(INPUT)
Alarm mode selector 2
(ALM2)
Alarm mode selector 1
(ALM1)
Function selector
(FUNCTION)
Key protection switch
(PROTECT)
E5BJ
Top
V
iew
Bottom View
Alarm mode selector 2
(ALM2)
Key protection switch
(PROTECT)
Alarm mode selector 1
(ALM1)
Input type selector
(INPUT)
Function selector
(FUNCTION)
E5EJ
Top
V
iew
Bottom View
Input Type Selector (INPUT)
This
selector selects the temperature sensor to be used. It is facto
-
ry-set
to position 2 to designate a K-type (chromel-alumel thermo
-
couple)
temperature sensor
. The following table lists the other pos
-
sible
settings for temperature sensors. Refer to temperature
range
charts
under
Ordering Information
for further information.
Switch
tti
Temperature
d
T
emperature range
Sc
setting
e peaue
sensor code
°C°F
0, 8
JPt100 –199.9to650.0 –199.9 to 999.9
1, 9
Pt100 –199.9to650.0 –199.9 to 999.9
2K –200 to1,300 –300 to 2,300
3J –100 to 850 –100 to 1,500
4T –199.9to400.0 –199.9 to 700.0
5L –100 to 850 –100 to 1500
6U –199.9to400.0 –199.9 to 700.0
7N –200 to1,300 –300 to 2,300
Note: JPt100:
139.16
Ω
at 100
°C
Pt100:
138.50
Ω
at 100
°C
Temperature Control in Fahrenheit
1. After setting all internal switch settings, set pin number 4 of
the
function switch to ON. This pin is normally set to OFF
.
2. Insert
the internal mechanism into the housing and turn on
the
Temperature
Controller
.
3. du will be displayed. Then press the Up Key to change the
set value display into Fahrenheit “
f.”
4. Turn
of
f the power 2 s after the set value display has changed
to
Fahrenheit.
5. Remove the internal mechanism from the housing, set pin
number
4 of the function switch to OFF
, replace it and turn on
the
power
.
Function Selector (FUNCTION)
1234
O
N
ON
OFF
The
DIP switch sets the operating parameters listed in the
following
table.
All pins are factory-set to OFF
.
Function selector pin
number 1 2 3 4
Output
operation
Normal
(see note 1)
ON --- --- ---
p
Reverse (see
note 1)
OFF --- --- ---
Control
d
ON/OFF --- ON --- ---
Co o
mode Advanced
PID --- OFF --- ---
PID
tuning
mode
With
auto-tuning
(see note 2)
--- --- ON
(see
note
3)
---
With fuzzy
self-tuning --- --- OFF
(see
note
3)
---
Level Engineering
level --- --- --- ON
Normal
operation --- --- --- OFF
Factory
setting
OFF OFF OFF OFF
Note: 1. For heating applications, use the reverse operation
mode. For cooling applications use the normal opera-
tion
mode. (In other cases, select the desired setting.)
2. To start auto-tuning, press the Level and Display Keys
simultaneously, for 1 s or longer to start auto-tuning.
During auto-tuning, the set value display flashes. (The
display
will stop flashing after tuning is finished.)
3. If the control mode is ON/OFF, pin 3 can be set ON or
OFF.
(Pin 3 is not important
in case of ON/OFF control.)

E5jJE5jJ
9
Alarm Mode Selectors (ALM1, ALM2)
Alarm
modes, listed
in the following table, can be selected using this switch. The switch is factory-set to position 2, i.e., the upper-limit alarm
mode.
Switch Mode Alarm output
Setting range
setting
Alarm operation
When X is positive
When X is negative
0
No alarm
OFF ---
1Upper- and lower-limit alarm
(deviation) XX
ON
OFF SP
Always ON –1999
to 9999, or –199.9 to 999.9
(The decimal position varies with
the
input type.)
2
Upper-limit alarm (deviation)
X
SP
X
SP
3
Lower-limit alarm (deviation)
X
SP
X
SP
4Upper- and lower-limit alarm
(deviation) XX
SP
Always OFF
5Upper- and lower-limit alarm with
standby
sequence (deviation)
XX
SP
Always OFF
6
Upper-limit alarm with standby
sequence (deviation)
X
SP
X
SP
7
Lower-limit alarm with standby
sequence (deviation)
X
SP
X
SP
8
Absolute-value upper-limit alarm
0°C/°F
X
0°C/°F
X
9
Absolute-value lower-limit alarm
0°C/°F
X
0°C/°F
X
Deviation Alarm
If
the alarm mode selector is set to a number between 1 to 7, alarm
values
are set to the width deviated from the set point as shown in
the
following illustration.
Set point (SP)
100°C/°F
Alarm value
10°C/°F
110°C/°F
Absolute Alarm
If
the alarm mode selector is set to 8 or 9, alarm values are set to the
absolute
value based on 0
°C/°
F as shown in the following illustra
-
tion.
0°C/°F
Alarm value
110°C/°F
110°C/°F

E5jJE5jJ
10
Key Protection Switch (PROTECT)
The
key protection switch is factory-set to the OFF position.
SP OFF ALL
T
o write-protect set values, the settings of the protect modes must be changed.
Mode Protection
SP
All set values other than the set point will be write-protected.
The Level Key will not be valid. The Down and Up Keys will not be valid except set point setting.
OFF
No key protection will be valid.
All keys will work normally.
ALL
All set values will be write-protected.
The Level, Down, and Up Keys will not be valid.
Inputting Parameters
The
temperature Controller has two display levels 0 and 1, in which only specific parameters can be set.
Level 0 is the initial level and is auto
-
matically
entered upon power application. T
o change the mode to set or change a dif
ferent
group of parameters, hold down the Level Key for
1 second minimum. The display level mode changes as shown below
. Actual displays vary with models and switch settings. If a display
does
not appear as expected, check your switch settings.
Besides
the functions explained here, the T
emperature Controller incorporates an alarm hysteresis function, set point limit function,
automatic
return
of display
mode function, input shift function, and event input 2 type selection (incorporated by the E5AJ and E5EJ only). Refer to the
E5
j
J
Operation Manual (Z103)
, which can be obtained from your OMRON representative, for details on these functions.
–––––
–––––
Level 0
Power ON
Level 1
Press the Level Key. Press the Level Key.
Process value, set point setting,
alarm 1 and 2
Output value display
, hysteresis, control
period, SP0/SP1 settings, heater current
value display
, heater burnout alarm value,
proportional band, integral time, derivative
time, manual reset value
Level 0
E5CJ
SV
PV
Process
value
(Set point setting)
0
PVModels with alarm
0
al1 (See note 1)
Alarm 1 setting
SV
0
al2
PV
(See note 2)
Alarm 2 setting
SV
Press a
Press a
Press a
Note: 1. Nothing is displayed if ALM1 is set to 0 (i.e., no alarm
function is ON).
2. Nothing is displayed if ALM2 is set to 0 (i.e., no alarm
function is ON).
E5AJ/E5BJ/E5EJ
Process value
0(Set point setting)
Press a
(See note 1)
Alarm 1 setting
(See note 2)
Alarm 2 setting
0
al2
0
Press a
Press a
al1
SV
PV
SV
PV
SV
PV
Note: 1. Nothing is displayed if ALM1 is set to 0 (i.e., no alarm
function is ON).
2. Nothing is displayed if ALM2 is set to 0 (i.e., no alarm
function is ON).

E5jJE5jJ
11
Set Point Setting (
°C or °F)
Use
the Down and UP Keys to set the set point. A model with event
input allows the change of the set point (SP0 or SP1) that has been
selected.
Alarm
1, 2:
al1
,
al2
(
°
C or
°F)
Alarm
values can be set with Down
and Up Keys. The alarm mode is
factory
set to upper-limit alarm (deviation) mode.
The alarm mode can be changed with the alarm mode selector
.
An
alarm value can be set
to the deviation width or absolute value
according
to the alarm mode.
Deviation alarm Absolute-value alarm
Upper- and lower-limit
alarm, upper-limit alarm,
lower-limit alarm, upper-
and lower-limit range alarm
Absolute-value upper-limit
alarm, absolute-value
lower-limit alarm
Set to the width deviated from
the set point.
Set point (SP)
100°C/°F
Alarm value
10°C/°F
Set to the absolute value
based on 0
°C/ °F.
0°C/°F
Alarm value
110°C/°F
Level 1
E5CJ
o
SV
PV
Output
value
Press
a
ON/OFF
control PID control
(Output value display)
1.0
hys
PV
(Hysteresis
setting) 20
cp
PV
(See note)
(Control period setting)
SVSV
Press aPress a
sp0
PV
(Set point 0 setting SP0)SV
Models with event input
0
0
sp1
PV
SV
Press a
Press a
Models with heater burnout alarm
ct
PV
(See note)
(Heater current display)
Current
value
SV
0.0
hb
PV
SV
Press
a
(See note)
(Heater burnout alarm
Set value)
Press a
p
PV
(Proportional band setting)SV 8.0
If the control mode is set to
advanced PID
233
i
PV
SV
Press a
(Integral time setting)
40
d
PV
SV
Press a
(Derivative time setting)
ofr
PV
(Manual reset
value setting)
SV
When I = 0
50.0
Press a
(Set point 1 setting SP1)
Press a
1234
O
N
1234
O
N
1234
O
N
Note: Nothing
is displayed in current output model.

E5jJE5jJ
E5AJ/E5BJ/E5EJ
Output value
Press a
o
(Output value display)
20
Press a
cp
1.0
Press a
hys
0
Press a
spĆ0
Press a
sPĆ1
Press a
ct
0.0
Press a
hb
8.0
Press a
p
233
Press a
i
40
Press a
d
50.0
Press a
ofr
ON/OFF
control
(Hysteresis
setting)
PID control
(Control period setting)
(Models with event input)
(Set point 0 setting SP0)
(Set point 1 setting SP1)
If control output is
current output.
(Heater current
value display)
(Heater burnout
alarm value setting)
If the control mode is set to
2-PID
(Proportional band setting)
(Integral time setting)
(Derivative time setting)
(Manual reset
value setting)
SV
PV
SV
PV
SV
PV
SV
PV
SV
PV
SV
PV
SV
PV
SV
PV
SV
PV
SV
PV
SV
PV
0
Current
value
(see note)
When I = 0
1234
O
N
1234
O
N
1234
O
N
(See note) Without heater
burnout alarm
(See note)
Note: Nothing
is displayed in current output model.
Output V
alue Display:
o
Displayed range 0.0% to 100.0%
Control Period: cp
The
control period can be set with the Down and Up Keys within a
range
of 1 to 99 s. The control period is factory-set to 20 s.
In
the case of 2-PID, the relay output or voltage
output repeats turn
-
ing ON and OFF, the cycle of which is
called a control period. The
duration that the output is ON is in proportion to the output value.
The
shorter
the control period is, the smoother the control operation
will be. If the control period
is, however
, too short, the life of the relay
will
be shortened. Therefore the control period should be 20 s mini
-
mum
in the case of relay output.
ON
OFF
Control period:
10 seconds
ON
OFF
Control period:
20 seconds
Output
V
alue: 50.0%
Hysteresis:
hys
The
hysteresis value for the ON/OFF control can be set in a range
from 0.0
°
to 999.9
°C/°
F while “
hys
” is displayed on the PV
display
using
the Up and Down Keys. The value is factory-set to
1.0
°C/°F.
However,
the E5
j
J-F (Fahrenheit Model) is factory-set to 1.8
°F.
Low temperature set point High temperature
Hysteresis
ON
OFF
Reverse operation
(heating control)
Hysteresis
ON
OFF
Normal operation
(cooling control)
Low temperature set point High temperature
Set
Point 0 Setting (
°C or °F): spĆ0
Use
the Down and Up Keys to set the set point 0. It is possible to set
the
value
regardless of whether the set value presently selected is
on
SP0 or SP1.

E5jJE5jJ
Set Point 1 Setting:
spĆ1
Use
the Down and Up Keys to set the set point 1. It is possible to set
the
value
regardless of whether the set value presently selected is
on
SP0 or SP1.
14
13
14
13
Contact Input No-contact Input
(Open Collector)
ON: The resistance is 1 kΩ
max. when short-circui-
ted.
OFF: The resistance is
100 k
Ω
min. when
opened.
E5CJ
The
set point can
be selected by opening or short-circuiting the
EV1
terminals (terminals 13 and 14).
ON: The residual voltage is
3 V min.
OFF: The current leakage is
1 mA max.
Open
Set point 0 (SP0) Set point 1 (SP1)
Closed
20
17
20
17
Contact
Input
No-contact Input
(Open Collector)
E5AJ/E5BJ/E5EJ
The
set point can be selected by opening or short-circuiting
the EV1 terminals (terminals 17 and 20). In the case of the
E5BJ,
however
, the terminals 16 and 17 of which should be
opened
or short-circuited instead.
17
16
17
16
E5BJ E5AJ/E5EJ E5BJ E5AJ/E5EJ
ON: The resistance is 1 kΩ
max. when short-circui-
ted.
OFF: The resistance is
100 k
Ω
min. when
opened.
ON: The residual voltage is
3 V max.
OFF: The current leakage is
1 mA max.
E5BJ E5AJ
E5EJ
or
Set point 0 (SP0)
E5BJ E5AJ
E5EJ
or
Set point 1 (SP1)
or or
Heater Current V
alue Display:
ct
The
display range is 0.0 to 55.0 A. FFFF will be displayed if the cur
-
rent exceeds 55.0 A. When the control output is ON, the current
flowing
to the heater is measured and
displayed. If the control output
is,
however
, turned ON for less than 190 ms, the current flow will not
be measured and the current previously measured will be dis-
played.
Heater Burnout Alarm V
alue Setting:
hb
The
current value to
detect heater burnout can be set within a range
of
0.0 to 50.0 A.
The current value is factory-set to 0.0 A. Check the normal heater
current
and the current at the time of heater burnout from the heater
current
value display
, and set the set value to the mean value of the
current
values (i.e., set value = (normal
current value + heater burn
-
out
current)
B
2).
If
the dif
ference between the normal heater current
and heater burn
-
out
current is small, heater
burnout detection will not be stable. For
stable detection, the
dif
ference in current must be 1.0 A minimum if
the heater input is less than 10.0 A and 2.5
A minimum if the heater
input
is 10.0 A or more.
Note: 1. Do
not allow a current exceeding 50 A
to flow in the CT
;
the
maximum continuous heater current is 50 A.
2. Set
the value to 0.0 A if the heater burnout
alarm is not
used,
in which case the alarm will not function at all.
Connected
to T
emperature Controller.
Connected to heater.
Current
T
ransformer Connections

E5jJE5jJ
Heater
+
–
200 VAC
14
13
12
11
7
6
9
8
10
5
4
1
3
2
Heater burnout and
temperature alarm
Alarm output 1
Control output
E5CJ-H
Note: 1. Alarm
1 is used as heater burnout alarm and temperature alarm
for
models incorporating a heater burnout alarm.
2. Wire
through the hole of the Current T
ransformer
. The Current
Transformer
and the T
emperature Controller can be connected
regardless
of polarity
.
(see
note 2)
(see note 1)
E5CJ-H
E5EJ-H
Heater
+
–
200 VAC
24
23
22
21
12
11
14
13
15
E5EJ-H
17
16
19
18
20
26
25
28
27
29
5
4
1
3
2
7
6
9
8
10
Alarm output 1
Heater burnout and
temperature alarm
(see note 1)
(see note 2)
Control output
CT
•
Set the alarm mode selector 1 to 0 (i.e., no alarm function is ON)
so
that alarm output 1 will output only heater burnout alarms.
•If the difference in current is small, increase the apparent
electrical
current by increasing the number of turns of the heater
wire
around the CT
. The current displayed by the heater current
value display increases in proportion to the number of turns of
the
heater wire.
•Use
the K2CU-F
jjA-j
GS (incorporating gate input terminals)
for
detecting three-phase heater burnout.
Output Retention Reset
Once
the heater burnout alarm detects heater burnout, alarm output
1 will turn ON. To turn OFF alarm output 1, set the heater burnout
alarm
value to 0.0 A or turn of
f the T
emperature Controller and then
turn
on the T
emperature Controller
.

E5jJE5jJ
•If the control mode is 2-PID with fuzzy self-tuning, the
parameters
p
,
i
,d
, or
ofr
will not be displayed (i.e., there is no
need
to set these parameters). Fuzzy self-tuning always adjusts
all PID constants to optimum values inside the Temperature
Controller.
Proportional
Band:
p
When
the character “
p
” is displayed on the PV display
, the propor
-
tional band (P constant) can be changed using the Up and Down
Keys.
The new
value will be displayed on the SV display
. It can be
set
in a
range from 0.1
°
to 999.9
°C/°
F in units of 0.1
°C/°F
. The value
is factory-set to 8.0
°C/°F
. However
, the E5
j
J-F (Fahrenheit Model)
is
factory-set to 14.4
°F.
Integral T
ime :
i
When
the character “
i
” is displayed on the PV display
, the integral
time (I constant) can be changed using the Up and Down Keys. It
can
be set in a range from 0 to 3,999 seconds in units of 1 second.
The
value is factory-set to 233 seconds.
Derivative T
ime :
d
When
the character “
d
” is displayed on the PV display
, the deriva
-
tive
time (D constant) can be
changed using the Up and Down Keys.
It
can be set in a range from 0 to 3,999 seconds in units of 1 second.
The
value is factory-set to 40 seconds.
Manual Reset V
alue Setting (%) :
ofr
The
necessary output value in stable state will be set within a range
of
0.0% to 100.0%. The output value is factory-set to 50.0%. In P
or
PD
mode
(i.e., when I is 0), the T
emperature Controller will be bal
-
anced
with a deviation value between the
set point and process val
-
ue. This deviation value is called the
of
fset. By changing the manual
reset
value, the of
fset can be eliminated.
Engineering Level Parameters
The value set before shipping
appears.
(see note 1)
Displayed
if the E5
j
J with a com
-
munications
function is used.
(Data bit length setting)
(Parity check setting)
(Stop bit length setting)
Displayed
if the E5
j
J is in 2-PID
opera
-
tion
with fuzzy self-tuning.
(Stable
range setting)
Displayed
if the E5
j
J is in 2-PID opera
-
tion.
(Alpha
setting)
(Automatic return of display mode)
Displayed if the E5jJ with an alarm
function
is used (see note 2).
(Standby sequence
reset
method
setting)
(Input
shift display selection)
Displayed if the E5jJ with an alarm
function
is used (see note 2).
(Alarm 1 hysteresis
setting)
Displayed if the E5jJ with an alarm
function
is used (see note 2).
(Alarm 2 hysteresis
setting)
(Set
point lower limit setting)
(Set point upper limit setting)
Displayed if the E5jJ with
event
input 2 is used.
(Event input 2 function
selection)
Note: 1. The
E5
jJ-jjjj
-F values set before shipping
are
dif
ferent. Refer to the
E5
j
J Operation Manu
-
al
(Z103).
2. The
value will
not be displayed if the alarm mode
switch
is set to 0 or if the E5
j
J does not incorpo
-
rate
any alarm.
(°C/°
F selection)
15.0

E5jJE5jJ
d-u°C/°
F Selection
To
change the temperature display unit from
°
C to
°F
, press the Up
Key
so that
f
will be displayed in the set value display
.
c
:
°C
f
:
°F
SV SV
E5j
J with Communications Function
The communications specifications of the E5
j
J are as follows:
•
Data bit length: ASCII 7- (set before shipping) or 8-bit code
•
Parity check: None, even (set before shipping), or odd
•
Stop bit length: 1 or 2 (set before shipping)
•
Use the following parameters to change the above setting.
len
Data Bit Length
Use
this parameter to change the communications data bit length.
prty
Parity
Check
Use this parameter to change the communications parity check.
none :
None
eUen :
even
odd :
odd
SV SV SV
sbit
Stop Bit
Use this parameter to change the stop bit length.
s.tĆb
Stable Range (
°C/°F)
This
parameter is used to decide conditions under which fuzzy self-tuning operates and can be set within a range of 0.1 to 999.9. If the absolute
value of the deviation (the difference between the process value and set point) is within the stable range, temperature control operation is
deemed
smooth and fuzzy self-tuning will not start.
Set point Stable
range
Stable
PID before tuning PID after tuning
Fuzzy self-tuning
It
is deemed
that the characteristics
of the control device have been
changed so that the response wa-
veform
is processed to
tune the PID
constants.
alfa
(
α) PID Control Type
By
adjusting internal parameter
α
of 2-PID within a range of 0.00 to 1.00, PID control such as derivative preceding PID or proportional 2-PID
(I-PD)
control will be possible.
Set point
α = 0.00 (Derivative preceding PID)
α = 1.00
(Proportional preceding PID)
Difference in set point response due to α.
α = 0.65
To
increase the set point response speed, decrease the value of parameter
α
. If the value of parameter
α
is decreased, however
, the overshoot
-
ing
value will increase.
ret
Automatic Return of Display Mode (Return T
ime)
By
setting automatic return of display mode, the display will return to the normal operation display (on level 0 displaying the process value or set
point) if no key is operated for the time set with this parameter
. The return time can be set within a range of 0 to 99 s. If the return time is set to 0 s,
this
function will not work. The return time is set to 0 s before shipping.

E5jJE5jJ
rest
Standby
Sequence Reset Method
It
is possible to select the restart conditions of the standby sequence
of the alarm attached with standby sequence. If this parameter is set
to
0, the standby sequence will restart when the set
point, alarm val
-
ue, or input shift value is changed or the moment
the E5
jJ starts
operating including the moment the E5jJ is turned on. If this pa-
rameter is set to 1, the standby sequence will restart only the mo-
ment
the
E5
j
J is turned on. The following timing chart is an exam
-
ple
of a lower limit alarm attached with standby sequence.
Standby sequence releasing point
Standby
sequence restart
Standby
sequence
releasing point
OFF point due to
alarm hysteresis
Alarm point
(Standby sequence reset method 0)
(Standby sequence reset method 1)
Alarm output
Set value
change
Alarm output
inĆs
Input Shift Display
It
is possible to select to display or not to display the input shift func
-
tion
on display level 1 with this parameter
.
off :
Not displayed
on :
Displayed
SV SV
alh1
Alarm 1 Hysteresis and
alh2
Alarm 2 Hysteresis
It
is possible to adjust alarm sensitivity with
both these parameters
within a range of 0.1 to 999.9. Change the alarm sensitivity of the
E5jJ
if the alarm output chatters.
ON
OFF
ON
OFF
Upper limit alarm
Hysteresis
Lower limit alarm
Hysteresis
Low
temperature Alarm point High
temperature
Low
temperature Alarm point High
temperature
The
alarm output will be OFF when the process value is within
the
alarm hysteresis range when the E5jJ restarts (e.g., when the
E5jJ
is turned on).
sl-l
Set Point Lower Limit V
alue (
°C/°
F) and
slĆh
Set Point
Upper Limit V
alue (
°C/°F)
It
is possible to limit the set point changeable range with both these
parameters.
For example, if the set point lower limit value is set to
0°C
and the set point upper limit value is set to 400
°
C, the set point
can
be changed only between 0
°
C and 400
°C.
eu-2
Event Input 2 T
ype Selection
It
is possible to select the function of event input 2. If 0 (set point
val
-
ue
selection) is selected,
sp-2
and
sp-3
will be displayed on display
level 1 and if 1 is selected RUN/STOP will be selected. When 0 is
selected, the set point can be selected from the following.
20
19
17
EV1
EV2
COM
EV1 EV2
Set point to be selected
Open Open SP0
Short-circuit Open SP1
Open Short-circuit SP2
Short-circuit Short-circuit SP3

E5jJE5jJ
Starting Control Operation
The
E5
j
J will start control operations as soon
as power is turned on
until
power is turned
of
f. T
urn of
f the power and then turn it back on
after
setting the desired parameters.
By short-circuiting the EV2 terminals (terminals 17 and 19) of the
E5AJ/E5EJ
incorporating event input, control operation
can be in
-
terrupted.
Note: Always
turn on the Controller and the load simultaneously
.
Never
turn on the load when the Controller is already turned
on. Doing so will disable proper self-tuning and optimum
control.
For
example, when setting the parameters to the Controller
with the load turned off, turn off the Controller once after
completing the setting and then turn it on again simulta-
neously
with the load. Or
,
switch event input 2 from ST
OP to
RUN.
Open Short-circuit
Operation Operation
is being
interrupted.
19 19
17 17
Error Messages
The
T
emperature controller is provided with self-diagnostic functions, and will display an error message on the PV
display when an error is
detected.
Message Error Error output status
Item to be checked
Control output Alarm output
s.err (S.Err)
Input error
OFF (2 mA max.)
Processes the
error as an
abnormally high
temperature error
.
1. Check
if the
input is outside the possible
control range (i.e., ±10% of the set
temperature
range) (see note).
2. Check if the settings of the inputs are
wrong.
3. Check if there is any wiring mistake,
wire
burnout, or short-circuit.
e111
(E1
11)
Memory error
OFF (2 mA max.)
OFF T
urn of
f and then turn on the
T
emperature Controller
. If the display
does not change then, repairs are
necessary.
e333
(E333)
A/D converter error
OFF (2 mA max.)
OFF
necessary.
If the display returns to normal, the
T
emperature Controller may have been
influenced by noise. Check if noise is
being generated.
a.err (A.Err)
Calibration data error (displayed
for 3 s when the T
emperature
Controller is turned on)
Normal operation (accuracy not
guaranteed) Re-calibration is necessary.
Note: When
the input is within the possible control range but outside the possible display range (i.e., –1999 to 9999),
will be displayed if
the
value is smaller than –1999 and
will be displayed if the value is larger than 9999, however
, the control and alarm output
functions of the T
emperature Controller will work normally
.

E5jJE5jJ
Fuzzy Self-tuning
Fuzzy self-tuning is a function that enables the E5jJ to calculate
the
most suitable PID constants for the controlled object.
Features
The E5
j
J judges by itself when to perform fuzzy self-tuning.
Fuzzy Self-tuning Function
The
fuzzy self-tuning function has three modes.
In
SR
T
(step response tuning) mode, the PID constants are tuned
using
a step response method at the time the set point is changed.
In
DT (disturbance
tuning) mode, the PID constants are amended
so
that the controlled temperature will be within the target range
set in advance when there is external disturbance.
In HT (hunting tuning) mode, when hunting occurs, the PID
constants
are amended to suppress the hunting.
Note: Be
sure to turn on the
power supply to the load either before
or simultaneously with the start of T
emperature Controller
operation.
Dead
time will be measured
from the time the T
emperature
Controller starts operating. If a load such as a heater is
turned on after the Temperature Controller is turned on,
dead time longer than the actual value will be measured
and
inappropriate PID constants will be obtained. If an ex
-
tremely
large amount of dead time is
measured, the control
amount will be set to 0% for a short period of time before
being
returned to 100%, and the constants will then be
re
-
tuned. Retuning is performed only for large amounts of
dead
time, so be sure to
follow the precaution given above
when
starting operation.
Startup Conditions of SRT
SRT
will start if the following conditions are satisfied simultaneously
when
the E5
j
J is turned on or the set point is changed.
At the time the E5
j
J starts
operating
At the time set point is
changed
1. The
set
point at the time the
E5jJ starts operating is
different from the set point
used at the time SRT was
last
executed (see note).
2. The
dif
ference between
the
set point and the process
value at the time the E5jJ
starts operating is larger
than
the present proportion
-
al
band value (P) x 1.27+4.
3. The process value at the
time the E5jJ starts oper-
ating
is smaller than the set
point in reverse operation
and
larger than the set point
in
normal operation.
1. The new set point is differ-
ent from the set point used
at the time SRT was last
executed
(see note).
2. The set point changing
range is larger than the
present proportional band
value
(P) x 1.27+4.
3. The process value is in
stable condition before the
set
point is changed.
4. A larger set point value is
set
in reverse operation and
a smaller set point is set in
normal
operation.
Note: The
last SR
T
-executed set point is set to 0 before shipping
and
when changing from 2-PID control to 2-PID control with
fuzzy
self-tuning.
Imposition Completion Condition of Step Control Amount
In order to prevent overshooting, the step controlled amount must
be imposed continuously only while the present deviation is the
same as or greater than the value obtained from the proportional
band
(P) x 1.27. The step control will not be applied when the devi
-
ation
becomes smaller than this value.
PID Constant Refreshing Conditions
If
the step control amount is applied before the maximum
tempera
-
ture
slope (R) is obtained, SR
T will not renew any PID constant. If
the proportional band obtained from the R and L values that were
measured
before the imposition had been completed is larger than
the present proportional band, the PID constants will be renewed
because
the measured value is in the direction towards the
suitable
proportional band value, and the set point at that time will be the
SRT-executed
set point.
Temperature Slope (R)
Completion
of
SR
T
Stable range
Time
SP P x 1.27
Stable
T
emperature Status
If the temperature is within the stable range for a certain time, it is
deemed that the temperature is stable. This time is called stability
judgement
time. Like PID constants, stability judgement time is ad
-
justed
with fuzzy
self-tuning according to the characteristics of the
object
to be controlled. Fuzzy
self-tuning will not be activated if the
temperature is stable because the Temperature Controller deems
that
temperature control is smooth.
Shorter than the stability judgement time
Set
point
Stable
range
Stable
range
(Set
to
15.0_C
before
shipping)
Stability judgement time
Stable Stable
Balanced
Status
If
the process value is within the stable range for 60 s when there is
no
output, it is deemed that the the temperature is balanced.
Startup Conditions of DT
1. DT
will start if the temperature that has been stable varies due
to
external
disturbance and the deflection of the temperature
exceeds the stable range, and then the temperature
becomes stable, provided that the number of maximum
temperature
values is less than four
.
2. DT
will start if the set point is changed under the condition that
SRT does not start and the temperature becomes stable,
provided
that the number of maximum temperature values is
less
than four
.
If there are four or more maximum temperature values, HT
will
start.
SP
Temperature Extreme value 2 Set point change
Time
Extreme value 1

E5jJE5jJ
Startup Conditions of HT
HT will be ON when there is hunting with four or more maximum
temperature values (extreme values) while SRT is not being
executed.
Extreme value 2 Extreme value 4
Extreme
value 1 Extreme
value 3
Temperature
Time
SP
Note: In specific applications where temperature varies periodi-
cally
due to disturbance, internal parameters need to be ad
-
justed.
For details, refer to
E5
j
J Operation Manual
.
Auto-tuning
Starting Auto-tuning
Auto-tuning can be started by using the following procedure. Use
this
procedure when appropriate results are not achieved via fuzzy
self-tuning.
1. Turn ON pin 3 of the function selector switch to select the
2-PID
control mode (refer to
page
8
).
2. Press
the Level Key and the Display Key simultaneously
for
1 s
or longer to start auto-tuning.
Conditions that Prevent Auto-tuning
You will not be able to start auto-tuning when any of the following
conditions exist.
•When the control mode is set for ON/OFF control or 2-PID
control
with fuzzy self-tuning.
•
When an engineering level parameter is displayed.
•
When the key protection switch is set to SP
or ALL.
•
When the remote/local setting is set to remote.
•
When the RUN/STOP setting is set to ST
OP.
•When
a sensor error
, memory error
, or A/D converter error has
occurred.
Force-ending Auto-tuning
Auto-tuning
will be forced to end for any of the following conditions.
•When
the T
emperature Controller is turned of
f.
•
When the RUN/ST
OP setting is changed to ST
OP.
•When a sensor error occurs.
•When the Level Key and the Display Key are pressed
simultaneously
for 1 s or longer
.
Changing Parameters during Auto-tuning
•Parameters cannot be changed during auto-tuning, but the
remote/local
setting can be changed.
•The SP also cannot be changed via the event input during
auto-tuning,
but the event input status can be changed and
the
SP
will be changed after auto-tuning has been completed.
Set point
Auto-tuning
Auto-tuning started.
Scale changes disabled here.
Event input
terminal
Open SP0 selected. Shorted SP1 selected.
SP0
SP1
Table of contents
Other Omron Temperature Controllers manuals

Omron
Omron E5CN User manual

Omron
Omron E5ZN-DRT User manual

Omron
Omron E5EN User manual

Omron
Omron E5CN Owner's manual

Omron
Omron EJ1G User manual

Omron
Omron E5CC-800 User manual

Omron
Omron E5CC-B-800 User manual

Omron
Omron E5*N Series Installation guide

Omron
Omron E5ZE-8 D1 B-V2 User manual

Omron
Omron E5AN User manual