Heating / Shared rel.
Adjustment
channel Description Adjustment range /
selection Factory setting
Dem. 1 (2) Demand 1 (2) Activated, Deactivated Deactivated
Relay Relay option Yes, No No
Relay Relay sub-menu - -
Output Output selection system dependent R5
Boiler pr. min Option for boiler protection min Yes, No No
Tmin Minimum boiler temperature 10 … 90 °C 55 °C
Boiler pr. max Option for boiler protection max Yes, No No
Tmax Maximum boiler temperature 20 … 95 °C 90 °C
Sensor Boiler Boiler sensor selection system dependent S4
0-10 V 0-10 V option Yes, No No
0-10 V 0-10 V sub-menu - -
Output Output selection -, A, B D
Tset 1 Lower boiler temperature 10 … 90 °C 10 °C
Volt 1 Lower voltage 0.0 … 10.0 V 1.0 V
Tset 2 Upper boiler temperature 10 … 90 °C 80 °C
Volt 2 Upper voltage 0.0 … 10.0 V 8.0 V
Tmin Minimum boiler temperature 1 … 90 °C 10 °C
Tmax Maximum boiler temperature 1 … 90 °C 80 °C
Sen. Flow Flow sensor option Yes, No No
Sensor Flow sensor selection system dependent S4
Interval Monitoring period 10 … 600 s 30 s
Hysteresis Correction hysteresis 0.5 … 20.0 K 1.0 K
Correction Correction of the voltage signal 0.1 … 1.0 V 0.1 V
Min. runtime Minimum runtime option Yes, No No
Min. runtime Minimum runtime 0 … 120 min 10 min
Pump 1 … 2 Shared relay option for loading
pump Activated, Deactivated Deactivated
Adjustment
channel Description Adjustment range /
selection Factory setting
Relay Relay selection system dependent system dependent
Start-up Pump delay No,Time,Temperature No
Delay Delay to a demand 0 … 300 s 60 s
TStart-up Boiler start-up temperature 10 … 90 °C 60 °C
Overrun Pump overrun No,Time,Temperature No
Overrun time Overrun time 0 … 300 s 60 s
TOverrun Remaining boiler temperature 10 … 90 °C 50 °C
Sensor Boiler
1 … 2 Boiler sensor selection system dependent system dependent
Valve 1 … 2 Activation of a shared relay
Parallel relay Activated, Deactivated Deactivated
Relay Relay selection system dependent system dependent
back
In this menu, up to 2 heating demands can be activated and adjusted.
Activated demands will be available for selection in the output alloca-
tion channels of the backup heating in heating circuits and heating op-
tional functions.This way, several heating circuits and optional functions
can demand the same heat source.
Every demand can be carried out by means of a relay and/or a 0-10 V output.
If both the Relay and the 0-10 V option are activated, the demand will use both
outputs in parallel.
Relay option
If the Relay option is activated, the sub-menu Relay appears, in which a relay can
be allocated to the demand.
The options Boiler protection min and Boiler protection max can be acti-
vated for the demand via a relay, allowing temperature-dependent control of the
boiler demand. For this purpose, a boiler sensor (Sensor Boiler) is required.
The Boiler pr. min option is used for protecting an older type boiler against
cooling. If the temperature falls below the adjusted minimum temperature, the
allocated relay is energised until the minimum temperature is exceeded by 2 K.
The Boiler pr. max option is used for protecting an older type boiler against
overheating.If the adjusted maximum temperature is exceeded, the allocated relay
is switched off until the temperature falls by 2 K below the maximum temperature.