Technical description „Aktor M ST L Modbus“
8101274584-V01.11.2019
ThecycletimecanbeconguredviatheModbus
parametrization.
Ifthevalueiszero,thisfunctionisdeactivated.
3.2.2 Calculation functions
Calculation of the volume ow
Incombinationwithapressureindependentcontrol
valve“CoconQTR/QFC”,thecurrentvolumeowis
calculated on the basis of the set valve characteristic
line and the current position of the actuator and can
bequeriedviaModbus.
Calculation of the thermal output
The current thermal output is calculated on the basis
ofthecalculatedvolumeowandthetemperature
differencebetweenthesupplyandreturnpipeand
canbequeriedviaModbus.
3.2.3 Limitation function
Return temperature limitation (register 315)
Return temperature limitation is carried out on the
basisofthelimitvalueconguredviaModbusand
the current measured return temperature. When ex-
ceededorundercut,thevolumeowwillbereduced
until the limit value is reached again.
Limitation of the thermal output (register 314)
Limitation of the thermal output is carried out on the
basisofthelimitvalueconguredviaModbusand
thecalculatedcurrentoutput.Whenexceeded,the
volumeowwillbereduceduntilthelimitvalueis
reached again.
3.2.4 Control function
Output control (registers 130, 200, 301, 310, 311, 410)
Controltoadenedoutputvaluecanbecarriedout
on the basis of the calculated current output.
Room temperature control (registers 131, 200, 300,
310, 311, 403)
Room temperature control is carried out on the basis
ofthenominaltemperatureconguredviaModbus
and the transmitted current room temperature.
Return temperature control (registers 130, 200, 302,
310, 311, 404, 405)
Return temperature control is carried out on the ba-
sisofthenominaltemperatureconguredviaMod-
bus and the current measured return temperature.
3.2.5 System monitoring
Leakage detection
A possible internal leakage is detected on the basis
ofthemeasuredowandreturntemperaturewiththe
valve closed.
A leakage is detected if the measured temperature
differenceexceeds8Kforatleast6hourswiththe
valve closed.
Operating and fault messages
All data registered by the actuator can be queried
viaModbus.Thestateofthehydraulicscanbe
assessed on the basis of these data and possible
errors and failures can be detected at an early stage.
Bus monitoring
Thebusfailuredetectioncanbeparametrizedvia
Modbus(seesection6.2 on page 12).