
STEP 17 Change the LINK DATE to the date the fiber will be tested using the format MM-DD-
YY.
Press <DONE> when you are finished entering the current date.
STEP 18 Highlight the cabling standard to use for the set of fibers you are testing.
Press <F2> to select the chosen standard.
STEP 19 Highlight the fiber type of the network under test.
Press <F2> to select the fiber type.
STEP 20 Enter the end-to-end length of the fiber link under test in meters.
Press <DONE> to continue.
STEP 21 Enter the number of connections (i.e. patch panels) in the link under test. Typical fiber
networks will have 2 connections – one for a patch panel located at each end of the link.
Press <DONE> to continue.
STEP 22 Enter the number of splices in the link under test. Splices can be either fusion or
mechanical. Typical multimode networks will have zero splices.
NOTE: some connectors use mechanical splice technology for termination. If the link under
test is terminated with these “no-polish, no-epoxy” type connectors, they should be considered
as mechanical splices.
Press <DONE> to continue.
STEP 23 Review your Link Wizard setup.
If correct, press <F1> and continue on to the next step.
If changes need to be made, press <F3> and go back to STEP 16.
STEP 24 Press <F1> until the asterisk (*) is in front of 850nm (as shown at right).
Press <F2> to begin the SET REFERENCE procedure for 850nm.
STEP 25 Connect the detector meter and 850nm light source (left-hand port) together with the
mandrel-wrapped cable as shown in Figure 4.
Press <F1> to continue.
STEP 26 Make sure that the 850nm light source port is powered ON and selected (the indicator LED on the left-
hand side will be lit).
STEP 27 Confirm setting the 850nm reference.
Pressing <F1> to continue. You will be returned to the SET SOURCE REFERENCES screen.
NOTE: if you are also testing at 1300nm, you will need to connect a separate mandrel-
wrapped patch cable to the 1300nm port.
It is important to set the current date in order to ensure that the correct date appears on the certification reports.
WAVELEN REF dBmX X
---------------------
* 850nm NOT SETX X X
X XXXX XXXX XWAVE SET DONE
X X X1300nm NOT SET
XXXXXXXXXXXXXXXXXXXXX
SET REFERENCESX
_____________________
XXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXX
X XXX XXX X<--- SHIFT --->
XXXXXXXXXXXXXXXXXXXXX
[03-20-08]
DATE:X[MM/DD/YY]
_____________________
XXXXXXXXXXXXXXXXXXXXX
X X X XXXXXUSER DEFINED #1
X X X XXXXXUSER DEFINED #2
x XX XXXXXXXXNEXT SELECT
X X XXXXXXXISO/IEC 11801
xx X XXXXFIBER STANDARDS
_____________________
X X XXXXXTIA-568B 3
XXXXXXXXXXXXXXXXXXXXX
XX X X xx50 0um MM
x XX XXXXXXXXNEXT SELECT
xx X xOUTDOOR SM
XXXXX X XXXXXFIBER TYPES
_____________________
XX X xxINDOOR SM
XX X X xxx62 5um MM
[1 TO 65535]X X
XXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXX
x XXX XXX X<--- --->UNITS
XXXXXXXXXXXXXXXXXXXXX
[01000]X XXMETERS
ENTER FIBER LENGTH:X X XX
_____________________
(A CONNECTION IS WHENX X X
TWO FIBER CONNECTORSX X X
MATE USUALLY A PATCHXX X X
x XXX XXX X<--- --->SHIFT
PANEL)XXXXXXXXXXXXXXX
[2 ]X XXXXXXXXXXXXXXXXX
INLINE CONNECTIONS?X XX
_____________________
SPLICES IN THE FIBERX X X X
BEING TESTED:X XXXXXXXX
XXXXXXXXXXXXXXXXXXXXX
x XXX XXX X<--- --->SHIFT
XXXXXXXXXXXXXXXXXXXXX
[0 ]X XXXXXXXXXXXXXXXXX
ENTER THE NUMBER OFX X X XX
_____________________
01000 Metersx xxxxxxxxx
02 Connectionsx xxxxxxx
00 Splicesx xxxxxxxxxxx
X XXXXXXXXXXXXX XXYES NO
62 5um MMx x
IS THIS CORRECT?X X XXXXX
TIA-568-B 3X XX
_____________________
Standard »
Length »
Connections »
Splices »
Fiber Type »
850nm
DONE
SOURCE
CONNECT
_____________________
XX850nm
X XXXXXXXXXXXXX XXYES NO
xxREF?
_____________________
xxxSET