
- 15 -
SETTING THE FLOW RATE
PROCEDURE FOR CHANGING FLOW RATE IN DIGITAL SETTING
Single SP (Setpoint) Setting Mode (Single Setpoint Per Function Setup ‘C-04’)
Follow the procedure below to change the SP (setpoint) value (set flow rate):
1. Press the [DISP] key (the instantaneous flow rate and SP values are displayed [display at
power supply ON]).
2. Press the [∧
∧∧
∧] key or [∨
∨∨
∨] key to change the SP value (the digit being changed blinks. Also,
when the [<] key is pressed, the digit being changed is moved.).
3. When you have reached the desired value, press the [ENT] key (the SP value is stored).
If the [DISP] key is pressed without pressing the [ENT] key, the SP value is not stored
and returns to the previous value.
Note: By changing the function setup, the multi-setting (4 maximum) or analog voltage setting
may be selected.
Direct Setup Function
Flow control can be achieved using the SP value currently being changed (indicated by blinking
display) when the direct setup function is enabled at function setup ‘C-21’ (the direct setup
function is enabled as the default setting). For instructions to change the function setup modes,
refer to ‘SECTION 6 – APPLICATION OPERATION’.
The [ENT] key does not to be pressed to establish the SP value. However, to switch the display
by pressing the [DISP] key, press the [ENT] key to establish the SP value prior to switching the
display. This function is useful when performing incremental changes to the SP value.
Multi-SP (Setpoint) Setting Mode (Multiple Setpoints Per Function Setup ‘C-04’)
Up to four (4) SP (setpoint) values (setting flow rate values) can be programmed by key operation
or by external switch inputs.
To program by key operation, follow the procedure below to change to SP number and SP value:
1. Press the [DISP] key (the instantaneous flow rate value and SP value are displayed
[display at power supply ON]).
2. Press the [DISP] key for one (1) second or longer (the SP number currently being
selected [SP-0, SP-1,SP-2 or SP-3] is indicated on the upper display and the SP value is
indicated on the lower display).
3. Press the [∧
∧∧
∧] key or [∨
∨∨
∨] key to change the SP number.
4. When the desired SP number is displayed, press the [ENT] key.
5. Press the [∧
∧∧
∧] key or [∨
∨∨
∨] key to change the SP value (the digit being changed blinks; move
to the digit to be changed by pressing the [<] key).
6. When the desired SP value is displayed, press the [ENT] key (the SP value is
programmed). Both the SP value and SP number are now updated.
Direct Setup Function
Flow control can be achieved using the SP value currently being changed (indicated by blinking
display) when the direct setup function is enabled at function setup ‘C-21’ (the direct setup
function is enabled as the default setting). For instructions to change the function setup modes,
refer to ‘SECTION 6 – APPLICATION OPERATION’.
The [ENT] key does not need to be pressed to establish the SP value. However, to switch the
display by pressing the [DISP] key, press the [ENT] key to establish the SP value prior to