Pego PLUS300 Expert VD 4 User manual

REV. 01/04
Use and maintenance manual
ELECTRICAL BOARDS FOR REFRIGERATING INSTALLATIONS
READ AND KEEP
REV. 01-18
ENG
PLUS300
EXPERT U THR
ENGLISH

PLUS300 EXPERT U THR
Thanks for choosing this PEGO electrical panel.
This manual gives detailed information on installation, use and maintenance of PLUS300
EXPERT U THR series electrical panels and special version. Our products are designed
and built in compliance with current standards, on the specific field of refrigeration and
conditioning systems. A different use is allowed respecting the working conditions for
which the panel is designed and made.
Before using the panel it’s suggested to fully read this manual paying special attention to
the highlighted parts with the simbology descripted below:
This symbol is used to focus on notes concerning installation, use and
maintenance operations
This symbol is used to focus on important notes
This symbol is used to indicate the prohibition to do the shown
operation

PLUS300 EXPERT U THR
Pag. 3
USE AND MAINTENANCE MANUAL
Rev. 01-18
INTRODUCTION
Pag. 4 1.1 General
Pag. 5 1.2 Product ID codes
Pag. 5 1.3 Overall dimensions
Pag. 5 1.4 Identification data
INSTALLATION
Pag. 6 2.1 Important general information for the installer
Pag. 6 2.2 Kit for mounting
Pag. 7 2.3 Installation
Pag. 8 2.4 Functions managed by PLUS300 EXPERT U THR
TECHNICAL SPECIFICATIONS
Pag. 9 3.1 Technical specifications
WARRANTY CONDITIONS
Pag. 10 4.1 Warranty conditions
PARAMETERS PROGRAMMING
Pag. 11 5.1 Control panel
Pag. 11 5.2 Frontal keyboard
Pag. 12 5.3 LED display
Pag. 14 5.4 General features
Pag. 14 5.5 Key to symbols
Pag. 14 5.6 Set point programming and displaying
Pag. 15 5.7 First level programming
Pag: 15 5.8 List of first level variables
Pag. 17 5.9 Second level programming
Pag. 17 5.10 List of second level variables
Pag. 20 5.11 Automatic programs Pr1, Pr2, Pr3, Pr4, Pr5
Pag. 22 5.12 Germination day/night cycle
Pag. 23 5.13 Ignition of PLUS300 EXPERT U THR electronic control
Pag. 23 5.14 Cold/hot: preservation of ambient temperature
Pag. 24 5.15 Humidity/dehumidification: preservation of ambient humidity
Pag. 25 5.16 Ventilation
Pag. 25 5.17 Air change
Pag. 26 5.18 Pause
Pag. 26 5.19 Defrost
Pag. 26 5.20 Hot gas defrost
Pag. 27 5.21 Funzione password
Pag. 27 5.22 Automatic programs
Pag. 29 5.23 Day/night cycle for germination lights
MAINTENANCE
Pag. 30 6.1 General security rules
Pag. 31 6.2 Maintenance
OPTIONS
Pag. 31 7.1 TeleNET monitoring/supervision system
DIAGNOSTIC
Pag. 32 8.1 Diagnostic
APPENDICES
Pag. 33 A.1 EU declaration of conformity
Pag. 34 A.2 100N master THR wiring diagram
REV. 01/04
INDEX
CAP. 2
CHAP. 8
CHAP. 1
CHAP. 3
CHAP. 3
CHAP. 4
CHAP. 5
CHAP. 8
CHAP. 6
Index
CHAP. 7

PLUS300 EXPERT U THR
Pag. 4
USE AND MAINTENANCE MANUAL
Rev. 01-18
GENERAL FEATURES
DESCRIPTION:
Three-phase electrical panel for temperature and humidity control for evaporating unit with
electrical heaters for hot.
To match with a compressor rack or a remote condensing unit.
Magnetothermic circuit breaker protection accessible from the front panel added to an
innovative form makes this panel a perfect and functional choice to provide safety,
protection, control of temperature and humidity with specific seasoning functions.
Programming up to five recipes, of seven phases each, settable and customizable (the
usable functions depend on the type of the panel).
Collectively the panel permits to control cold solenoid, condensing unit enabling, hot
heaters, ventilation (up to 800W), cold room light, humidification enabling, air exchange,
pauses, de-humidification, defrosts (up to 7500W), alarms.
APPLICATIONS:
-Seasoning/drying rooms.
-Germination rooms with day/night cycles.
-Storage rooms with or without humidity control.
MAIN FEATURES:
-Backlit LCD screen.
-Clock and calendar.
-Manual or automatic mode.
-Up to 5 formula completely customazible automatic management of 7 phases for each
formula (dripping first phase, seasoning/conservation last phase). simple programming
and selection of set formula. possibility of join together more formula for exceeding the
7 phases limit.
-Heat and humidity can be excluded to manage storage cells with defrost activation.
-Temperature to one decimal point.
-Password for keypad lock.
-Day/night cycle for germination systems with double set-point.
-Dehumidification program with cold or heat call.
1.1
CHAPTER 1: INTRODUCTION
CHAP. 1 - Introduction

PLUS300 EXPERT U THR
Pag. 5
USE AND MAINTENANCE MANUAL
Rev. 01-18
PRODUCT IDENTIFICATION CODE
110P30EUTHR Temperature and humidity control for
seasoning, preservation and industrial
processes.
DIMENSIONS
Dimensions in mm
IDENTIFICATION DATA
The unit described in this manual has an ID plate on its side showing the relevant ID data:
• Manufacturer name
• Product identification code
• Serial number
• Date
• Power supply
• Frequency
• Rated current
• Protection rating (IP)
1.3
CHAP. 1 - Introduction
1.2
1.4

PLUS300 EXPERT U THR
Pag. 6
USE AND MAINTENANCE MANUAL
Rev. 01-18
IMPORTANT GENERAL INFORMATION FOR THE INSTALLER
1. Install the device in places where the protection rating is observed and try not to
damage the box when drilling holes for wire/pipe seats;
2. Do not use multi-polar cables in which there are wires connected to inductive/power
loads or signaling wires (e.g. probes and digital inputs);
3. Do not fit power supply wiring and signal wiring (probes and digital inputs) in the same
raceways or ducts;
4. Minimize the length of connector wires so that the wiring does not have a spiral shape;
5. All wiring must be of a cross-section suitable for relevant power levels;
6. Place a general protection fuse upstream from the electronic controller;
7. When it is necessary to extend the probes, the wires must have a cross-section of at
least 1mm². The probes extension or shortening could alter the factory calibration; then
check and calibrate through an external thermometer.
KIT FOR MOUNTING
PLUS300 EXPERT U THR electronic controller kit, for assembling and using, contains:
• N° 4 seals, to be fitted between the fixing screws and the box back panel.
• N° 1 use and maintenance manual.
• N° 1 electrical drawing.
• N° 1 drilling layout.
• N° 2 probes NTC 10K 1% .
CHAPTER 2: INSTALLATION
CHAP. 2 - Installation
2.1
2.2

PLUS300 EXPERT U THR
Pag. 7
USE AND MAINTENANCE MANUAL
Rev. 01-18
INSTALLATION
Raise the transparent cover that shields the magneto-thermal cut-out switch and
remove the screw cover on the right-hand side.
Undo the 4 fixing screws at the front of the box.
Open the front of the box, lift it and slide the two hinges out as far as they will go. Bend
the hinges and rotate the front panel by 180° downward to get access inside the panel
Using the furnished drilling layout make four fixing holes on the wall. Using holes made
on previous point fix the bottom with 4 screws of a length suitable for the thickness of
the wall to which the panel will be attached. Fit a o-ring (supplied) between each screw
and the box backing
Make all the electrical connections as illustrated in the diagram for the corresponding
model (see relative table in APPENDICES).
To effect correct electrical connection and maintain the protection rating, use
appropriate wire/raceway grips to ensure a good seal.
Route the wiring inside the unit in as tidy a fashion as possible: be especially careful to
keep power wires away from signal wires. Use clips to hold wires in place.
Close the front panel, making sure that all the wires are inside the box and that the box
seal sits in its seat properly.
Tighten the front panel using the 4 screws, making sure the O-rings on the head of
each screw are used.
Power up the panel and carry out thorough reading/programming of all the
parameters.
Be careful not to over-tighten the closure screws as this could warp the box and
compromise proper operation of the membrane-type keypad.
Install short-circuit overload safety devices on all the power cables connected to the
PLUS300 EXPERT U THR so as to prevent damage to the device. Work and/or
maintenance must ONLY be carried out on the unit after disconnecting the panel from
the power supply and from any inductive/power loads: doing so allows the worker to
do his job safely.
CHAP. 2 - Installation
2.3

PLUS300 EXPERT U THR
Pag. 8
USE AND MAINTENANCE MANUAL
Rev. 01-18
FUNCTIONS MANAGED BY PLUS300 EXPERT U THR
• Display and adjustment of temperature and humidity settings (neutral zone).
• Stand-by activation/deactivation.
• Sensor alarms.
• Air change parameter adjustment.
• Defrost parameter adjustment.
• Pauses parameter adjustment.
• Fan parameter adjustment.
• Outputs status display.
• Simultaneous display of temperature and humidity.
• Automatic program control with automatic variation of temperature and humidity settings
over time.
• Clock function.
2.4
CAP. 2 - Installation

PLUS300 EXPERT U THR
Pag. 9
USE AND MAINTENANCE MANUAL
Rev. 01-18
TECHNICAL CHARACTERISTICS
TECHNICAL CHARACTERISTICS
PLUS300 EXPERT U THR
Box dimension
400 x 300 x 135mm
Weight
6 Kg
Protection rating
IP65
Power supply ( 3F + N + T )
400Vac ±10% 50/60Hz
Load type
three-phase
Working temperature
- 5 ÷ +40 °C
Storage temperature
-25 ÷ +70 °C
Relative ambient humidity
form 30% to 90% RH without condensate
Reading range
- 45 ÷ +45 °C / 0 ÷ 100% Rh
Control
PEGO THR integrated
Status indicators
Display LCD
Main switch general protection
4 poles magnetothermic 20A
INPUTS
Ambient probe
NTC 10K 1%
Evaporator probe
NTC 10K 1%
Humidity probe
4÷20mA (0 ÷ 100% Rh)
Door switch
Present
Min. temperature sensor
Present
Max temperature sensor
Present
OUTPUTS
Enable condensing unit
Present
Evaporator fans
800W (1ph)
Defrost
Off-cycle
Hot heaters
7500W (AC1)
Enable humidifiers
Present
Enable dehumidifiers
Present
Air change
Present
Pause
Present
Room light
Present
Alarm relay
Present
Supervision system
TeleNET
CHAP. 3 - Technical characteristics
CHAPTER 3: TECHNICAL CHARACTERISTIC
3.1
Connection diagrams:

PLUS300 EXPERT U THR
Pag. 10
USE AND MAINTENANCE MANUAL
Rev. 01-18
WARRANTY CONDITIONS
PLUS300 EXPERT U THR series products are covered by a 24-months warranty against
all manufacturing defects as from the date indicated on the product ID code.
In case of defect the product must be appropriately packaged and sent to our production
plant or to any authorized Service Center with the prior request of the Return Authorization
Number.
Customers are entitled to have defective products repaired, spare parts and labour
included. The costs and the risks of transport are at the total charge of the Customer.
Any warranty action does not extend or renew its expiration.
The Warranty does not cover:
Damages resulting from tampering, impact or improper installation of the product and
its accessories.
Installation, use or maintenance that does not comply with the instructions provided
with the product.
Repair work carried out by unauthorized personnel.
Damage due to natural phenomena such as lightning, natural disasters, etc…
In all these cases the costs for repair will be charged to the customer.
The intervention service in warranty can be refused when the equipment is modified or
transformed.
Under no circumstances Pego S.r.l. will be liable for any loss of data and information,
costs of goods or substitute services, damage to property, people or animals, loss of sales
or earnings, business interruption, any direct, indirect, incidental, consequential,
damaging, punitive, special or consequential damages, in any way whatsoever caused,
whether they are contractual, extra contractual or due to negligence or other liability arising
from the use of the product or its installation.
Malfunction caused by tampering, bumps, inadequate installation automatically declines
the warranty. It is compulsory to observe all the instructions in this manual and the
operating conditions of the product.
Pego S.r.l. disclaims any liability for possible inaccuracies contained in this manual if due
to errors in printing or transcription.
Pego S.r.l. reserves the right to make changes to its products which it deems necessary
or useful without affecting its essential characteristics.
Each new release of the Pego product user manual replaces all the previous ones.
As far as not expressly indicated, is applicable the Law and in particular the art. 1512 C.C.
(Italian Civil Code).
For any controversy is elected and recognized by the parties the jurisdiction of the Court of
Rovigo.
4.1
CHAP. 4 - Warranty conditions
CHAPTER 4: WARRANTY CONDITIONS

PLUS300 EXPERT U THR
Pag. 11
USE AND MAINTENANCE MANUAL
Rev. 01-18
CONTROL PANEL
FRONTAL KEYBOARD
PROGRAM START/STOP (to press 5 sec for selecting the program to run, to
press 5 sec for finishing a running program)
TIMER (displays remaining time of running phase with a single key press)
UP
MANUAL PAUSE and DEFROST (activates both functions)
STAND BY
(system ON/OFF, the running program maintains the count of remaining time)
SET ambient temperature and humidity (following pressures alternate
temperature and humidity)
CHAP. 5 - Parameters programming
CHAPTER 5: PARAMETER PROGRAMMING
5.1
5.2

PLUS300 EXPERT U THR
Pag. 12
USE AND MAINTENANCE MANUAL
Rev. 01-18
DOWN / MUTE ALARM / FORCING AIR CHANGE
ROOM LIGHT
DISPLAY LED
1
PHASE 0 advancing/ Dripping / Day germination phase
2
PHASE 1 advancing
3
PHASE 2 advancing
4
PHASE 3 advancing
5
PHASE 4 advancing / Night germination phase
5.3
CHAP. 5 - Parameters programming

PLUS300 EXPERT U THR
Pag. 13
USE AND MAINTENANCE MANUAL
Rev. 01-18
6
PHASE 5 advancing
7
Refreshment
8
Ambient temperature value/ parameters
9
Ambient relative humidity / parameters value / error codes
10
Time / date / time parameters value / running program / timer
11
PRG
Programming (the controller is in programming phase)
12
Cold (flashing if called for dehumidification only)
13
Hot (flashing if called for dehumidification only)
14
Humidification
15
Dehumidification
16
Defrost
17
Fans
18
Light (flashing if the door switch is active)
CHAP. 5 - Parameters programming

PLUS300 EXPERT U THR
Pag. 14
USE AND MAINTENANCE MANUAL
Rev. 01-18
19
Alarm
20
Stand-by
GENERAL FEATURES
For safety reasons and to simplify the operator’s work, the PLUS300 EXPERT U THR has
two programming levels; the first level is used to modify SETPOINT parameters (i.e. those
parameters that are changed frequently). The second level is for general parameter
programming of the various board work modes.
It is not possible to access the first programming level directly from the second level: you
must exit the programming mode first.
KEY TO SYMBOLS
For practical purposes the following symbols are used:
• ()indicates the UP key used to increase value and to force the defrost / pause;
• ()indicates the DOWN key used to decrease value, to mute the alarm and to force
the air changing.
SET POINT PROGRAMMING AND DISPLAYING
1. Push the SET key to display the current SET POINT (temperature and humidity
alternately).
2. Press the SET key and push one of () or () keys to modify the SET POINT value.
Release the SET key to return to cold room temperature display; modifications are saved
automatically.
5.4
CHAP. 5 - Parameters programming
5.5
5.6

PLUS300 EXPERT U THR
Pag. 15
USE AND MAINTENANCE MANUAL
Rev. 01-18
FIRST LEVEL PROGRAMMING (User Level)
To access the first programming level proceed as follows:
1. Press the ()and ()keys simultaneously and keep them pressed for a few seconds
until the first programming variable appears on the display.
2. Release the () and () keys.
3. Select the variable to be modified using the () or () key.
4. When the variable has been selected it is possible:
•To display its setting by pressing SET.
•To modify its setting by pressing the SET key and the ()or ()buttons.
When configuration values have been set you can exit the menu by pressing ()and ()
simultaneously for a few seconds until the room temperature value appears.
5. The modifications are saved automatically when you exit the configuration menu.
LIST OF 1ST LEVEL VARIABLES (User Level)
VARIABLES
MEANING
VALUES
DEFAULT
dtC
HOT temperature differential with reference to main
SET-POINT. It is expressed in absolute value and it defines
the temperature hysteresis for the HOT referred to
temperature SET POINT.
(dtn+0,2) ÷ 10 °C
2 °C
dtF
COLD temperature differential with reference to main
SET-POINT. It is expressed in absolute value and it defines
the temperature hysteresis for the COLD referred to
temperature SET POINT.
(dtn+0,2) ÷ 10 °C
2 °C
dtn
Temperature NEUTRAL zone with reference to main
SET-POINT. In neutral zone cold and hot are not activated;
it includes symmetrically both a superior part (hot) and an
inferior part (cold) as to temperature SET-POINT.
dtF>dtn ÷ 0 °C
dtC>dtn ÷ 0 °C
0 °C
dUU
HUMIDIFICATION differential with reference to humidity
SET-POINT. It is expressed in absolute value and it defines
the humidification hysteresis referred to humidity SET-
POINT
(dUn+1) ÷ 10
rH%
5 rH%
dUd
DEHUMIDIFICATION differential with reference to
humidity SET-POINT. It is expressed in absolute value and it
defines the dehumidification hysteresis referred to humidity
SET-POINT .
(dUn+1) ÷ 10
rH%
5 rH%
dUn
Humidity NEUTRAL zone with reference to main
SET-POINT . In neutral zone humidification and
dehumidification are not activated; it includes symmetrically
both a superior part (humidification) and an inferior part
(dehumidification) as to humidity SET-POINT.
dUU>dUn ÷ 0
rH%
dUd>dUn ÷ 0
rH%
0 rH%
d4
Defrost interval (hours).
d4=0 disables the defrosts
0 ÷ 24 hours
0 hours
d5
Maximum lenght of defrost (minutes)
1 ÷ 60 min
10 min
d6
End of defrost setpoint.
The defrost is not executed if the temperature read
from defrost probe is superior to d6 value.
(In case of broken probe it will have a timing defrost)
-35 ÷ 45 °C
15°C
CHAP. 5 - Parameters programming
5.7
5.8

PLUS300 EXPERT U THR
Pag. 16
USE AND MAINTENANCE MANUAL
Rev. 01-18
d7
Dripping duration (minutes)
At the end of defrosting, the compressor and the fans remain
still for the d7 set time, the defrosting icon flashes.
0 ÷ 10 min
0 min
F5
Fans pause after defrosting (minutes)
Enables keeping the fans still for an F5 time after dripping.
This time starts from the end of dripping. If dripping is not
set, at the end of defrosting the fans pause occurs directly.
0 ÷ 10 min
0 min
At1
Minimum temperature alarm
Enables defining a minimum temperature value to the
ambient. Below value At1, the alarm status will be signalled
with the alarm icon flashing, the temperature flashes and an
internal buzzer acoustically signals the existence of an
anomaly. The alarm is signalled after the Ald time.
-45 ÷ At2-1 °C
-45°C
At2
Maximum temperature alarm
Enables defining a maximum temperature value to the
ambient. Above value At2, the alarm status will be signalled
with the alarm icon flashing, the temperature flashing and an
internal buzzer acoustically signals the existence of an
anomaly. The alarm is signalled after the Ald time. The
alarm does not suspend any defrosting in progress.
At1+1 ÷ 45 °C
+45°C
AU1
Minimum humidity alarm
Enables defining a minimum humidity value to the ambient
to be humidified. Below the AU1 value, the Eu alarm status
will be signalled with the alarm icon flashing and the buzzer
active. Silencing, the humidity and the alarm icon remain
flashing. The alarm is signalled after the Ald time.
1 ÷ AU2-1 Rh%
1 Rh%
AU2
Maximum humidity alarm
Enables defining a maximum humidity value to the ambient
to be humidified. Below the AU2 value, the Eu alarm status
will be signalled with the alarm icon flashing and the buzzer
active. By silencing, the humidity and the alarm icon remain
flashing.
The alarm is signalled after the Ald time. AU2=99 does not
signal the alarm.
AU1+1 ÷ 99 Rh%
99 Rh%
rA
Air change enabling in real time
With rA=1 it is possible to set up to 6 air changes in real time
during one day, through parameters rA1…rA6.
0 = Disabled
1 = Enabled
0
rA1
…
rA6
Air change times programming
It is possible to set up to 6 times for the air changes. The
previous value blocks the subsequent one making them
sequential.
00:00 ÷ 23:50
--
drA
Air change duration
0 ÷ 10 min
6 min
tEu
Evaporator probe temperature display
(if dE =1 nothing is displayed)
temperature
only
reading
CHAP. 5 - Parameters programming

PLUS300 EXPERT U THR
Pag. 17
USE AND MAINTENANCE MANUAL
Rev. 01-18
SECOND LEVEL PROGRAMMING (Installer Level)
To access the second programming level press the UP ()and DOWN ()keys and the
LIGHT key simultaneously for a few seconds.
When the first programming variable appears the system automatically goes to stand-by.
1. Select the variable to be modified by pressing the UP ()and DOWN () keys.
When the parameter has been selected it is possible:
2. To display the parameter setting by pressing the SET key.
3. To modify the parameter setting by pressing the SET key and pressing the ()or ()
key.
4. When setting has been completed you can exit the menu by pressing the ()and ()
keys
simultaneously and keeping them pressed until the cold room temperature reappears.
5. Modifications are saved automatically when you exit the configuration menu.
6. Press STAND-BY to enable electronic control.
LIST OF 2ND LEVEL VARIABLES (Installer Level)
VARIABLES
MEANING
VALUES
DEFAULT
AC
Microdoor input status (with door closed)
0 = usually open
1 = usually closed
0
Pc
main alarm digital input status
0 = NA
1 = NC
0 = NA
F3
Fans status when cold, hot,
humidification and dehumidification are
at a stand-still
0 = Fans in continuous start
1 = Fans switched-off if cold,
hot, humidification and
dehumidification switched-off
1
F4
Fans pause during defrosting
0 = Fans working during
defrosting
1 = Fans not working during
defrosting
1
F6
Evaporator fans activation for air
recirculation. The fans activate for a time
defined byF7 if they have not started working
for the F6 time.
If activation time coincides with the defrosting
time, end of defrosting is awaited.
The speed of the fans (high/low) is the same
as that selectedfor the phase in progress.
0 –240 min
0 = (function not activated)
0 min
F7
Evaporator fans duration for air
recirculation. Fans working time for F6.
0-240 sec.
0:00:10
CHAP. 5 - Parameters programming
5.9
5.10

PLUS300 EXPERT U THR
Pag. 18
USE AND MAINTENANCE MANUAL
Rev. 01-18
F8
Fans speed during
seasoning/preservation . The value of
this variable is amended based on the set-
up made during the last phase of a
performed program.
0 = High speed
1 = Low speed
(only if rin=1)
0
Pr
Refreshment period.
Interval between one refreshment and the
subsequent one. The refreshment is a
work pause in which cold, hot, humidifies
and dehumidifies are disabled.
0 ÷ 24 hours
(at 10 min steps)
0 = Disabled
0 h
dr
Refreshment phase duration.
1 ÷ 240 min
120 min
rin
K7 Multifunction relay function choice.
0 = Refreshment
1 = Fans low speed
0
Ald
Signal delay and alarm display time of
minimum or maximum temperature or
humidity.
(1 min ÷ 4 hours)
240 min
C1
Minimum time between switch-off and
subsequent ignition of the compressor.
It also stops the fans if they are not active
for other functions
0...15 min
0
dEU
Dehumidification method selection
The separate dehumidification calls hot
and cold only for temperature
0 = cooling
1 = heating
2 = separate dehumidification
0
EnU
Humidification enabling
0 = disabled
1 = enabled
1
End
Dehumidification enabling
0 = disabled
1 = enabled
1
Cat
Ambient probe value correction
-10...+10
0
CaU
Humidity probe value correction
-20...+20
0
EnH
Hot enabling
EnH = 1 hot enabled
EnH = 0 hot disabled
1
Hr
Humidity management
Hr = 1 enables humidity
management
Hr = 0 disables humidity
management The humidity
probecan be disconnected
without error on display.
The evaporator probe is
displayed instead of
humidity(if dE= 0)
1
dE
Evaporator probe exclusion
0 = probe present
1 = probe absent
1
d1
Type of defrosting, at cycle inversion (hot
gas) or resistance. The compressor output
is also activated with hot gas
1 = with hot gas
0 = with resistance
0
LSt
Minimum value attributable to setpoint
of temperature
-45 ÷ HSt °C
-45°C
HSt
Maximum value attributable to setpoint
of temperature
+45 ÷ LSt °C
+45°C
CHAP. 5 - Parameters programming

PLUS300 EXPERT U THR
Pag. 19
USE AND MAINTENANCE MANUAL
Rev. 01-18
btF
Temperature differential referred to Setpoint
forCOLD BLOCK.
It constitutes the SET-btF limit below which the
cold call relay and the dehumidification relay
are disabled.
0 ÷ 20 °C
0 = Disabled
2
btC
Temperature differential referred to
Setpoint for HOT BLOCK.
It constitutes the SET+btC limit above
which the hot call relay , the humidification
relay and the dehumidification relay are
disabled.
0 ÷ 20 °C
0 = Disabled
2
dEt
Limit time for DEHUMIDIFICATION.
If the dehumidification request is not
satisfied (achievement of humidity SET)
within the time (dEt), the variable (dEO) is
taken into consideration for the operation
to be performed. Counting starts at every
new dehumidification request.
(0 min ÷ 4 hours)
(1 min steps)
0 = Disabled
0
dEo
Operation to be performed in case Timeout
for dehumidification (dEt) intervenes
dEO = 0 an alarm signal (Ed) + buzzer +
alarm relay is given. The alarm is
displayed even when humidity set is
achieved; it does not block the normal
functioning and once silenced, the dEt
count re-starts.
dEO = 1 a refreshment of the duration (dr)
is launched and the timer relating to the
interval (Pr), if present, is recharged.
0 = alarm only
1 = a refreshment is
performed.
0
Ad
Net address for connection to TeleNET
supervision system.
0 ÷ 31
0
Aut
Automatic cycles management or via
TeleNET. For managing the cycles via
TeleNET to set Aut=1
0 = local cycles
1 = TeleNET management
0
Cg
Seasoning or germination selection
0 = seasoning cycles active
1 = germination day/night
cycle active
0
CgA
Not used.
0
0
tg2
Not used.
0
0
P1
Password: type of protection.
(Active when PA is different from 0).
0 = Total block. It is possible to
onlysee the temperature and
humidity set point.
1 = Blocks access in 1st and
2nd level programmes.
Blocks access in germination
cycle amendment and
programmesamendment.
2 = Blocks access in 1st and
2nd level programmes.
3 = Blocks access in 2nd level
programmes.
3
CHAP. 5 - Parameters programming

PLUS300 EXPERT U THR
Pag. 20
USE AND MAINTENANCE MANUAL
Rev. 01-18
PA
Protection password
0 –999
dMY
Current date
dd:mm:yy
HMS
Current time
0:00...23:59
reL
Software release
Shows the software release
(reading only)
6
AUTOMATIC PROGRAMS Pr1, Pr2, Pr3, Pr4, Pr5
To access the automatic programmes parameters, keep keys START/STOP and
SET pressed for a few seconds (the function is active only if Cg=0).
1. Using key ()or key () select the program to be amended. After having selected the
program, press the SET key to display the parameters.
2. Using key ()or key () select the parameter to be amended.
3. Amend the setting by keeping the SET key pressed and by pressing one of the keys
() or ().
4. Once configuration values have been set, to exit the menu press keys () and ()
simultaneously keeping them pressed for a few seconds, until the temperature value
appears.
5. Memorisation of the amendments made to the variables will happen automatically when
exiting the configuration menu. Exiting from the menu happens spontaneously after an
inactivity period or by simultaneously pressing keys () and ()for a few seconds.
The following table represents any one of the Pr1, Pr2, Pr3, Pr4, Pr5 programmes.
CHAP. 5 - Parameters programming
5.11
Other manuals for PLUS300 Expert VD 4
2
This manual suits for next models
2
Table of contents
Other Pego Control Panel manuals

Pego
Pego ECP200 Expert d7.5 User manual

Pego
Pego ECP300 EXPERT VD Series User manual

Pego
Pego ECP 200 Base 2 User manual

Pego
Pego ECP200 Expert d7.5 User manual

Pego
Pego ECP200 STEPPER User manual

Pego
Pego 100N MASTER3 Operating instructions

Pego
Pego ECP300 EXPERT VD Series User manual

Pego
Pego ECP202BASE User manual

Pego
Pego ECP300 EXPERT VD Series User manual

Pego
Pego 202BASE User manual