Penn Connected PC10 User manual

LIT-12013314
PC10
Johnson Controls
www.penncontrols.com
2020-03-03
PENN Connected PC10 Commissioning
Guide


Contents
ContentsIntroduction.................................................................................................................................... 3
Hardware requirements..................................................................................................................... 3
Software requirements....................................................................................................................... 3
Surveying the site........................................................................................................................... 4
Mounting guidelines...................................................................................................................... 5
Installation sequence..................................................................................................................... 6
Installing the gateway................................................................................................................... 7
Installing the repeaters................................................................................................................. 8
Installing the temperature sensors............................................................................................. 9
Installing the door sensors......................................................................................................... 10
Commissioning the gateway...................................................................................................... 11
Commissioning the sensors........................................................................................................ 12
Signing off..................................................................................................................................... 13
Related documentation............................................................................................................... 14
Single point of contact................................................................................................................. 15
Software terms............................................................................................................................. 16
Product warranty.......................................................................................................................... 17
Patents........................................................................................................................................... 18
PENN Connected PC10 Commissioning Guide i


Introduction
This document describes how to install and commission a PENN Connected PC10 Remote Wireless
Monitoring System to monitor refrigeration equipment. The following inexhaustive list provides
examples of refrigeration equipment that the PC10 system can monitor:
• Wall chillers
• Wall freezers
• Well freezers
• Plug-in refrigerators and freezers
• Chiller and freezer rooms
• Chiller and freezer room doors
Hardware requirements
Table 1: PENN Connected hardware
Product code Description Region Quantity
RMZ-1214-E10 Single-probe, internal temperature sensor
RMZ1214E11-NT1 Cable lenth: 0.9 m NTC
RMZ1214E11-NT3
Dual-probe, internal and
external temperature sensor Cable length: 2.8 m NTC
One for each refrigeration unit
RMZ1214E61-DS1 Magnetic, external door sensor with reed contact switch
All
One for each chiller or freezer
room door
RMZ1214R10-UK UK and
Ireland
RMZ1214R10-EU Europe
RMZ1214R10-US
Repeater to extend the wireless network range
North
America
One for every 15 temperature
sensors
RMZ1216C20-UK UK and
Ireland
RMZ1216C20-EU
GSM and GPRS gateway for Zigbee® wireless sensors
Europe
RMZ1218C40-UK UK and
Ireland
RMZ1218C40-EU Europe
RMZ1218C40-US
LTE 4G gateway for ZigBee wireless sensors
North
America
One for each site
Software requirements
• Android® device, minimum version 4.4.4.
• PENN Connected Commissioning app. Download the app for free from the Google Play® store.
3PENN Connected PC10 Commissioning Guide

Surveying the site
About this task: Before you install and commission the hardware, survey the site and make the
following observations:
• The location of the refrigeration units, freezer rooms, and chiller rooms
• The locations of the gateway and repeaters
• The presence of any structures or walls that may interfere with the signal strength of the
hardware
See the following figure and table for the typical layout of a site and its hardware.
Figure 1: Typical site layout
Note: The shaded cells indicate refrigeration units.
Table 2: Typical site layout
Callout Description
1 Gateway
2 Repeaters
3 Freezer room
4 Chiller room
PENN Connected PC10 Commissioning Guide4

Mounting guidelines
Note: The installation engineer consults with the site manager to identify the mounting
locations for the hardware.
• Mount the gateway and repeaters in an open enclosure in a safe and secure position.
• The maximum range from a gateway to a sensor is 30 m (98.42 ft).
• It is best practice to install independent power supplies for the gateway and repeaters.
5PENN Connected PC10 Commissioning Guide

Installation sequence
About this task: Install the hardware in the following sequence:
1. Gateway
2. Repeaters
3. Temperature and door sensors
PENN Connected PC10 Commissioning Guide6

Installing the gateway
1. Place the gateway in a safe and secure location.
2. Connect the gateway to a power supply and check that it powers on in the following sequence:
- The power light blinks blue once every second.
- The data light blinks red when the gateway connects to the global system for mobile
communications (GSM) network.
- The server light turns green when the gateway connects to the server.
Figure 2: Gateway power on sequence
Table 3: Gateway power on sequence
Callout Description
1 Power light
2 Data light
3 Server light
7PENN Connected PC10 Commissioning Guide

Installing the repeaters
About this task: Use the repeaters to extend the range of the wireless network.
1. Identify the locations for the repeaters.
2. Mount the repeaters with or without a bracket. To secure the repeaters, use screws, tie wraps,
or double-sided tape.
3. Connect the repeaters to a power supply; the repeaters flash blue.
PENN Connected PC10 Commissioning Guide8

Installing the temperature sensors
About this task:
Each temperature sensor ships with a set of stickers that display a serial code. The serial code on
the stickers matches the serial code on the side of the sensor. Use these stickers to trace the tem-
perature sensors.
1. Mount a sensor with or without a bracket in each refrigeration unit that you want to monitor.
To secure the sensor, use screws, tie wraps, or double-sided tape.
2. Attach a sticker to a visible location on the refrigeration unit.
3. Swipe the sensor once from top to bottom with a magnet and observe the following light
sequence:
- The sensor light turns blue.
- The sensor light flashes green approximately four times.
- The sensor light turns off.
9PENN Connected PC10 Commissioning Guide

Installing the door sensors
About this task: Each door sensor ships with a set of stickers that display a serial code. The serial
code on the stickers matches the serial code on the side of the sensor. Use these stickers to trace
the door sensors.
1. Mount a sensor with or without a bracket to each chiller or freezer room door that you want to
monitor. To secure the sensor, use screws, tie wraps, or double-sided tape.
2. Attach the magnetic strip to the frame of the chiller or freezer room door.
3. Attach a sticker to a visible location on the refrigeration unit.
4. Swipe the sensor once from top to bottom with a magnet and observe the following light
sequence:
- The sensor light turns blue.
- The sensor light flashes green approximately four times.
- The sensor light turns off.
PENN Connected PC10 Commissioning Guide10

Commissioning the gateway
1. On the Android device, open the PENN Connected Commissioning app and enter the username
and password that the PENN Connected administrator sent by email.
2. Commission the gateway in one of the following ways:
- Locate the unique 15 or 16-digit serial number on the side of the gateway. In the ICCID or
IMEI field, enter the serial number, and tap Register.
- Tap SCAN GATEWAY to open the camera. Scan the QR code or the barcode on the side of the
gateway, and tap Register.
11PENN Connected PC10 Commissioning Guide

Commissioning the sensors
1. On the Android device, in the upper-right of the app, tap +.
2. Commission a sensor in one of the following ways:
- Tap SCAN to open the camera. Scan the QR code or the barcode on the side of the sensor.
- Locate the unique 16-digit serial number on the side of the sensor. In the Or Enter Device
MAC Address field, enter the serial number.
3. From the Select sensor type list, select the sensor type from the available options, and tap
Register.
4. In the Enter cabinet name field, enter a name for the sensor.
5. From the Select alarm configuration list, select the appropriate alarm parameter from the
available options.
Note: You can change these alarm parameters on the PENN Connected platform. On the
Manage Alarms page, click on the alarm row to open the Edit Sensor dialog box.
Results: To indicate a successful commission, the sensor name displays in green on the app. To
commission another sensor, in the upper-right of the screen, tap +, and repeat Steps 1 to 5.
PENN Connected PC10 Commissioning Guide12

Signing off
About this task: To conclude the commissioning process, tap SIGN OFF. The following options dis-
play on the app:
Sign off with X units
Submit the commissioned units for the current site.
Sign off and view
Submit the commissioned units for the current site, and view them on the PENN Connected
platform.
Sign off and add new
Submit the commissioned units for the current site, and commission a new site.
Cancel
Cancel the submission of the current site.
13PENN Connected PC10 Commissioning Guide

Related documentation
Table 4: Related documentation
Document title Document Number
PENN Connected E10 Temperature Sensor Catalog Page LIT-1901118
PENN Connected E11 Temperature Sensor Catalog Page LIT-1901119
PENN Connected R10 Repeater Catalog Page LIT-1901120
PENN Connected C20 Gateway Catalog Page LIT-1901121
PENN Connected PC10 User Guide LIT-12013307
PENN Connected PC10 Commissioning Guide14

Single point of contact
APAC Europe NA/SA
JOHNSON CONTROLS
C/O CONTROLS PRODUCT MANAGEMENT
NO. 32 CHANGJIJANG RD NEW DISTRICT
WUXI JIANGSU PROVINCE 214028
CHINA
JOHNSON CONTROLS
WESTENDHOF 3
45143 ESSEN
GERMANY
JOHNSON CONTROLS
507 E MICHIGAN ST
MILWAUKEE WI 53202
USA
For more contact information, refer to www.johnsoncontrols.com/locations.
15PENN Connected PC10 Commissioning Guide

Software terms
Use of the software that is in (or constitutes) this product, or access to the cloud, or
hosted services applicable to this product, if any, is subject to applicable terms set forth at
www.johnsoncontrols.com/techterms. Your use of this product constitutes an agreement to such
terms.
PENN Connected PC10 Commissioning Guide16
This manual suits for next models
12
Table of contents
Other Penn Control System manuals

Penn
Penn A421 Series User manual

Penn
Penn A25 Series Service manual

Penn
Penn System 450 Series User manual

Penn
Penn A28 Series User manual

Penn
Penn A421 Series User manual

Penn
Penn System 450 Series Service manual

Penn
Penn V43 Series V243 Series Manual

Penn
Penn P77 Series User manual

Penn
Penn P78 Series User manual

Penn
Penn System 450 Series Service manual