23833A179 11/12/12
3
1. The lower turn-off control should be set so that the
pump stops at approximately the top of the pump.
2. The upper turn-on control should be set above the
lower turn-off control. The exact height between
the two controls is determined by the number of
pump starts desired and the depth of the basin.
A maximum of 10 starts per hour should not be
exceeded.
3. The override control is set at a specified height
above the upper turn-on control.
4. The alarm control is set about 6" to 12" above the
override control.
5. No control should be set above the inlet invert.
Junction Boxes:
If a junction box is used in a hazardous location, it
must be a hazardous location approved type with
hazardous location cord connectors. Wires from the
junction box must pass through a hazardous location
seal connector.
CAUTION – No persons should be in the basin when
pump is lowered into position! DO NOT lift pump in a
manner where any failure could result in loss of life.
Air Venting:
Air tends to trap in the pump volute when water raises
in the sump or when the pump is lowered into water
after service. To vent off this air, a small hole is drilled
into the pump volute. Be sure this vent hole is clean
after any service work on pump.
USAGE – The TPL15 grinder pumps are for pumping
domestic sewage. These pumps are not to be used for
pumping commercial or industrial sewage from motels,
schools, apartments, factories, etc.
PUMP MODELS – The TPL15 pumps are equipped
with 230 volt single phase motors with seal leak
detector.
CAUTION – PUMP IS ONLY TO BE DISASSEMBLED
AT MYERS FACTORY OR AN AUTHORIZED MYERS
SERVICE FACILITY.
DESCRIPTION OF PUMP – This pump is intended to
grind and pump all normal sewage for home use.
Pump is of heavy duty construction, and submersible
type for long life when pumping ground sewage. Motor
is capacitor start, capacitor run for single phase.
Capacitors and start relay are mounted in the electrical
control box. All single phase motors must have special
electrical control box furnished by Myers.
INSTALLING SINGLE PHASE MOTORS WITH
CONTROLS OTHER THAN MYERS VOIDS
WARRANTY.
CAUTION – After pump is installed NEVER WORK
ON MOTOR OR GRINDER UNIT WITHOUT
DISCONNECTING MOTOR LEAD WIRES FROM
CONTROL PANEL. DON’T RELY ON OPENING
CIRCUIT BREAKER ONLY.
Pump has two oil-filled chambers — 1) the motor and
ball bearings and, 2) the seal chamber—for long life
and best heat transfer.
The lower seal above the pump impeller acts as
a buffer for upper seal that holds oil in the motor
chamber. If lower seal leaks for any reason, water
enters the seal chamber. If motor has the seal leak
detector, the electrode will contact the water and close
the circuit to the red seal light in the control panel
indicating motor must be serviced before upper seal
fails.
MOTOR OVERLOAD PROTECTION – The motor is
provided with an on-winding overload switch. If motor
overloads or overheats for any reason, the switch
opens stopping motor. As soon as the motor cools to
normal temperature the switch closes and restarts the
motor.
MOTOR POWER CORDS – Pump models with seal
leak detector use a 5 conductor cord. The three power
conductors are BLACK, WHITE, RED, the BROWN
conductor connects to the seal leak probe and GREEN
conductor connects to the ground screw inside the
cord cap.
CORD SEAL – The lines from the motor chamber are
sealed with a rubber sealing grommet that prevents
oil from leaking into the cord cap compartment. If
necessary to replace power cord, the sealing grommet
must not be loosened. This wire seal is removed only
for complete motor repair that must be done at an
authorized motor repair shop.
IMPORTANT – Ground wires must be connected in the
control box to grounding bar, which is connected to a
good outside ground. MOTOR IS NOT SAFE UNLESS
GROUNDED.
SINGLE PHASE CONTROL BOX – Single phase
pumps must use the Myers control box. Warranty is
void if other than Myers single phase control box is
used.
THREE PHASE CONTROL BOX – Any suitable three
phase control equipment can be used for simplex
or duplex operation. These control boxes are also
available from Myers. If other than Myers box is used,
overload heaters must be selected in accordance with
full load amp ratings.
If any amp readings are higher than listed, it indicates
voltage may be higher or lower than normal, or that
pump grinder may be clogged with trash causing extra
load on motor.