Polyaire Zonemaster Unipoint User manual

UNIPOINT CONTROL
SYSTEM
Setup Guide
Polyaire™ Pty Ltd
11-13 White Road
GEPPS CROSS
South Australia, 5094
Tel: (08) 8349 8466
Fax: (08) 8349 8446
www.polyaire.com.au


CONTENTS
Features 1
Application 1
Components 2
Conguration 3
Installation 5
Zone Address and Allocation 9
RecommendedCommissioningProcedure 10
1. Initiating and Exit Setting Process 10
2. Room Temperature Sensor 10
3. Number of Zones in the System 10
4. Supply Air Safety High & Low Limits 11
5. Spill/Bypass Air Setpoint 11
6. Naming Zones 13
7. Damper on/off Test 13
Information Sheet 14
TroubleShootingGuide 15
Specications 16
Liability
Please read the instructions before installing this Zonemaster Zoning
Control System. Polyaire Pty Ltd does not accept any responsibility for
loss or damage that may occur as a result of the installation of this Zoning
Control System.

FEATURES
• Manual and time programmable zone on/off control.
• Expandable up to 8 zones based on a serial control bus.
• Each zone has a unique address selected by a DIP switch.
• LCD indicator for zone status and parameter display.
• Room temperature display using an on-board sensor.
• Real time clock with battery backup.
• 5-1-1 zone on/off time programs.
• Personalised zone labelling.
• Auto spill/bypass --- the designated zones/bypass are forced
open when all zones are turned off.
• Safety system --- Opens all dampers if the supply air
temperature is less than low limit or more than high limit.
• All zones automatically return their original on/off state once
power up.
APPLICATION
Zonemaster UniPoint control system is a fully featured and engineered
system that is well suited to all ducted, reverse cycle, heating and
evaporative air conditioning system for light commercial, residential or
apartment applications.
Page 1

COMPONENTS
1) Touchpad
User can input control commands from the touchpad to
turn a zone on or off. The LCD on the touchpad displays
clock, room temperature and zone status.
2) Damper Controller
Damper controller receives control signal from the
touchpad to turn on/off the zone. Each damper controller
hasauniqueaddressidentiedbythetouchpad.
3) Motorised Damper
Motorised damper drives the blade of the damper to turn
on/off the air from ducting to a zone.
4) BridgeCable
Bridge cable connects the damper controller and the
motorised damper together.
5) Supply Air Sensor
Supply air sensor measures the temperature of the
supply air for safety purpose.
6) Power Supply
The 24VAC transformer provides power to the touchpad
and damper controllers.
7) Battery
3.6 V rechargeable battery for real time clock backup.
8) Double Adaptor (Optional)
It can be used to connect the touchpad with the
control bus to shorten the length of the cable.
9) MountingBracket
Page 2

Page 3
CONFIGURATION
The cabling of the Zonemaster UniPoint is straightforward. One
connection is to connect the touchpad, dampers and power supply in
series via a control bus as shown on Figure 1.
Figure 2 shows another connection in which a double adaptor is used to
connect the touchpad in the middle of the control bus to save cables. The
installation procedure is detailed as follows.
Figure1.Wiringdiagram1

Page 4
Figure2.Wiringdiagram2

INSTALLATION
1) Take off the small cover on the top of the damper controller.
2) Allocate and set unique addresses to all zones with
considerationofspillprivilegesforthezones. Please
refer to the Zone Address section for details. Please note that
bypass damper has a special address as shown in Figure 3.
Page 5

3) Mount the damper controller on the top of the motorised
damper, or installed elsewhere close to the motorised damper.
Plug the bridge cable into the damper port on the damper
controller and the motor.
Warning - Do not plug the damper controller into any
other motorised damper except a Polyaire authorised one.
4) Apply the power to the transformer by plugging in the
transformer into the 240VAC power outlet.
5) Plug the 24VAC power supply into the socket on the last
damper controller at the end of the control bus. The LED light
on the damper controller should be on. Otherwise, check the
power supply and the connection.
Page 6

Page 7
6) Use a pre-tested cable to connect the last damper controller
with the next one. The LED light on the next damper controller
should also be on. If not, check the cable and the connection.
7) Repeat the step 6) until all damper controllers are connected
together in series and all LED lights are on.
8) Use another pre-tested cable to connect the touchpad with the
rstdampercontrollerasshowninFigure1orinthemiddleof
the control bus via a double adaptor as shown in Figure 2.

Page 8
9) Check all the LED lights on the damper controllers again.
Ifsomeofthelightsareoff,thecabletotherstoff-light
damper controller could be crossed over. Check and replace it.
10) Repeat step 9) until all of the lights are on and the LCD screen
on the touchpad shows clock time and the room temperature
where the touchpad is located after showing “initiate” on the
second line for about 15 seconds.
11) Hold down both and buttons on the touchpad for
about 5 seconds to enter the setting mode (refer to next
section). Check all the LED lights on the damper controllers
again.AlloftheLEDlightsmustbeashinginone-second
interval. Otherwise, check the cable and the connection.
12) Turn off the power and disconnect the touchpad.
13) Position the touchpad at the right place. Ideally, its position
isapproximate1.6Mofftheooronthewall.Fitthecable
through the wall cavity and connect the touchpad again.
14) Apply the power again to the transformer. The LCD should
show clock time and temperature. If not, check the cable.
15) Mount the supply air sensor in the supply air duct upstream the
motorised damper.
16) Fit the sensor cable through the
wall cavity and plug into the socket
on the back of the touchpad.
17) Connect the battery by plugging into
the socket on the back of the touchpad.
battery
sensor

Page 9
18) Mount the touchpad onto the bracket in the wall cavity.
Please note that the touchpad should not be exposed to
directsunlightandotherheatsources.
ZONE ADDRESS AND ALLOCATION
Each damper should have a unique address in the serial control bus to
beidentiedbythetouchpad.Thisaddressisconguredbyastandard
4-way DIP switch inside the damper controller to provide 8 unique normal
zone damper addresses and a special address for the bypass damper. All
damper addresses can be set as shown in Figure 3.
When allocating address to each zone in spill mode, it is strongly
recommended to give lower addresses to those zones that have higher
spill privileges. The lower the address, the higher the spill privilege the
zone has. When the spill setpoint is reached, the touchpad instructs zone
1toopenasspill.Iftherstspillzonecannotsatisfythespillaircontrol,
the zone 2 will be instructed to open to spill excess air. This process will
continueuntilthespillairsetpointissatisedinthesystem.Suchaspillair
control strategy implemented in the Zonemaster UniPoint control system
requires the installer to allocate the zone 1 near the return air grilles.
Figure3.Damperaddresssetting

Page 10
RECOMMENDED COMMISSIONING PROCEDURE
1.InitiatingandExitSettingProcess
The Zonemaster UniPoint has several parametres that must be set in the
commissioning stage.
1) Hold down both and buttons
for about 5 seconds until the LCD displays
‘Setting’ on the top line of the LCD screen.
2) At the setting mode, pressing button at any
time will return to the normal operation mode.
2. Room Temperature Sensor
The touchpad has an onboard sensor to measure the temperature of
the room for indication purpose. The sensor can be calibrated by the
parameter and provides more accurate temperature display.
1) Using an accurate probe to measure the
temperature of the area you want to calibrate
and record the value.
2) At the setting mode, press button
until the LCD displays the ‘Sensor’ screen.
3) Press or button to adjust the
displayed value to the record value.
3. Number of Zones in the System
For the purpose of zone status display and spill/bypass zone
calculation, the controller needs to know the total number of
on/off zones in the system. Its factory default value is 8.
1) At the setting mode, press button until the
LCD displays the ‘O/FZone’ screen.
2) Press or button to adjust the number
of zones to the total number of the zones installed.
It can be selected from 1(show ‘Zone1’) to 8
(show ‘Z1—Z8’).

Page 11
4.SupplyAirSafetyHigh&LowLimits
For safety reasons, the system monitors the
supply air temperature closely.
If the temperature moves outside of the limits,
all dampers in the system are forced open and
the LCD displays ‘Safety’ on screen.
The factory default supply air safety high & low
limits are 60oC and 5°C respectively and safety
control is disabled.
1) At the setting mode, press button until the
LCD displays the ‘H_limit’ screen.
2) Press or button to change the high
limit to the desired value. The adjustable range
of the high limit is from 45°C to 75°C.
3) Press button once again, the LCD screen will
display the ‘L_Limit’.
4) Press or button to change the low
limit to the desired value. The adjustable range
of the low limit is from 0°C to 15°C.
If the customer does not want the safety function, the supply air
sensor is not needed to be installed. The safety H_limit and L-limit
MUSTbedisabledbypressingbuttonduringthesetup.
5. Spill/Bypass Air Setpoint
Spill/Bypass air is primarily used to relieve duct pressure for the safety
of the ducting. Such a control is achieved by comparing the system
requirement with a setpoint. The factory default is in spill mode and the
setpoint is 30% of the total number of zones, which is equivalent to 30% of
thetotalairowacrossthefancoil.

Page 12
Spill mode uses the zones with the lowest addresses in the system as spill
zones that will be automatically forced to open if the total number of open
zones is less than its setpoint.
In bypass mode, a bypass damper is used to return the air directly to the
duct if the total number of open zones is less than its setpoint. The bypass
damper is also serially connected with other dampers and has a special
address as mentioned before.
1) At the setting mode, press button until
the LCD displays the ‘Spill’ or ‘Bypass’ screen.
2) Press button to select spill or bypass mode.
3) Press and button to change the
spill/bypass setpoint to its desired value. The
adjustable range is from 0% to 50%.
If no spill or bypass control is required in the
system, the setpoint MUST be set to 0.

Page 13
6.NamingZones
The name of a zone is called‘Zone_addr’. For example, zone 1, which
has an address of 1, is called ‘Zone_1’ on its factory default. The names
can be customised as you prefer as follows:
1) At setting mode, press button until the
LCDdisplaystherstzonenaming,forexample,
‘Z1 Name’ on the top line of the LCD. The second
line shows the current name of zone 1.
2) Press or button to select one of the
27 preset zone names for the zone.
3) To make changes to the preset selected name,
press button to move to the character that
isashing.
4) Use or button to select the character
from the list as desired. There are 26 alphabets
in capital and normal case, 10 numbers and a
space in the list.
5) Press button to select the next zone
naming screen and follow steps 2 to 4 to
customise the name of the zone.
7. Damper on/off Test
1) Switch on the air conditioner.
2) Press button to turn each of the zones on or off to
check if the damper is correctly connected by feeling the air
at the outlet. Refer to User’s manual for the operation.

INFORMATION SHEET
The following zone table is designed to assist installation and
commissioning.
Address Default Name Custom Name
Zone_1
Zone_2
Zone_3
Zone_4
Zone_5
Zone_6
Zone_7
Zone_8
Parameter Default Value Custom Value
O/F Zone Z1—Z8
High limit disable/60 oC
Low limit Disable/5 oC
Spill Spill/30%
Page 14

Page 15
TROUBLE SHOOTING GUIDE
Problem SuggestedAction
The LED light on the
damper controller
does not lit up after
powering up.
• Check the power supply.
• Check the cable to and from this damper
controller.
• Check the connection between the cables and
the controller.
Touchpad has
nothing shown on
LCD.
• Check the power supply.
• Check the cable and plug to the touchpad.
Touchpad display is
not normal.
•Disconnectthebatteryatrst.
• Reset the touchpad by turning off and turning
on the power supply again. If the display is
normal, plug in the battery again.
Dampers have no
response when
turning it on or off.
• Check the damper controller and make sure
that the LED lit up.
• Check the damper address.
• Check the cable to the damper controller.
Some zones cannot
be turned off.
• Check if it is spill zone (with lower address).
• Check spill setpoint.
All zones open and
touchpad display
“safety”.
• Check high & low limit setting.
• Check and replace the supply air sensor.
Please contact distributors for any other
problems not listed as above.

Page 16
SPECIFICATIONS
Electrical Requirements
Power supply 24VAC ± 10%
Line frequency 50 Hz
Components Power Consumption
Touchpad 0.5 VA
Damper controller 2.5 VA
Environmental Requirements
Operating temperature 0°C to 60°C
Altitude 0 to 2000 metres
Operating relative humidity 10% to 80%
Avoid static electricity hazards
Avoid electromagnetic radiation sources
Avoid dust contamination
Avoid highly corrosive environments
Touchpad
Power input 24VAC, 50Hz
Dimensions 78W x 118H x 13D
Damper Controller
Power input 24VAC, 50Hz
Dimensions 60W x 85H x 25D
Transformer
Input Voltage 240VAC, 50Hz
Output Voltage 24VAC, 50Hz
Wattage 24W
Supply Air Sensor NTCtype,10kΩat25°C
Battery AAAM rechargeable battery, 3.6V
Control Bus 50 metres

Table of contents
Other Polyaire Control System manuals
Popular Control System manuals by other brands

Johnson Controls
Johnson Controls CCXL01 Engineering manual

Intermatic
Intermatic RC2163E Installation, operation & service manual

Yetter
Yetter AIR ADJUST 2940 Operator's manual

Rotel
Rotel RR-700 owner's manual

Pentair
Pentair EasyTouch Appliance Upgrade Guide

Grundfos
Grundfos PC Tool CU 300 Installation and operating instructions