PAD300-LFSB
Addressable Low Frequency Sounder Base
8830213- REV A • 10/22 PAGE 1 OF 2
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com
Description
The Addressable Low Frequency Sounder Base (PAD300-LFSB) is a
sounder base that may be utilized in a variety of applications. The base
has a locking feature for the detector that may be used or removed in
the eld. Once the head is removed, the sounder is accessible in the
bottom of the unit.
The PAD300-LFSB low frequency sounder base is designed to meet
NFPA 72 sleeping space requirements to produce a frequency of 520
Hz +/- 10% with a square wave.
It is shown that a lower frequency, centered around 520 Hz, is the ideal
to awaken sleeping occupants, even those with mild to severe hearing
loss.
The base has an independent sounder module that may be programmed
as a single station, zone or all call sounder. The PAD300-LFSB
passes through the sound pattern sent to the sounder, therefore it may
reproduce in any pattern the power supply provides.
The PAD300-LFSB does not consume an address on the loop and
is fully programmable to operate with any input. Once activated the
sounder will also follow the input from the power source and de-
activate accordingly.
Technical Specications
SLC Voltage 24VDC
SLC Standby Current 300 µA
PWR Voltage 16-33 VDC
PWR Active Current 155mA
Alarm LED Current 1.4mA
Sound Pressure Level 75dB @ 10ft per UL464
85dB @ 10ft per UL268
Installation Temperature Range 32 to 150°F (0°C to 66°C)
Operating Humidity Range < 93% (Non-condensing)
Dimensions 6.4in (163 mm)
Weight 240 g (8.47 oz)
Height 1.57 in (40 mm)
Features
• Addressable low frequency sounder base, allows for single
station, grouped or all call activation
• May be mapped to any device connected to the control panel
• Terminals accept 22 to 12 AWG wire sizes
• Supports Class A, Class X and Class B wiring
• Does not require SLC Loop address, uses PAD sub point
addressing feature
• Complies with the Low Frequency Signal Requirements per
NFPA 72 and UL 464 for Audible Signaling Devices
• 24 VDC Sounder base power connection supervised internally
by each sounder base. No external power supervision relays
required
• UUKL Listed for smoke control