UB10.241
– U Series 24V, 10A
March 2006 DS-UB10.241-ENRev 2.0 / All parameters are specified at 24V, 10A and 25°C ambient unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
1/11
DC-UPS
■Requires only one 12V battery
■Regulated output voltage in buffer mode
■Compact, width only 49mm
■50% power reserves
■Low voltage drop between input and output
■Electronically protected against output overloads
■Extensive battery management including battery
quality and installation tests
■Soft charger for optimum battery life
■Extensive diagnostic and monitoring functions
■Selectable buffer time limiter
■3 Year warranty
1. GENERAL DESCRIPTION 2. SHORT-FORM DATA
Operating voltage DC 24V
Voltage range 22.5-30Vdc
Output voltage 22.4V ±2% Buffer mode
Voltage drop IN/OUT < 0.3V at 10A Normal mode
Output current 0 to 15A Normal mode
0 to 10A, cont. Buffer mode
0 to 15A, for 5s Buffer mode
Input current typ. 0.12A *) Standby mode
max. 1.1A *) Charging mode
*) add output current to calculate the total input current
Charging current typ. 1.5A into 12V battery
Charging time typ. 5h 12V, 7Ah battery
Cut-in threshold typ. 22.5V
Power losses 2.7W Standby mode
4.6W 10A, Normal mode
Buffer time min. 6’ 15’’ at 10A, 7Ah battery
typ. 8’ 30’’ at 10A, 7Ah battery
typ. 32’ at 4A, 7Ah battery
Allowed batteries >3.9Ah, VRLA batteries
< 27Ah
Temperature range -25°C…+60°C operational
Derating 0.25A/°C +60 to +70°C
Dimensions 49x124x117mm
WxHxD
Power failures or voltage fluctuations can cause
damage and downtime, which usually costs a lot of
time and money. The UB10.241 together with a
battery module offers a reliable and economical
protection for 24V applications.
The output is isolated from the input, which allows
an easy separation of buffered and non-buffered
branches. The energy of the battery will not be
wasted by uncritical consumers.
In times when the power supply provides sufficient
voltage, the DC-UPS charges the 12V battery. In
case the input power fails, the battery voltage will
be boosted to a 24V level and the energy will be
released in a regulated process to the load.
The included battery management incorporates a
battery charger, a deep-discharge protection and
an overload protection to achieve a long service life
of the battery.
The availiability of the DC-UPS is reported by lamps
and relay contacts. The DC-UPS automatically
checks the installation, the battery fuse and the
quality and presence of the battery. Diagnosis is
very easy, thanks to clear understandable indicators
and relay contacts for remote signaling.
Extensive protection features protect the unit
against wrong battery polarity, wrong battery
voltage, wrong input oltage or output overloads.
Weight 530g
3. ORDER NUMBERS 4. MARKINGS
DC-UPS UB10.241 24V, 10A
Accessory UZK12.07 12V, 7Ah Battery module
ZM1.WALL Wall mounting bracket
pending
pending
EMC, LVD