Puls MLY10.241 User manual

Headquarters: PULS GmbH, Elektrastr. 6, 81925 Munich, Germany, www.pulspower.com
Germany +49 89 9278 0
China +86 512 62881820 France +33 478 668 941
North America +1 630 587 9780 Austria +43 2764 3213
Singapore +65 6684 2310 Switzerland +41 56 450 18 10
United Kingdom +44 1525 841001
The information in this document is believed to be accurate and reliable and may change without notice.
EN MLY10.241 Installation Manual Redundancy Module 24V, 10A
DE MLY10.241 Installationsanleitung Redundanzmodul 24V, 10A
FR MLY10.241 Manuel d'installation Module redondant 24V, 10A
ES MLY10.241 Manual de instalación Módulo de redundancia 24V, 10A
Doc. ID: PU-350.015.01-xxZ (2018-03-13-MR1)
Read this first! English Vor Inbetriebnahme lesen! Deutsch
Before operating this device, please read this manual thoroughly and retain this
manual for future reference! This device may only be installed and put into operation
by qualified personnel. If damage or malfunction should occur during operation,
immediately turn power off and send device to the factory for inspection. The device
does not contain serviceable parts. The information presented in this document is
believed to be accurate and reliable and may change without notice. For any
clarifications, the English translation will be used.
Bitte lesen Sie diese Warnungen und Hinweise sorgfältig durch, bevor Sie das
Gerät in Betrieb nehmen. Bewahren Sie die Anleitung zum Nachlesen auf. Das
Gerät darf nur durch fachkundiges und qualifiziertes Personal installiert werden. Bei
Funktionsstörungen oder Beschädigungen schalten Sie sofort die
Versorgungsspannung ab und senden das Gerät zur Überprüfung ins Werk. Das
Gerät beinhaltet keine Servicebauteile. Die angegebenen Daten dienen allein der
Produktbeschreibung und sind nicht als zugesicherte Eigenschaften im
Rechtssinne aufzufassen. Im Zweifelsfall gilt der englische Text.
WARNING Risk of electrical shock, fire, personal injury, or death: WARNUNG Missachtung nachfolgender Punkte kann einen
elektrischen Schlag, Brände, schwere Unfälle oder
Tod zur Folge haben:
Turn power off before working on the device and protect against inadvertent re-
powering.
Do not open, modify or repair the device.
Use caution to prevent any foreign objects from entering the housing.
Do not use in wet locations or in areas where moisture or condensation can be
expected.
Do not touch during power-on and immediately after power-off. Hot surfaces may
cause burns.
Schalten Sie die Eingangsspannung vor Installations-, Wartungs- oder
Änderungsarbeiten ab und sichern Sie diese gegen unbeabsichtigtes
Wiedereinschalten.
Führen Sie keine Änderungen oder Reparaturen durch. Gerät nicht öffnen!
Verhindern Sie das Eindringen von Fremdkörpern.
Betreiben Sie das Gerät nicht in feuchter Umgebung oder in einer Umgebung, bei
der mit Betauung oder Kondensation zu rechnen ist.
Gehäuse nicht während des Betriebes oder kurz nach dem Abschalten berühren.
Heiße Oberflächen können Verletzungen verursachen.
A lire avant mise sous tension! Français Lea primero! Español
Veuillez lire ces instructions de montage et d'entretien avant de mettre l'alimentation
sous tension. Conservez ce manuel qui vous sera toujours utile. Cette alimentation
ne doit être installée que par du personnel qualifié et compétent. En cas de
dommage ou dysfonctionnement, coupez immédiatement la tension d’alimentation
et retournez l’appareil à l’usine pour vérification. ! L’alimentation ne contient pas de
pièces échangeables Les données indiquées dans ce document servent
uniquement à donner une description du produit et n'ont aucune valeur juridique. En
cas de divergences, le texte anglais fait foi.
Conserve este manual como referencia para futuras consultas. La fuente de
alimentación solo puede ser instalada y puesta en funcionamiento por personal
cualificado. Por favor lea detenidamente este manual antes de conectar la fuente
de alimentación. Si se produce un fallo o mal funcionamiento durante la operación,
desconecte inmediatamente la tensión de alimentación. En ambos casos, el equipo
debe ser inspeccionado en fábrica. La información presentada en este documento
es exacta y fiable en cuanto a la descripción del producto y puede cambiar sin
aviso. En casa de duda, prevalece el texto inglés.
AVERTISSEMENT Prendre en compte les points suivants, afin
d'éviter toute détérioration électrique,
incendie, dommage aux personnes ou mort:
ADVERTENCIA Riesgo de descarga eléctrica, incendio,
accidente grave o muerte:
Mettre l’alimentation hors tension avant toute intervention sur celle-ci et s'assurer
qu'il n'y a pas risque de redémarrage.
Ne pas ouvrir, modifier ou réparer l'alimentation.
Veiller à ce qu'aucun objet ne rentre en contact avec l'intérieur de l'alimentation
(trombones, pièces métalliques).
Ne pas faire fonctionner l'appareil dans un environnement humide ou dans un
environnement où il peut y avoir de la condensation.
Ne pas toucher le carter pendant le fonctionnement ou directement après la mise
hors tension. Surface chaude risquant d’entraîner des blessures.
Desconectar la tensión de red antes de trabajar en la fuente de alimentación. Evite
una posible reconexión involuntaria.
No realizar ninguna modificación o reparación de la unidad. No abrir la unidad.
Evitar la introducción en la carcasa de objetos extraños.
No usar el equipo en ambientes húmedos. No operar el equipo en ambientes
donde se espere la formación de rocío o condensación.
No tocar durante el funcionamiento ni inmediatamente después del apagado. El
calor de la superficie puede causar quemaduras graves.
EN MLY10.241 Installation Manual
Product Description
The MLY10.241 is a redundancy module for building redundant power supply systems. It is
equipped with two input channels and one output. The two inputs are decoupled by diodes.
Intended Use
This device is designed for installation in an enclosure and is intended for commercial use, such as
in industrial control, process control, monitoring and measurement equipment or the like. Do not use
this device in equipment where malfunction may cause severe personal injury or threaten human
life.
The redundancy module can be used with any type of power supply as long as the maximum output
current ratings are not exceeded. It is suitable for power supplies with continuous overload current
as well as any kind of intermittent (Hiccup) overload behavior.
If this device is used in a manner outside of its specification, the protection provided by the device
may be impaired.
Installation Instructions
Install the device in an enclosure providing protection against electrical, mechanical and fire
hazards.
Do not ground or earth the positive output pole which could prevent redundancy in case of a ground
failure. Ground the negative output pole, when needed.
Use only power supplies with a negligible output ripple voltage in the low frequency range between
50Hz and 10kHz when used in marine applications according to the GL regulations.
Install the device onto a DIN-rail according to EN 60715 with the input terminals on the top of the
device. Other mounting orientations require a reduction in output current.
Make sure that the wiring is correct by following all local and national codes. Use appropriate copper
cables that are designed for a minimum operating temperature of 60°C for ambient temperatures up
to +45°C, 75°C for ambient temperatures up to +60°C and 90°C for ambient temperatures up to
+70°C. Ensure that all strands of a stranded wire enter the terminal connection. Unused screw
terminals should be securely tightened.
The device is designed for pollution degree 2 areas in controlled environments. No condensation or
frost is allowed.
The enclosure of the device provides a degree of protection of IP20. The enclosure does not provide
protection against spilled liquids.
The input must be powered from a PELV or SELV source or an “Isolated Secondary Circuit” in order
to maintain a SELV or PELV output.
Check correct input polarity. The device will not operate when input voltage is reversed.
The device is designed as “Class of Protection III” equipment according to IEC 61140.
The device is designed for convection cooling and does not require an external fan. Do not obstruct
airflow and do not cover ventilation grid!
The device is designed for altitudes up to 5000m (16400ft). Above 2000m (6560ft) a reduction in
output current is required.
Keep the following minimum installation clearances: 40mm on top, 20mm on the bottom, 5mm left
and right side. Increase the 5mm to 15mm in case the adjacent device is a heat source. When the
device is permanently loaded with less than 50%, the 5mm can be reduced to zero.
The maximum surrounding air temperature is +70°C (+158°F). The operational temperature is the
same as the ambient or surrounding air temperature and is defined 2cm below the device.
The device is designed to operate in areas between 5% and 95% relative humidity.
Installation Instructions for Hazardous Location Areas
The device is suitable for use in Class I Division 2 Groups A, B, C, D locations and for use in Group
II Category 3 (Zone 2) environments.
Hazardous Location classification: ATEX: EPS 11 ATEX 1 312 X, II 3G EX ec IIC T4 Gc
WARNING EXPLOSION HAZARDS!
Substitution of components may impair suitability for this environment.
Do not disconnect the device unless power has been switched off or the area is known to be non-
hazardous.
A suitable enclosure must be provided for the end product which has a minimum protection of IP54
and fulfils the requirements of the EN 60079-0.
Functional Description
The device can supply any kind of loads, including unlimited capacitive and inductive loads.
Do not apply return voltages from the load to the output higher than 200Vdc.
Technical Data
All values are typical figures specified at 24Vdc input voltage, 10A
output current, 25°C ambient temperature and after a 5 minutes
run-in time unless otherwise noted.
Input voltage DC 12-48V ±25%
Input voltage range 9–60Vdc
Input current 2x 5A Below +60°C ambient
2x 3.75A At +70°C ambient
2x 8A Up to 5 seconds
Derate linearly between +60°C and +70°C
Output current 10A Below +60°C ambient
7.5A At +70°C ambient
16A Up to 5 seconds
Maximum overload current 16A R.M.S. In any overload or
short circuit condition
Input to output voltage loss 800mV At 2x 2.5A input
900mV At 2x 5A input
Power losses 0W At no load
4.0W At 2x 2.5A input
9.0W At 2x 5A input
Temperature range -40 to +70°C
Max. wire size (litz wire) 4mm²
Wire size AWG AWG 20-10
Max. wire diameter 2.8mm
Wire stripping length 7mm / 0.28inch
Tightening torque 1Nm / 9lb.inch
Size (wxhxd) 45x75x91mm Without DIN-rail
Weight 140g / 0.31lb
Functional Diagram
+
-
+
-
+
-
Input 1
Input 2
Output
-
Wiring Scheme - 1+1 Redundancy
L1
L2
PE
L3
Load
Failure
Monitor
I I I I I I
Power
Supply
Output
DC-
OK
L1 L2 L3
Input
+
-
+
-
o o
Redundancy
Module
Output
Input
1 Input
2
+
-
+
-
+
--
Power
Supply
Output
DC-
OK
L1 L2 L3
Input
+
-
+
-
o o
Wiring Scheme - N+1 Redundancy
L1
L2
PE
L3
Load
Failure
Monitor
I I I I I I I I II I I
Power
Supply
Output
DC-
OK
L1 L2 L3
Input
+
-
+
-
o o
Power
Supply
Output
DC-
OK
L1 L2 L3
Input
+
-
+
-
o o
Power
Supply
Output
DC-
OK
L1 L2 L3
Input
+
-
+
-
o o
Power
Supply
Output
DC-
OK
L1 L2 L3
Input
+
-
+
-
o o
Redundancy
Module
Output
Input
1 Input
2
+
-
+
-
+
--
Redundancy
Module
Output
Input
1 Input
2
+
-
+
-
+
--

Other Puls Control Unit manuals

Puls PISA-B-812-B1 User manual

Puls

Puls PISA-B-812-B1 User manual

Puls Dimension Y Series User manual

Puls

Puls Dimension Y Series User manual

Puls MiniLine MLY-Series User manual

Puls

Puls MiniLine MLY-Series User manual

Puls DIMENSION U Series User manual

Puls

Puls DIMENSION U Series User manual

Puls Dimension PISA11 Series User manual

Puls

Puls Dimension PISA11 Series User manual

Puls PISA-B-812-B4 User manual

Puls

Puls PISA-B-812-B4 User manual

Puls YR20.246 User manual

Puls

Puls YR20.246 User manual

Puls DIMENSION UF Series User manual

Puls

Puls DIMENSION UF Series User manual

Puls YR2.DIODE User manual

Puls

Puls YR2.DIODE User manual

Puls UZK12.072 User manual

Puls

Puls UZK12.072 User manual

Puls YR20.246 User manual

Puls

Puls YR20.246 User manual

Puls YR2.DIODE User manual

Puls

Puls YR2.DIODE User manual

Puls DIMENSION UB40.241 User manual

Puls

Puls DIMENSION UB40.241 User manual

Puls DIMENSION YR40.245 User manual

Puls

Puls DIMENSION YR40.245 User manual

Puls YR40.482 User manual

Puls

Puls YR40.482 User manual

Puls UBC10.241 User manual

Puls

Puls UBC10.241 User manual

Puls DIMENSION YR40.246 User manual

Puls

Puls DIMENSION YR40.246 User manual

Puls Dimension Y Series User manual

Puls

Puls Dimension Y Series User manual

Puls YR80.242 User manual

Puls

Puls YR80.242 User manual

Puls UZK12.071 User manual

Puls

Puls UZK12.071 User manual

Puls UZK12.071 User manual

Puls

Puls UZK12.071 User manual

Puls YR20.242 User manual

Puls

Puls YR20.242 User manual

Puls YR40.242 User manual

Puls

Puls YR40.242 User manual

Puls DIMENSION U Series User manual

Puls

Puls DIMENSION U Series User manual

Popular Control Unit manuals by other brands

Vaillant VR 70 installation instructions

Vaillant

Vaillant VR 70 installation instructions

Mitsubishi A1SD75M3 user manual

Mitsubishi

Mitsubishi A1SD75M3 user manual

SCT RC5-P60 Series installation guide

SCT

SCT RC5-P60 Series installation guide

ApenGroup aermaxline PCH Installation and user guide

ApenGroup

ApenGroup aermaxline PCH Installation and user guide

Bosch MS 3 Sport GT3 Cup manual

Bosch

Bosch MS 3 Sport GT3 Cup manual

Texas Instruments DAC8580 user guide

Texas Instruments

Texas Instruments DAC8580 user guide

GCE druva LINE 200 operating instructions

GCE

GCE druva LINE 200 operating instructions

Staubli MA010 Assembly instructions

Staubli

Staubli MA010 Assembly instructions

SMSCOM SwitchBox All-In-One SW-B2L user manual

SMSCOM

SMSCOM SwitchBox All-In-One SW-B2L user manual

Danfoss EKF Series installation guide

Danfoss

Danfoss EKF Series installation guide

RS 571-439 Instruction leaflet

RS

RS 571-439 Instruction leaflet

HP 75000 B Series user manual

HP

HP 75000 B Series user manual

Cameron WKM 370D6 Installation, operation and maintenance manual

Cameron

Cameron WKM 370D6 Installation, operation and maintenance manual

Texas Instruments INA220 user guide

Texas Instruments

Texas Instruments INA220 user guide

Honeywell MCV2000AA Product specification sheet

Honeywell

Honeywell MCV2000AA Product specification sheet

iWorX ASM2 Application guide

iWorX

iWorX ASM2 Application guide

CIAT Magister 2 Series Installation, Operation, Commissioning, Maintenance

CIAT

CIAT Magister 2 Series Installation, Operation, Commissioning, Maintenance

Align APS-M Firmware update

Align

Align APS-M Firmware update

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.