UZK12.071, UZO12.07
-Series BATTERY MODULE 12V, 7AH
Apr. 2021 / Rev. 2.3 DS-UZK12.071
All parameters are typical values specified at 25°C ambient temperature unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
3/12
NTENDED
SE
This device is designed for installation in an enclosure and is intended for commercial use, such as in industrial control,
process control, monitoring and measurement equipment or the like.
Do not use this device in equipment where malfunction may cause severe personal injury or threaten human life.
NSTRUCTIONS FOR
ISPOSAL OF THE
ATTERIES
Always dispose batteries through a recycling organization. Optionally, batteries can be returned to the supplier or the
battery manufacturer. Batteries must be completely discharged before recycling.
CAUTION: The unit contains wet cell batteries. Ventilation of the installation room in accordance with the rules of
Canadian Electrical Code, part 1 is required if used in Canada.
NSTRUCTIONS FOR
ATTERY
TORAGE
Do not store batteries or battery modules at temperatures higher than 25°C or performance and lifetime may change.
Before initial use, check the last charging which is marked on the battery. If it is older than 9 months, replace the
battery.
Do not store batteries longer than 9 months without charging or performance and lifetime may change. Every 9
months or whenever the open circuit voltage (OCV) falls below 12.6V, the battery module should be charged. Apply a
charging voltage of 13.8V (at 25°C) for 72 hours. Batteries with an OCV below 12V should be disposed.
NSTALLATION
NSTRUCTIONS
This device may only be installed and put into operation by qualified personnel.
This device does not contain serviceable parts, except the fuse or replacement battery. If malfunction should occur
during installation or operation, first check the fuse and battery for proper functionality. If the unit is damaged or if
the malfunction continues, immediately turn power off and send device to the factory for inspection.
Do not install the battery fuse until the installation work is complete.
Replacement fuses must be of the same type or an UL listed fuse with the same nominal value and characteristics.
Do not store batteries or battery modules at temperatures higher than 25°C or performance and lifetime may change.
Before initial use, check the last charging which is marked on the battery. If it is older than 9 months, replace the
battery.
Do not short-circuit the battery poles or power wires and always check correct battery polarity.
Mount the device onto a heavy-duty DIN-rail or screw it securely on a flat surface. Before mounting the unit on a flat
surface, detach the DIN-rail slider (remove the plastic lock mechanism by using a flat-blade screwdriver and move the
lock downwards while pushing the plastic slide upwards at the same time) and the two aluminum DIN-rail brackets
(Torx T10 screwdriver).
Do not install the battery module upside down.
Install the device in a cool area inside an enclosure providing protection against electrical, mechanical and fire hazards.
Ensure sufficient ventilation by following the requirements of the EN 50272-2.
The device is designed for pollution degree 2 areas in controlled environments. No condensation or frost allowed.
The enclosure of the device provides a degree of protection of IP00.