Refco PRV-2000 User manual

PRV-2000 & PRV-2200
Instruction Manual
Nitrogen test control unit
Bedienungsanleitung
Stickstoffprüfgerät
Mode d'emploi
Détendeur azote
Istruzioni per l'uso
Kit test azoto
Manual de instrucciones
Unidad de prueba para nitrógeno
EN
DE
R
IT
ES


Pressure regulators / Druckminderer / Détendeur azote /
Riduttore di pressione / Regulador de presión
Index:
1 Introduction
2 echnical data
3 System drawing
4 Use
5 Safety notes
6 Designation in accordance with
DIN EN ISO 2503
7 Support device
7.1 Pressure regulation
7.2 Setting the pressure
7.3 Disconnecting the pressure regulator
8. Pressure and leak-tightness tests
9. Refrigerants and their test ranges
10. Washing and blow out
11. Notes on operation and maintenance
12. Repair
Inhaltsverzeichnis: Index:
1 Einleitung 1 Introduction
2 echnische Daten 2 Caractéristiques techniques
3 Systemzeichnung 3 Dessin de système
4 Verwendung 4 Utilisation
5 Sicherheitshinweise 5 Consignes de sécurité
6 Kennzeichnung gemäss DIN EN ISO 2503 6 Marquage suivant DIN EN ISO 2503
7 Inbetriebnahme 7 Mise en service
7.1 Druckregulierung 7.1 Régulation de la pression
7.2 Einstellen des Druckes 7.2 Réglage de la pression
7.3 Entfernen des Druckminderes 7.3 Débranchement du détendeur
8. Druck- und Dichtheitsprüfungen 8. Contrôles de pression et d'étanchéité
9. Kältemittel und deren Prüfbereich 9. Pressions
d'essai
selon
fluides
frigorigènes
10. Spülen und Ausblasen 10. Nettoyage et soufflage
11. Hinweise für Betrieb und Wartung 11. Consignes pour le fonctionnement et
la maintenance
12. Reparatur 12. Réparation
Indice: Índice:
1 Introduzione 1 Introducción
2 Specifiche tecniche 2 Datos técnicos
3 Disegno del sistema 3 Descripción de las piezas
4 Utilizzo 4 Uso
5 Avvertenze per la sicurezza 5 Advertencias de seguridad
6 Etichettatura secondo la norma
DIN EN ISO 2503
6 Identificación según la norma DIN EN
ISO 2503
7 Messa in funzione 7 Puesta en funcionamiento
7.1 Regolazione della pressione 7.1 Regular la presión
7.2 Impostazione della pressione 7.2 Ajustar la presión
7.3 Rimozione del riduttore di pressione 7.3 Desmontar el regulador de presión
8. est di pressione e di tenuta 8. Controles de presión y estanqueidad
9. Refrigeranti e relativi intervalli di test 9. Controles de presión y estanqueidad
10. Pulizia e spurgo 10. Enjuague y vaciado
11. Avvertenze per il funzionamento e
la manutenzione
11. Observaciones sobre el funcionamiento y
el mantenimiento del equipo
12. Riparazione 12. Reparaciones

1. Introduction
hese instructions for use are intended to facilitate the correct and safe use of this pressure
regulator. Reading and observing these instructions for use will help to avoid hazards,
reduce downtimes and increase the reliability and service life of the equipment.
he instructions for use must be kept to hand at all times.
= safety notes, see also point 5
In cases of doubt, contact the manufacturer and/or distributor
Scope
Pressure and leak-tightness tests on moderately sized and large refrigerant circuits
Washing and blowing out refrigerant circuits
Simple and safe pressure regulation
Versions available
PRV-2000 for nitrogen cylinder connection conforming to UNI 4409
PRV-2200 for nitrogen cylinder connection conforming to DIN 477 no.10
2. Technical data
1. PRV 2000 connection Nut, male, for standard nitrogen cylinders
UNI 4409 (W 21.7 x 1/14" RH)
1. PRV 2200 connection Crown nut, female, for nitrogen cylinders,
DIN 477 no.10 (W 24.32 x 1/14" RH)
2. Pressure regulator Max. 220 bar primary 5-50 bar secondary
3. Pressure relief valve Set to 55 bar and secured
4. Marking gauge Ø 80 mm, with marking indicator
5. Charging hose 900 mm with ¼" connection
SAE J2196 / J2888
6. Adapter for PRV-1000 FM UNI 4409 thread on M10x1 for small
Nitrogen cylinders
7. ransition piece 1/4SA ransition piece with valve depressor,
¼" SAE x ½" 20UNF

3. System drawing
1.) PRV 2000/2200 connection 8.) Handwheel
2.) Pressure regulator 9.) Primary gauge
3.) Pressure relief valve 10.) Secondary gauge
4.) Marking gauge 11.) Connection for filling hose
5.) Charging hose 12.) ap to marking gauge
6.) Shutoff valve 13.) Connection to refrigeration system
7.) Adapter to M10x1 thread 14.) Refrigeration system
4. Use
Proper use:
REFCO products have been developed and manufactured specifically for use by trained
refrigeration engineers and technicians. Due to the high pressure levels as well as the
chemical and physical gases used in refrigeration systems, REFCO accepts no responsibility
or liability in the event of accidents, injuries or death.
he pressure regulator has been developed especially for pressure regulation of nitrogen
(N2). he maximum primary pressure is 220 bar. he secondary pressure is 5 - 50 bar. he
safety valve (pressure relief valve) is set to 55 bar. Interference with the safety valve is
forbidden.
he pressure regulator may only be used for nitrogen pressure cylinders. his set should
only be used for testing refrigeration systems using nitrogen.
Improper use:
• Do not use the pressure regulator for gases in the liquid phase.
• Do not operate the pressure regulator in ambient temperatures below
-30°C and over +60°C.
• Do not use the pressure regulator for aggressive gases, e.g. ethylamine,
dimethylamine, ammonia, etc.
• he device may not be used for purposes other than those relating to
air conditioning and refrigeration.

5. Safety notes
All instructions marked with this symbol are special safety
instructions.
he pressure regulators conform to the latest technological standards as well as the
requirements of existing regulations.
No modifications or conversions are permitted without
permission from the manufacturer.
It is not permitted to insert adapters between the gas cylinder
valve and cylinder pressure regulator.
Incorrect and improper usage could result in danger to the
user and other persons, as well as damage to the pressure
regulator and the system.
Always wear protective goggles and gloves when working with the device.
6. Designation in accordance with DIN EN ISO 2503
A (rear)
•Gas type
•P1
•P2
•Date of manufacture
B (front nameplate)
•Name/manufacturer's mark
7. Commissioning
Read the information in these instructions for use before working with the device and
observe the information during work!

7.1 Pressure regulation
Connecting the pressure regulator
Before screwing on the pressure regulator (8), open the cylinder valve once briefly
to blow out any dirt present. During this process, do not stand in front of the valve
and do not hold your hand in front of the valve.
When installing the pressure regulator (8), all components coming into contact with
the gas must be completely free of oil and grease.
Before connecting the pressure regulator to the gas cylinder, check that the cylinder
definitely contains nitrogen (N2).
Check the nitrogen cylinder connection. Do not under any circumstances connect
the pressure regulator if it is damaged or leaking.
Depressurise the pressure regulator by turning the setting hand wheel (8) to the zero
position (anti-clockwise).
Connect the pressure regulator to the nitrogen cylinder by tightening the connection
nut (1) securely. Do not tighten the threaded connection too much as this could
damage the seal. he setting handwheel (8) must be pointing vertically downwards.
7.2 Setting the pressure
First close the shutoff valve (6) and depressurise the pressure regulator by unscrewing
the adjusting screw (8). Slowly open the cylinder valve. he high pressure gauge (9) will
now be indicating the cylinder pressure. Open the shutoff valve (6) and open the
corresponding shutoff valve slightly on the consumer equipment. Now set the required
backpressure (working pressure) by screwing in the adjusting screw (8) and take the
reading from the low pressure gauge (10). Correct the pressure setting in the event of a
pressure drop.
7.3 Disconnecting the pressure regulator
It is not permitted to remove the pressure regulator when under
pressure!
Close the nitrogen cylinder valve.
Release the pressure from the low pressure range. Make absolutely sure
that the pressure regulator and the nitrogen cylinder connection (1) are not
under pressure. During the check, the primary pressure (9) and secondary
pressure gauge (10) must be on zero.
First hold the pressure regulator with your hand and carefully (there may be
residual pressure present) loosen the connection between the pressure regulator
and the gas cylinder valve with a half or a whole turn. o make sure that all the
gas has been released, waggle the pressure regulator briefly. Do not remove the
pressure regulator before doing this.
Ensure that the setting handwheel (8) has been fully depressurised and store
the pressure regulator in the case together with the other components. his
ensures that the threaded connections and gauge are optimally protected
against damage.

8. Pressure and leak-tightness tests
• Connect the pressure regulator (2) as described under "7.1 Pressure regulation".
• hen connect the charging hose to the pressure regulator connection.
• Connect the other end of the charging hose (5) (45° bend) to the marking gauge
(connection to tap 12).
• In this process, ensure that the tap (12) is closed. he yellow handle must be pointing
towards you.
• hen tighten the connection (13) on the respective refrigeration circuit.
• Now open the gas cylinder valve slowly. he primary gauge (9) will be indicating the
cylinder pressure.
• hen open the yellow tap (12) on the marking gauge. he tap will now be pointing in
the direction of the hose.
• urn the handwheel (8) clockwise to set the required pressure. he pressure being
tested depends on the required refrigerant in the refrigeration circuit. See table:
9. Refrigerants and their test ranges
Refrigerant Pressure
R134A 18-22 bar
R404A 28-32 bar
R407C 28-32 bar
R507 28-32 bar
R22 28-32 bar
R410A 38-42 bar
• If the correct pressure range has been set, mark the pressure indicator on the
gauge (4). o do this, move the red marker precisely over the pressure indicator
on the gauge.
• Wait for approx. 20 seconds. If the marking indicator and the gauge indicator are
still covering one another, you can close the yellow tap on the marking gauge and
remove the charging hose.
• he marking gauge (4) is now connected to the refrigerant circuit at the required
pressure.
• he test duration depends on the size and type of the refrigerant circuit. If the
marking indicator and the gauge indicator are still covering one another after the
test time has elapsed, the refrigerant circuit is without leaks. If the pressure
indicator has dropped below the marking indicator, the refrigerant circuit is leaking.
10. Washing and blowing out
• Position a sufficiently large bucket underneath the outlet of the refrigerant system,
and open it.
• hen connect the pressure regulator (2) as described under
"7.1 Pressure regulation".

• hen connect the charging hose (5) to the pressure regulator connection (11).
• Connect the other end of the charging hose (45° bend) to the marking gauge (4).
• In this process, ensure that the tap (12) is closed. he yellow handle must be
pointing towards you.
• hen tighten the connection (13) on the respective refrigeration circuit (14).
• Now open the gas cylinder valve slowly. he primary gauge (9) will be indicating
the cylinder pressure.
• hen open the yellow tap (12) on the marking gauge. he tap must be pointing
in the direction of the charging hose.
• Turn the handwheel (8) to set the required pressure (10). For washing, set a pressure
between 4 and 7 bar.
• he system will then be blown out at a constant pressure.
11. Notes on operation and maintenance
• Always protect the pressure regulator against damage (visual inspection at regular
intervals).
• It is not permitted to change the factory setting of the blow-off valve.
• Make sure that the connection gaskets, sealing surfaces and gauges are in perfect
condition.
• In the event of any faults, e.g. a rise in the backpressure on removal = 0, with leaks
into the atmosphere, faulty gauges or if the safety valve is triggered, decommission
the pressure regulator and close the cylinder valve immediately.
he test device is very sensitive. In the event of improper use or impact, it must be
re-tested by a specialist centre.
12. Repair
Repairs to the pressure regulators may only be carried out by experienced, qualified
specialists in authorised workshops or by REFCO Manufacturing Ltd. Only genuine
replacement parts are permitted to be used.
No liability shall be accepted for any consequences of unauthorised repairs or
modifications carried out by the user or by third parties not approved by the
manufacturer.

1. Einleitung
Diese Gebrauchsanleitung soll dazu dienen, die bestimmungsgemäße und sichere
Verwendung dieses Druckminderers zu ermöglichen. Das Lesen und die Beachtung der
Gebrauchsanleitung helfen, Gefahren zu vermeiden, Ausfallzeiten zu vermindern und die
Zuverlässigkeit und Lebensdauer der Geräte zu erhöhen.
Diese Gebrauchsanleitung muss stets griffbereit zur Verfügung stehen.
= Sicherheitshinweise, siehe auch Punkt 5
In Zweifelsfällen ist der Hersteller und/oder Vertreiber zu befragen
Anwendungsbereich
Druck- und Dichtheitsprüfungen bei mittleren und grösseren Kältekreisläufen
Spülen und ausblasen von Kältekreisläufen
Einfache und sichere Druckregulierung
Erhältliche Ausführungen
PRV-2000 für Stickstoffflaschenanschluss nach UNI 4409
PRV-2200 für Stickstoffflaschenanschluss nach DIN 477 Nr.10
2. Technical data
1. Anschluss PRV 2000 Mutter, männlich, für Stickstoffflaschen Norm
UNI 4409 (W 21.7 x 1/14“ RH)
1. Anschluss PRV 2200 Überwurfmutter, weiblich, für Stickstoff-
flaschen, DIN 477 Nr.10 (W 24.32 x 1/14“ RH)
2. Druckminderer max. 220 bar primär 5-50 bar sekundär
3. Überdruckventil: Eingestellt auf 55 bar und gesichert
4. Markiermanometer Ø 80 mm, mit Markierzeiger
5. Füllschlauch 900 mm mit ¼“ Anschluss SAE J2196 / J2888
6. Adapter für PRV-1000 Gewinde FM UNI 4409 zu M10x1 für kleine
Stickstoffflaschen
7. Übergangsstück 1/4SA Übergangsstück mit Ventildrücker,
¼“ SAE x ½“-20UNF
This manual suits for next models
3
Table of contents
Languages:
Other Refco Measuring Instrument manuals

Refco
Refco SM4 User manual

Refco
Refco 4687787 Installation guide

Refco
Refco REF-VAC Installation guide

Refco
Refco Apex User manual

Refco
Refco REF-VAC Installation guide

Refco
Refco REF-CLASS-GAUGE Installation guide

Refco
Refco REFCLAMP User manual

Refco
Refco REFSCALE-CB User manual

Refco
Refco MULTITHERM 4688582 User manual

Refco
Refco TAP Installation guide