
9 │
REGULUS - RBC Hot Water Storage Tanks - www.regulus.eu
6 - Installation and Commissioning
Installation must meet valid rules and may be done only by qualified staff. The tank shall be placed on the floor,
as close to the heat source as possible.
Warning: Defects caused by improper installation, use or handling are not covered by warranty.
6.1 - Connection to heat sources
Connect the heat source to the inlets and outlets of X1 and X2 heat exchangers using G 5/4“ fittings.
6.2 - Connection to a solar thermal system
This tank can also be used with a solar thermal system. In such a case, the inlet from a solar thermal system
connects to the upper G 5/4“sleeve of the heat exchanger marked X1, and the lower outlet X2 connects to the
return piping to the solar thermal system. Insulate all the piping between the tank and the solar thermal system
using insulation suitable for solar applications.
6.3 - Heating element installation
The G 6/4“ side connection marked E1 is designed to accommodate an electric heating element. Tanks of all
sizes can be retrofitted with another heating element installed in the L1 lower flange. The precondition for this is
replacing magnesium anode rods with an electronic one, and replacing the factory-supplied flange with a new
flange containing a G 6/4“ for the installatioon of an el. heatimg rod and a G 1/2“ connection for an electronic
anode rod. Codes of Electronic Anode Kits w. flanges needed for installation of another heating element can be
found in the table in Chap. 6.5. Heating elements of output up to 12 kW can be used (depending on the tank
diameter and element length), connected either directly to the mains (thermostat-equipped elements), or via a
heating system controller. The installation may be done by qualified staff only.
Warning: Electric heating elements shall be protected by a safety thermostat.
6.4 - Connection to water mains
DHW piping shall be done according to valid rules. Pipe fittings are used to connect the tank to a cold water inlet
and hot water outlet. Install a safety group that meets the requirements of ČSN 06 0830 - e.g. code 17387 or
18678 depending on the tank volume. Installation of a pressure reducing valve to the tank inlet is recommended.
If the pressure from water mains exceeds 6 bar, a pressure reducing valve is necessary. In order to prevent
water loss, an expansion vessel should be installed at the cold water inlet as well (8 l volume for RBC 200, 12 l
volume for RBC 300 and 400, 18 l volume for RBC 500, 24 l volume for RBC 750, 35 l volume for RBC 1000, 60
l volume for RBC 1500, 80 l volume for RBC 2000, 100 l volume for RBC 2500 and 2×60 l volume for RBC 3000).
Should the water be too hard, install a water softener before the tank. In case the water contains mechanical
impurities, install a filter.
A pressure temperature relief valve (PTR) shall be installed at the hot-water outlet from the tank - e.g. code
17240 with a connection kit 17526. It is also recommended to install a corresponding anti-scald valve that
prevents too hot water from entering the taps.
Install a drain valve to the lowest point of the tank.
Complete DHW piping shall be properly insulated.
6.5 - Electronic anode rod installation
An electronic anode rod can be installed instead of the magnesium one. Its principle advantage is that it is
not necessary to dismantle it from the tank to determine its function. In such a case, just visual check of the
electronic anode rod is sufficient.
A space equal to the el. anode length is needed between the tank top and ceiling to install/replace the electronic
anode rod, see the table below. In order to protect the tank properly and meet its warranty conditions, select the
proper electronic anode rod from the table below.