Guarantee
For the Reliable Automatic Sprinkler Co., Inc. guarantee, terms,
and conditions, visit www.reliablesprinkler.com.
Ordering Information
Specify the following when ordering.
Sprinkler
• Model: F1-56SS Pendent, F1-56SS Upright,
F1-80SS Pendent, F1-80SS Upright
• Temperature Rating: 135°F (57°C), 155°F (68°C),
175°F (79°C), 200°F (93°C), 286°F (141°C), 360°F
(182°C), 500°F (260°C)
• Threads: NPT or ISO7-1
Escutcheon (Pendent Only)
• Model: F1 recessed stainless steel, FP recessed
stainless steel, B stainless steel
Sprinkler Wrench
• Model W2 (pendent, upright)
• Model GFR2 (recessed pendent)
Maintenance
Model F1-SS series sprinklers should be inspected and the
sprinkler system maintained in accordance with NFPA 25.
Do not clean sprinklers with soap and water, ammonia or any
other cleaning fluids. Remove dust by gentle vacuuming. Re-
place any sprinkler which has been painted (other than factory
applied) or damaged in any way. A stock of spare sprinklers
should be maintained to allow quick replacement of damaged
or operated sprinklers. Prior to installation, sprinklers should
be maintained in the original cartons and packaging until used
to minimize the potential for damage to sprinklers that would
cause improper operation or non-operation.
Bulletin 064
July 2017
Page 6 of 6
www.reliablesprinkler.com
Listings and Approvals
Listed by Underwriters Laboratories, Inc. and UL Certified for
Canada (cULus)
UL Listing Category
Sprinklers, Automatic and Open
UL Guide Number
VNIV
Wrench
P/N 9999970521
Model W2 (upright, pendent) Model GFR2 (recessed pendent)
Installation
Glass bulb sprinklers have orange bulb protectors to minimize
bulb damage during shipping, handling, and installation. Re-
liable sprinkler installation wrenches are designed to install
sprinklers with bulb protectors in place. Remove the bulb pro-
tector at the time when the sprinkler system is placed in service
for fire protection. Removal of the bulb protector before this time
may leave the bulb vulnerable to damage. Remove bulb protec-
tors by undoing the clasp by hand. Do not use tools to remove
bulb protectors.
Model F1-SS series sprinklers must be installed with the Reli-
able sprinkler installation wrench identified in this Bulletin. Any
other wrench may damage the sprinkler. Recommended instal-
lation torque is 8 to 18 lb/ft (11 to 24 N/m) for 1/2” NPT and
ISO7-1R1/2 sprinklers or 14 to 20 lb/ft (19 to 27 N/m) for 3/4”
NPT and ISO7-1R3/4 sprinklers. Do not tighten sprinklers over
the maximum recommended installation torque. Exceeding the
maximum recommended installation torque may cause leakage
or impairment of the sprinkler.
Recessed pendent sprinklers are to be installed as shown in
Fig. 2 or Fig 5., as applicable to the specific model being in-
stalled. Model F1-SS series recessed pendent sprinklers may
only be installed with the Reliable Model F1 stainless steel or
Model FP stainless steel recessed escutcheon. The use of any
other recessed escutcheon will void all approvals and negate
all warranties. The Reliable Model FP escutcheon may not be
used in ceilings having positive pressure with respect to the
space below. Ensure that the openings in the Model FP es-
cutcheon/can assembly are unobstructed following installation.
Application
Model F1-SS series sprinklers are standard spray, standard-re-
sponse sprinklers intended for installation in accordance with
NFPA 13 and the requirements of applicable Authorities Having
Jurisdiction. Model F1-SS series sprinklers are cULus Listed
as Corrosion Resistant sprinklers. Verify compatibility with the
environment where the sprinkler will be located prior to instal-
lation.