Temperature Rating
Classification
Sprinkler
Temperature
Maximum
Ambient
Temperature
Bulb
Color
°F °C °F °C
Ordinary
Ordinary
Intermediate
135
155
175
57
68
79
100
100
150
38
38
66
Orange
Red
Yellow
Maximum Working Pressure
175 psi (12 bar)
SIN RA2845 cULus listed for 250 psi (17 bar)
100% Factory tested hydrostatically to 500 psi (34.5 bar)
Finishes (1)
Standard Finishes
Sprinkler (2) Escutcheon Coverplate
Bronze
Chrome Plated
White & Black Polyester Coated(3)
Brass
Chrome Plated
White Painted
Chrome
White
Special Application Finishes
Sprinkler (2) Escutcheon Coverplate
Electroless Nickel PTFE(3)
Bright Brass
Black Plated
Black Paint
Off White
Chrome Dull
Bright Brass
Black Plated
Black Paint
Off White
Chrome Dull
Bright Brass
Black Plating
Black Paint
Off White
(1) Other colors and finishes are available on special order. Consult factory
for details.
(2) FM Approvals limited to Bronze, Bright Brass, Satin Chrome Plated,
Black Plated and Polyester Coated.
(3) cULus Listed Corrosion Resistant Sprinkler.
Note: Paint or any other coating applied over the factory finish will void
approvals and warranties.
Ordering Information
Specify:
1. Sprinkler Model: F1FR56 QREC
2. Sprinkler Type
3. Temperature Rating
4. Sprinkler Finish
5. Sprinkler Thread Type: [½” NPT] [ISO 7-1R½]
6. Escutcheon Finish (where applicable)
7. Coverplate Finish (where applicable)
8. Coverplate Temperature Rating
Note: When Model F1FR56 QREC Recessed sprinklers are ordered,
the sprinklers, escutcheons and coverplates are packaged
separately.
After installation, inspect all sprinklers to ensure that
there is a gap between the cover plate and ceiling and
that the four cup slots are open and free from any air flow
impediment to the space above.
Concealed cover plate/cup assemblies are listed only
for use with specific sprinklers. The use of any other
concealed cover plate/cup assembly with the Model
F1FR56 QREC Pendent Sprinkler or the use of the Model
CCP concealed cover plate assembly on any sprinkler
with which it is not specifically listed may prevent good
fire protection and will void all guarantees, warranties,
listings and approvals.
Glass bulb sprinklers have orange bulb protectors to
minimize bulb damage during shipping, handling and
installation. REMOVE THIS PROTECTION AT THE TIME
THE SPRINKLER SYSTEM IS PLACED IN SERVICE FOR
FIRE PROTECTION. Removal of the protectors before this
time may leave the bulb vulnerable to damage. RASCO
wrenches are designed to install sprinklers when covers
are in place. REMOVE PROTECTORS BY UNDOING THE
CLASP BY HAND. DO NOT USE TOOLS TO REMOVE
THE PROTECTORS.
Maintenance
The Models F1FR56 QREC and F1FR56 QREC
Recessed Sprinklers should be inspected and
maintained in accordance with NFPA 25. Do not clean
sprinklers with soap and water, ammonia or any other
cleaning fluids. Remove dust by gentle vacuuming.
Replace any sprinkler which has been painted (other
than factory applied) or damaged in any way. A stock
of spare sprinklers should be maintained to allow quick
replacement of damaged or operated sprinklers. Prior
to installation, sprinklers should be maintained in the
original cartons and packaging until used to minimize
the potential for damage to sprinklers that would cause
improper operation or non-operation.
Escutcheon Data:
Escutcheon
Model Adjustment “A”
Dimension
Face of Fitting
to Ceiling
Wall Dimension
F1 Max Recessed
Min Recessed
11/2” (38.1mm) (1)
3/4” (19.1mm) (2)
3/16” - 15/16”
(5m - 24mm)
F2 Max Recessed
Min Recessed
11/2” (38.1mm) (1)
1” (25mm) (2)
3/16” - 11/16”
(5m - 17mm)
FP Push-on/
Thread-off
Max Recessed
Min Recessed
7/16” (11mm)
15/16” (24mm)
11/2” (38.1mm)
1” (25mm)
(1) EC Pendent.
(2) EC HSW.
EG. Printed in U.S.A. 03/20 P/N 9999970388
Reliable Automatic Sprinkler Co., Inc.
(800) 431-1588 Sales Offices
(800) 848-6051 Sales Fax
(914) 829-2042 Corporate Offices
www.reliablesprinkler.com Internet Address
Manufactured by
Recycled
Paper
Revision lines indicate updated or new data.
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 100 years.