Application and Installation
The Model F1FR/ CCP Concealed Sprinkler uses the ½²
orifice, ½²NPT (R½), 135°F(57°C), 155°F(68°C), 175°F
(79°C) or 200°F(93°C) Model F1FR Pendent Sprinkler with
a threaded Model CCP cup which is factory attached to
the sprinkler. The assembly is completed by the
installation of the attractive, low profile, 135°F(57°C) or
165°F(74°C) rated Model CCP push on cover plate
assembly. The cover plate and sprinkler cup assemblies
are joined using a cover plate skirt with flexible tabs for
threaded engagement. A choice of two cover plate
assemblies provide either ½²(13mm) or 5/16" (8mm) of
cover adjustment.
Do not install these sprinklers in ceiling which have
positive pressure in the space above.
After a 258"(67mm) diameter hole is cut in the ceiling, the
sprinkler is easily installed with the Model RC1 Wrench. A
Teflon*based thread sealant should be applied to the
sprinkler threads only. The Model RC1 Wrench is then
used to engage the sprinkler wrenching surfaces and to
install the sprinkler in the fitting. When inserting or
removing the wrench from the sprinkler/cup assembly,
care should be taken to prevent damage to the sprinkler.
DO NOT WRENCH ON ANY OTHER PART OF THE
SPRINKLER. The cover plate is then pushed onto the cup.
Final adjustment is made by hand turning the cover plate
until the skirt flange makes full contact with the ceiling.
Cover plate removal requires turning in the counter
clockwise direction.
After installation, inspect all sprinklers to ensure that there
is a gap between the cover plate and ceiling and that the
four cup slots are open and free from any air flow
impediment to the space above.
Concealed cover plate/cup assemblies are listed only for
use with specific sprinklers. The use of any other
concealed cover plate/cup assembly with the Model F1FR
Pendent Sprinkler or the use of the Model CCP Concealed
cover plate assembly on any sprinkler with which it is not
specifically listed my prevent good fire protection and will
void all guarantees, warranties, listings and approvals.
Maintenance
Model F1FR/CCP Concealed Sprinklers should be
inspected quarterly and the sprinkler system maintained in
accordance with NFPA 25. Do not clean sprinklers with
soap and water, ammonia or any other cleaning fluids.
Remove dust by using a soft brush or gentle vacuuming.
Remove any sprinkler cover plate assembly which has been
painted (other than factory applied) or damaged in any way.
A stock of spare sprinklers should be maintained to allow
quick replacement of damaged or operated sprinklers. Prior
to installation, sprinklers should be maintained in the original
cartons and packaging until used to minimize the potential
for damage to sprinklers that would cause improper
operation or non-operation.
Approval Organizations
1. Underwriters Laboratories, Inc.
2. Underwriters’ Laboratories of Canada.
3. NYC MEA 258-93-E
ULI Listing Category
Sprinklers, Automatic and Open.
Quick Response, Concealed
Ordering Information
Specify
1. Sprinkler Model F1FR
½²(13mm) orifice, ½²NPT (R½)
2. Sprinkler Temp. Rating:
135°F (56°C), 155°F (68°C), 175°F (79°C), 200°F (93°C)
3. Cover Plate Model: CCP
4. Cover Plate Thread size: ½²NPT (R½)
5. Cover Plate Temp. rating:135°F (56°C) for 135°F (56°C) and
155°F (68°C) Spks165°F (74°C) for 175°F (79°C) and 200°F
(93°C) Spks
6. Cover plate adjustment.
Either ½²(13mm) or 516²(approximate adjustment)
7. Cover Plate Finish
Installation Wrench
Model RC1 Sprinkler Wrench
Installation Aid
A protective cap is included for use during installation.
Note: Paint or any other coatings applied over the factory finish will
void all approvals and warranties. Sprinklers and cup/ cover plate
assemblies are packaged separately.
Important: The F1FR Sprinkler with Model CCP cover plate is not
an FM Approved combination.
Nominal
Orifice
"K" Factor Thread
Size Model
Temp. Rating Max.
Ambient
Temp Bulb Color Approvals
Sprinkler
Identification
Number(SIN)
US Metric Sprinkler Cover
12²(15mm) 5.62 81.0 12²NPT F1FR 135°F/57°C 135°F/57°C 100°F/38°COrange 1, 2, 3 R3615
12²(15mm) 5.62 81.0 12²NPT F1FR 155°F/68°C 135°F/57°C 100°F/38°CRed 1, 2, 3 R3615
12²(15mm) 5.62 81.0 12²NPT F1FR 175°F/79°C 165°F/74°C 100°F/38°CYellow 1, 2, 3 R3615
12²(15mm) 5.62 81.0 12²NPT F1FR 200°F/93°C 165°F/74°C 100°F/38°CGreen 1, 2, 3 R3615
Model F1FR Concealed Pendent Sprinkler
Technical Data
*DuPont Registered Trademark
Standard Finishes
Chrome
White
Special Applications Finishes
Bright Brass
Satin
Off-White
Black Paint
Black Plating
Cover Plate Finishes
2.
(1) Other finishes and colors are available. Consult factory for details.