19
Appendix 1. Checklist for configuration design
Listed below are check items before construction:
No. Item Judgment criteria Judgment/result
1 Power supply
capacity in PoE HUB
The power supply capacity is sufficient even if the
maximum number of gas detectors are connected
to the ports or the number of connected detectors
is restricted by design.
OK/NG
2 LAN cable
Anti-noise measures
The cable route is isolated from noise sources. OK/NG
3 RJ-45
Modular plug
selection
Plugs for stranded wire are not used for solid wire
cables.
Plugs for solid wire and stranded wire are not used
together.
OK/NG
4 LAN cable selection UTP Category 5 or Category 5e OK/NG
5 LAN cable length 80 m or less OK/NG
Appendix 2. System construction checklist
Listed below are the check items after construction.
No. Item Judgment criteria Judgment/result
1 LAN cable
Tension
The cable is not pulled tightly but is laid loosely. OK/NG
2 LAN cable
Bending
The bending radius is 25 mm or more. OK/NG
3 LAN cable
Binding
The cable is not bound tightly by cable ties, etc. OK/NG
4 LAN cable
Long distance parallel
cabling
The cables are not laid completely in parallel over
extended distances.
OK/NG
5 LAN cable
Isolation from noise
sources
The cable is isolated in racks dedicated for
communication or by separators.
OK/NG
The cable is kept away from noise sources.
[Reference]
From transformers and motors: 120 cm or more
From AC power cables: 30 cm or more
From fluorescent lamps: 13 cm or more
OK/NG
6 LAN cable
Treatment of excess
lengths of cable
When an excess length of cable is rolled in circles,
the diameters of the circles are varied.
OK/NG
7 LAN cable
Unwound portion
On termination, the length unwound is 12.7 mm or
less.
OK/NG
8 LAN cable
Test
Straight-through connection OK/NG
No wire breaks or short circuits OK/NG
Each cable is 80 m or less. OK/NG
9 LAN cable
Marking
Both ends are marked.
Example: Gas detector tag number
OK/NG
10 LAN cable
Securing
The cables are secured so that they will not come
loose even if subjected to a sudden force.
OK/NG
11 Grounding The gas detector case is grounded.
(Equivalent to Class D grounding)
OK/NG