
Rinnai 6 ES_FIM
REGULATIONS & CLEARANCES
The heater and the ue system shall be installed in accordance with the following:
• Manufacturer’s Installation Instructions • Current AS/NZS 3000, AS/NZS 3500 & AS 5601
• Local Regulations and Municipal Building Codes • Any other relevant Statutory Regulation
Before commencing an installation, read the installation sections of the ‘Customer and Installation
Manual’ supplied with the heater. Note that AS/NZS 5601 is referred to in this instruction and
was current at the time of printing, but may have since been superseded. It is the Installer’s
responsibility to ensure that requirements of the current version of AS/NZS 5601 are met.
These components MUST be installed, serviced and removed by an Authorised Person! ONLY the Rinnai ue
system components specied in this manual MUST be used. Components NOT specied in this manual, whether
manufactured by Rinnai or otherwise, are NOT compatible and MUST NOT be used!
Rinnai Energysaver space heater when correctly installed with Rinnai approved ue components are room-sealed
appliances and no internal ventilation is required. The Rinnai Energysaver space heater is fan-assisted. Therefore
the fan assisted ue clearance dimensions from AS/NZS 5601 extract shown on this page MUST be used.
The outer plastic section of the Co-Axial Flue complies with temperature hazard requirements and can be installed
with zero clearance to combustible material. Vertical clearances when using a roof terminal (ESROOFCOWL) are
shown in Fig.1. If in doubt contact the Rinnai Australia National Helpline (number on the back page).
Flue terminal Fan assisted flue appliance only Gas meter Electricity meter or fuse box Mechanical air inlet
Minimum Clearance 500 mm
ESROOFCOWL
Decktite or lead collar flashing
ESPLATE
ESPIPE900
Flue pipe clip supplied with ESPIPE900
Flue pipe clip supplied with ESROOFCOWL
Fan assisted
• Appliances up to 50 MJ/h input 200
• Appliances over 50 MJ/h input 300
b From the ground, above a balcony or other surface * 300
c Front a return wall or external corner * 300
d
From a gas meter (M) (see 5.11.5.9 for vent terminal location of regulator )
(see Table 6.6 for New Zealand requirements) 1000
e From an electricity meter or fuse box (P) † 500
500
f From a drain pipe or soil pipe 75
g Horizontally from any building structure* = or obstruction facing a terminal
h From any other flue terminal , cowl, or combustion air intake † 300
• Appliances up to 150 MJ/h input * 300
• Appliances over 150 MJ/h input up to 200 MJ/h input * 300
• Appliances over 200 MJ/h input up to 250 MJ/h input * 500
• Appliances over 250 MJ/h input * 1500
• All fan-assisted flue appliances , in the direction of discharge 1500
k From a mechanical air inlet, including a spa blower 1000
• Space heaters up to 50 MJ/h input 150
• Other appliances up to 50 MJ/h input 500
• Appliances over 50 MJ/h input and up to 150 MJ/h input 1000
• Appliances over 150 MJ/h input 1500
1Where dimensions c, j or kcannot be achieved an equivalent horizontal distance
measured diagonally from the nearest discharge point of the terminal to the opening
may be deemed by the Technical Regulator to comply.
2See Clause 6.9.4 for restrictions on a flue terminal under a covered area.
3See Figure J3 for clearances required from a flue terminal to an LP Gas cylinder.
A flue terminal is considered to be a source of ignition.
4
Ref. Item
a
Min. clearances (mm)
Below eaves, balconies and other projections:
j
Horizontally from an openable window, door, non-mechanical air inlet, or any other opening into a building
with the exception of sub-floor ventilation:
Vertically below an openable window, non-mechanical air inlet, or any other opening into a building with the
exception of sub-floor ventilation:
NOTES:
† - Prohibited area below electricity meter or fuse box extends to ground level.
FIGURE 6.2 (in-part) MINIMUM CLEARANCES REQUIRED FOR BALANCED FLUE TERMINALS, FAN-ASSISTED FLUE
TERMINALS, ROOM-SEALED APPLIANCE TERMINALS AND OPENINGS OF OUTDOOR APPLIANCES
* - unless appliance is certified for closer installation
For appliance snot addressed above acceptance should be obtained from the Technical Regulator.
n
Horizontal Clearances (Extract AS/NZS 5601 Fig. 6.2)
All Rinnai Energysaver space
heaters are fan assisted (forced
exhaust) appliances.
WARNINGS & IMPORTANT INFORMATION