The N56kWi ue diverter, code FFP100DIV, is manufactured from polypropylene. It has been
tested and can ONLY BE used with the Rinnai INFINITY N56kWi water heater. The ue diverter
is tested and approved for use with the a maximum ue gas temperature of 120 °C.
• Flue terminal must be compliant with ue terminal locations shown in AS/NZS 5601.1.
• Kit elbows count as two bends → subtract 6 m from the total ue length (minus 3 m per bend).
• Flue should terminate in the same direction and on the same wall as the air intake.
• If you don’t need to extend the full 1.5 m, you can just use the connecting pipe (1000 mm)
Important
Installation
Remove nose section from horizontal wall terminal
1. Underneath the exhaust nose is a slot in which a athead screwdriver can be placed.
2. Insert the screwdriver approximately 25 mm in and release the nose section.
3. Put the nose aside as this will be reinstalled with the elbow component of the diverter.
Install diverter elbows, pipe extensions, and nose
1. Place the 90 degree diverter elbow in the position where the nose terminal was removed.
2. Push the elbow into position, the correct position is reached if a click can be detected.
3. Insert the ue extension and connecting ue. If necessary these can be shortened. Fix the
extensions using the three wall brackets supplied. Fixings are not supplied—these must be
suitable for the wall material. The brackets have an o-centre xing
4. Install the second elbow in the top section of the extension, pointing away from the wall.
Reinstall the nose from the wall terminal in the elbow. Note the correct position of the nose, as
shown in image below.
Rectangular slot underneath nose
section of the wall terminal
Nose section removed
There is a small tab in the nose section
that needs to be released, this is what
holds it in place.
Wall bracket with
o-centre xing
Nose from the wall terminal
installed inside the elbow