
12
40752-195 (1) Eective 2/2011
Ground fault circuit breakers detect ground fault currents
through residual sensing (they are not designed to use
source ground or zero sequence ground fault sensing
methods). If the system neutral is grounded, but no phase
to neutral loads are used, the neutral current sensor is not
necessary.
If the system neutral is grounded and phase or neutral
loads are used, then the neutral current sensor (see Figure
5-1) must be used. It should be connected to the breaker
according to Figure 5-2.
The neutral sensor has the same ratio as the breaker cur-
rent sensors.
Note: The polarity of the sensor connections is critical.
Always observe the polarity markings on the installa-
tion drawings. To insure correct ground fault equip-
National Electric Code requirements under article 230-
95(C). See section 7 for testing instructions.
6. INSPECTION AND FIELD TESTING
Inspection
Circuit breaker should be inspected periodically. This
inspection can be best done during normal equipment
maintenance periods when no voltage to the equipment
is available. The inspection should include the following
checks 6-1 through 6-8.
VOLTAGES IN ENERGIZED EQUIPMENT CAN CAUSE
SEVERE PERSONAL INJURY OR DEATH BEFORE
INSPECTING THE CIRCUIT BREAKER IN AN ELECTRI-
CAL SYSTEM. MAKE SURE THE CIRCUIT BREAKER IS
SWITCHED TO THE OFF POSITION AND THAT THERE
IS NO VOLTAGE PRESENT WHERE WORK IS TO BE
PERFORMED. SPECIAL ATTENTION SHOULD BE PAID
TO REVERSE FEED APPLICATIONS TO ENSURE NO
VOLTAGE IS PRESENT.
SOME COMMERCIAL CLEANING AGENTS WILL DAM-
AGE THE NAMEPLATES OR MOLDED PARTS. MAKE
SURE THAT CLEANING AGENTS OR SOLVENTS USED
TO CLEAN THE CIRCUIT BREAKER ARE SUITABLE
FOR THE JOB.
6.1 Remove dust, dirt, soil, grease, or moisture from the
surface of the circuit breaker using a lint-free dry cloth,
brush, or vacuum cleaner. Do not blow debris into the cir-
cuit breaker. If contamination is found, look for the source
and eliminate the problem.
6.2 Switch circuit breaker to ON and OFF several times to
be sure that the mechanical linkages are free and do not
bind. If mechanical linkages are not free, replace circuit
breaker.
6.3 With the circuit breaker in the ON position, press the
PUSH-TO-TRIP button to mechanically trip the circuit
breaker. Trip, reset, and switch circuit breaker ON several
times. If mechanism does not reset each time the circuit
breaker is tripped, replace the circuit breaker.
6.4 Check base, cover, and operation handle for cracks,
chipping, and discoloration. Circuit breakers should be
replaced if cracks or severe discoloration is found.
6.5 Check terminals and connectors for looseness or signs
of overheating. Overheating will show as discoloration,
melting, or blistering of conductor insulation, or as pitting
or melting of conductor surface due to arcing. If there is
no evidence of overheating or looseness, do not disturb or
tighten the connections. If there is evidence of overheat-
ing, terminatons should be cleaned or replaced. Before
re-energizing the circuit breaker, all terminations and cable
should be refurbished to the same condition as when origi-
nally installed.
6.6 Check circuit breaker mounting hardware, and tighten
if necessary.
6.7 Check area where circuit breaker is installed for any
Exposure to certain types of chemicals can cause deterio-
ration of electrical connections.
7. PERFORMANCE TESTING FOR GROUND FAULT
CIRCUIT BREAKERS
7.1 Code Requirements
The National Electric Code under Article 230-95-C
requires that any ground-fault protection system be
5. Ground Fault