35
A
Torque level of the start up after an nvers on due to safety edge or ant crush ng
0 → start p not enable, the gate inverts with the torq e settled d ring the normal travel
1-8 → LEVEL (1 = minim m... 8 = maxim m)
8
36
A
Start up t mes
1-20 → SECONDS of the start p torq e
3
38
A
Release thrust:: when it receives an inp t and the gate is completely closed, it makes a closing for a time
settled and after it opens. It helps a release of electric lock.
0 → it normally starts and it does not make the inversion. The release thr st is not enable
1-99 → DECIMAL SECONDS time of the first closing
0
41 Slow-down speed
0 → slow speed d ring the slow-down
1 → very slow speed d ring the slow-down
2 → slow-down not enables
0
42
A
Sens b l ty to f nd an obstacle dur ng the normal travel
1-99 → sensibility (1=not sensible ... 99=max sensibility)
70
43
A
Sens b l ty to f nd an obstacle dur ng the slow-down
1-99 → sensibility (1=not sensible ... 99=max sensibility)
10
49
A
Automat c reclos ng chances after an nvers on due to safety edge or ant crush ng
0 → NOT a tomatic reclosing d e to safety edge or anticr shing
1-3 → n mbers of a tomatic reclosing chances d e to safety edge or anticr shing
0
50
A
Behav our f we nterrupt the beam of photocell 1 (FT1) dur ng the open ng
0 → IGNORE, it does nothing or FT1 is not instsalled
1 → STOP, the gate stops ntil the next inp t
2 → IMMEDIATELY INVERtS, so it makes a closing
3 → TEMPORARY STOP, when the beam is restored it contin es to open
4 → INVERTS when the beam is restored the gates inverts, so it makes a closing
0
51
A
Behav our f we nterrupt the beam of photocell 1 (FT1) dur ng the clos ng
0 → IGNORE, it does nothing or FT1 is not instsalled
1 → STOP, the gate stops ntil the next inp t
2 → IMMEDIATELY INVERtS, so it makes an opening
3 → TEMPORARY STOP, when the beam is restored it contin es to open
4 → INVERTS when the beam is restored the gates inverts, so it makes an opening
2
52
A
When the gate s closed t allows an open ng w th the beam of photocell 1 (FT1) nterrupted
0 → gate closed, NOT allowed the opening by the beam of photocell (FT1) interr pted
1 → gate closed, allowed the opening by the beam of photocell (FT1) interr pted
2 → when the beam of photocell (FT1) is interr pted, it ca ses an opening
0
53
A
Behav our f we nterrupt the beam of photocell 2 (FT2) dur ng the open ng
0 → IGNORE, it does nothing or FT2 is not instsalled
1 → STOP, the gate stops ntil the next inp t
2 → IMMEDIATELY INVERtS, so it makes a closing
3 → TEMPORARY STOP, when the beam is restored it contin es to open
4 → INVERTS when the beam is restored the gates inverts, so it makes a closing
3
54
A
Behav our f we nterrupt the beam of photocell 2 (FT2) dur ng the clos ng
0 → IGNORE, it does nothing or FT2 is not instsalled
1 → STOP, the gate stops ntil the next inp t
2 → IMMEDIATELY INVERtS, so it makes an opening
3 → TEMPORARY STOP, when the beam is restored it contin es to open
4 → INVERTS when the beam is restored the gates inverts, so it makes an opening
2
55
A
When the gate s closed t allows an open ng w th the beam of photocell 2 (FT2) nterrupted
0 → gate closed, NOT allowed the opening by the beam of photocell (FT2) interr pted
1 → gate closed, allowed the opening by the beam of photocell (FT2) interr pted
2 → when the beam of photocell (FT2) is interr pted, it ca ses an opening
0
56
A
When the gate s completely open, t closes after 6 seconds f the beam of photocells s nterrupted
0 → an interr ption of the beam of photocells when the gate is open, it does nothing
1 → when the gate is completely open it closes after 6 sec. if there is an interr ption of FT1
2 → when the gate is completely open it closes after 6 sec. if there is an interr ption of FT2
0
60
A
Enables break ng when the gate ach eves the l m t sw tch
0 → breaking OFF on limit switch
1 → breaking ON on limit switch
1
61
A
Enables break ng due to photocells
0 → breaking OFF on photocells
1 → breaking ON on photocells
1
62
A
Enables break ng due to STOP nput
0 → breaking OFF on STOP
1 → breaking ON on STOP
1
13