4. CONFIGURATION
4.1 Device programming
The address of factory new HRT82MF is ID=1 and such device is ready to communicate with HRC
series controller requiring no additional configuration. In case of operation with PR821-CH controller
it is necessary to configure the address ID=0.
If necessary, HRT82MF settings can be modified with RogerVDM software (available at
www.roger.pl) after connection to RUD-1 communication interface.
Fig. 5 HRT82MF and RUD-1 connection
Connection and configuration procedure
1. Connect device to RUD-1 communication interface according to fig. 5
2. Place jumper on MEM pins
3. Restart the device (place and remove jumper on RST pins or switch power supply off and on)
4. Install and start RogerVDM software
5. In the opened window select device, firmware version, communication channel and serial port
with connected RUD-1 –see fig. 5
6. Select
Connect
button, the software shall establish connection with the device and automatically
switch to configuration window
7. Enter required settings (configuration window is shown in fig. 7, while options are described in
table 4)
8. Select
Send to Device
button –the software shall upload new settings
9. Remove jumper from MEM pins
10.Restart the device (place and remove jumper on RST pins or switch power supply off and on)
Note:
During connection procedure placing jumper on MEM pins and restarting the device restores its
factory default settings.