EB 6126 EN 11
Operation
Span:
6. Set the input signal to 20mA using a
suitable ammeter. The output signal at
the test pressure gauge should indicate
the upper range value of 1.0bar. If an-
other value is indicated, readjust the
span accordingly with the SPAN adjuster.
7. Change the input signal abruptly from
the upper range value (20mA) to 0mA
(or gently tap the device) and check
whether the output signal assumes the
upper range value, e.g. 1.0bar. As the
adjustment of zero and span inuence
each other, recheck both values and cor-
rect them, if necessary.
8. Reactivate the switch-off electronics in the
4 to 20mA version at the switch (5), if
required.
Voltage signal as input:
For u/p converters (devices with [V] input)
proceed in the same way as already de-
scribed.
The pneumatic output signal, e.g. 0.2 to
1bar is assigned to the signal range 0 or 2
to 10V with the ZERO and SPAN adjusters
(see nameplate).
Converters with voltage input do not have
the switch-off electronic function.
Note
5 Operation
See Fig. 1 on page 6.
The device converts the input signal propor-
tionally into the output signal.
The signal ranges are specied on the name-
plate.
In case of a mounting position that is not
horizontal or when the pressure gauge/
screw plug does not face upwards, zero and
span can be corrected by approx. 10% us-
ing the electronics. To do this, proceed as
follows:
Example:
The output signal 0.2 to 1bar is to be as-
signed to an input signal of 4 to 20mA.
1. Unscrew the enclosure cover to access
the ZERO and SPAN adjusters on the cir-
cuit board.
Zero:
2. Connect a pressure gauge (minimum ac-
curacy class 1) to the converter output.
3. Set the supply air to at least 0.4bar
above the upper output signal range val-
ue and apply it to the device.
4. Deactivate the switch-off electronics in
the 4 to 20mA version at the switch (5).
5. Set the input signal to the lower range
value (4mA) using a suitable ammeter.
The output signal at the test pressure
gauge should indicate a lower range val-
ue of 0.2bar.
If this is not the case, readjust the zero point
accordingly with the ZERO adjuster.