10 EB 6126 EN
Connections
3. Place a screwdriver at the recess (4) and
lever the plug insert (3) out of the plug
connector case.
4. Run the wires for the input signal through
the cable gland of the plug connector
case to the terminals of the insert marked
1 (+) and 2 (–). Secure them with screws.
– For u/p converters (devices with [V]
input), additionally run the wire for the
auxiliary power 24V DC (+) to terminal
3.
– i/p converters (devices with [mA] in-
put) do not require a supply voltage.
5. Push the insert into the plug connector
case, making sure that the cable gland
points in the correct direction after the
plug connector case has been reassem-
bled (the plug connector case can be
mounted in all four directions, turned at
90° angles around the insert).
6. Plug the plug connector onto the device
and screw tight the screw (1).
4.2 Pneumatic connection
The pneumatic connections for supply air
(SUPPLY 8) and output (OUTPUT36) are de-
signed as threaded ports with G¼ or
¼–18NPT thread.
Customary ttings for metal tubing or plastic
hoses can be used.
Risk of property damage due to water en-
tering the device when a pipe is used to ex-
tend the vent pipe.
Make sure that no water can enter at the end
of an extension pipe (minimum cross-section
of 28mm² = 6mm inside diameter) connect-
ed to either vent elbow piece or directly to
the G or NPT connection.
Note
NOTICE
!