
14
8.
Select a location where the condensation water
2.
4.
5.
Selection of installation location
3.
Requirements for electrical connection
Air switch capacity
Indoor unit
3.
4.
Basic requirement
Installing the unit in the following places may cau-
se malfunction. If it is unavoidable, please consu-
lt the local dealer:
5.
6.
7.laundry.
1.
2.
5.
can be dispersed easily and won't affect other
people.
Safety precaution
2.
Select a location which is out of reach for chil-
dren and far away from animals or plants. If it
is unavoidable, please add the fence for safety
purpose.
1.
5.
6.
2.
It’s not allowed to be installed on
the unstable
or motive base structure
(such as truck) or in
the corrosive environment (such as chemical
factory).
3.
3.
Select a location which is convenient to conne-
ct the outdoor unit and near the power socket.
Grounding requirement
Do not put through the power before finishing
4.Make sure that the installation follows the req-
uirement of installation dimension diagram.
There should be no obstruction near air inlet
and air outlet.
4.Select a location which is out of reach for children.
Must follow the electric safety regulations w-
hen installing the unit.
2.
air emitted by the outdoor unit will not affect
neighborhood.
installation.
7.
If the supply cord is damaged, it must
be repla-
The location should be well ventilated and dry,
in which the outdoor unit won't be exposed dir-
ectly to sunlight or strong wind.
The location should be able to withstand the
weight of outdoor unit.
According tothe local safety regulations, use
Outdoor unit
1.Select a location where the noise and outflow
qualified power supply circuit and air switch.
7.
8.Please try your best to keep way from fluores-
cent lamp.
The yellow-green wire in air conditioner is
grounding wire, which can't be used for other
purposes.
An all-pole disconnection switch having a co-
ntact separation of at least 3mm in all poles
should be connected in fixed wiring.
The grounding resistance should comply with
weight of indoor unit and won't increase noise
and vibration.
The appliance must be installed 2.5m above
floor.
Don't install the indoor unit right above the ele-
ctric appliance.
1.
The place with sulfureted gas.
Other places with special circumstances.
The appliance shall not be installed in the
The place with strong heat sources, vapors,
flammable or explosive gas, or volatile objects
spread in the air.
The place with high-frequency devices (such
as welding machine, medical equipment).
The place near coastal area.
The place with oil or fumes in the air.
with national wiring regulations.
8.The temperature of refrigerant circuit will be hi-
4.Properly connect the live wire, neutral wire and
from the copper tube.
9.The appliance shall be installed in accordance
6.
1.T
he air conditioner is the first class
electric
3.
appliance. It must be properly grounded with
specialized grounding
device by a professional.
Please make
sure it is always grounded effecti-
vely, otherwise it may cause electric shock.
ced by the manufacturer, its
service agent or
similarly qualified
persons in order to avoid a
hazard.
national electric safety regulations.
The appliance must be positioned so tha t the
p
l
u
g is accessible.
The location should be able to withstand the
Make sure the power supply matches with the
requirement of air conditioner.
Unstable power
supply or incorrect wiring or malfunction. Pl-
ease install proper power supply cables before
using the air
conditioner.
gh, please keep the interconnection cable away
grounding wire of power socket.
5.Be sure to cut off the power supply
before pr-
oceeding any work related to
electricity and safety.
Including an air switch with suitable capacity,
please note the following table . Air switch sh-
ould be included magnet buckle and heating
buckle function, it can protect the circuit-short
and overload. (Caution: please do not use the
fuse only for protecting the circuit)
Air-conditioner Air switch capacity
09K、12K 10A
18K 16A
24K 25A